Contrel EMM-D4h Instruction Manual Download Page 8

 

EMM-D4h 

instruction manual 

IM443-U v0.7 

pag. 8  

Programming

 

of

 

the

 

address

 

for

 

the

 

communication

 

network

 

(

SET

 

ID

 

ADR

)

 

(only

 

for

 

vers.

 

with

 

serial

 

output) 

After the confirm with the 

A

 key of the previous value, the message 

ID aDR

 will appear

 

on 

F

 display; to set the value 

that will identify the instrument when it will be connected in a EIA485 communication network, proceed with the 
modality, already described. The settable values are from 1 to 247. To confirm, press the 

A

 key. 

 

Programming of the baud rate (

SET BDR

) (only for vers. with serial output) 

The

 

following

 

setting

 

is

 

the

 

baud

 

rate.

 

The

 

message

 

SET

 

appears

 

on

 

G

 

display,

 

the

 

message

 

SET BDR

 

on

 

the

 

first

 

two

 

parts

 

of

 

F

 

display

 

to

 

indicate

 

the

 

programming

 

of

 

the

 

baud

 

rate

 

displayed

 

on

 

the

 

third

 

part

 

(L3)

 

o

f

 the

 

F

 

display.

 

To

 

modify

 

the

 

value

 

set,

 

it’s

 

necessary

 

to

 

use

 

the

 

C

 

key

 

to

 

decrease

 

and

 

B

 

to

 

increase

 

the

 

rate.

 

The

 

values

 

settable

 

are: 

19.2

 => 19200 

baud 

9.60

 => 9600 

baud 

4.80

 => 4800 

baud 

2.40

 => 2400 

baud 

Press 

A

 to confirm the value displayed. 

 

Programming of the serial parameters (only for vers. with serial output) 

On 

G

 display will appear the message 

SET

. The following message will appear on 

F

 display using the 

B

 and 

C

 keys. 

To confirm press the 

A

 key. 

8 1

 

8 data bit / 1 stop bit

 

PAR

 

No parity

 

NO 

8 2

 

8 data bit / 2 stop bit  

PAR

 

No parity 

NO 

8 1

 

8 data bit / 1 stop bit

 

PAR

 

Even parity 

EVE 

8 1

 

8 data bit / 1 stop bit 

PAR

 

Odd parity 

ODD 

 

Programming of the Password (

SET PAS

The instrument is supplied without password. When a password (from 0002 to 9999) is set, using the 

B

 (to increase), 

C

 (to decrease) and 

A

 (to confirm) keys, only who know this value can to enter in the setup. The password, in fact, is 

required all the time that someone try to enter in the setup (pressing the 

A

 and 

B

 key at the same time). If the 

password is wrong, the message 

PASS ERR

 will appear on 

F

 display and the instrument go back to the measures 

visualization. To input the password, when required by the instrument, at the enter of the setup, use the 

A

B

 and 

C

 

keys as the same way done previously. 

 

The menu is cyclic. After the last setting, the instrument go back to the first page of Setup (SETUP). It’s always 
possible to come back to measures visualization mode pressing at the same time the 

A

 and 

C

 keys.

 

 

PEAK VALUES AND ENERGY COUNTERS RESET (

RESET

From the measures visualization mode, pressing the 

A

 and 

C

 keys simultaneously the message 

SETUP

 will appear 

on 

F

 display, press the key 

C

 until the message 

RESET

 appears on the same display. To accede to the menu, press 

the 

A

 key. Now it’s possible to select the enabling of cancellation type, by pressing the 

C

 key, according with following 

types: 

RESET PEA

: all maximum value will be delete. 

RESET AVG

: all average and average maximum value (maximum demand) will be delete. 

RESET EN

: with 

NORMAL

 as energy mode (

EN

) the total energy counters will be delete, with 

TOT PAR

 the 

partial energy counters will be delete (as when the digital input is closed) and with 

TB1 TB2

 the band 

counters will be delete. 

RESET ALL

:  to delete average maximum values and energy counters. 

 

Entry to menu: 

seT UP 

  seT Up 

 

RESET 
SET DO1 
SET DO2 
SET AN OUT 
SET HR_ 
--- OFF OFF

  

(the visualization depends on the settings and the I/O status)

 

 

RESET PEA 

NO

 / 

YES

 

 

Confirm Reset

 

Deleting maximum values (max) 

RESET AVG 

NO

 / 

YES

 

 

Confirm Reset

 

Deleting average values (avg) 
and maximum demand (maxD) 

RESET EN 

NO

 / 

YES

 

 

Confirm Reset

 

Deleting energy counters 

RESET ALL 

NO

 / 

YES

 

 

Confirm Reset

 

Deleting maximum and average 
values, and energy counters 

 

To enable the chosen type, press the 

B

 key to change the indication on display 

G

 from 

NO

 to 

yes

Confirm enabling cancellation, by pressing the 

A

 key. The indication on display 

G

 change from 

yes

 to 

---

Summary of Contents for EMM-D4h

Page 1: ...s version with analog output OPTIONS Power Supply 20 60 Vac dc C1 Power Supply 90 250 Vac dc C2 Current Input 1A 1A Insulated current inputs t Neutral current input n Digital input DI it s not availab...

Page 2: ...Vac dc version Terminals Power Supply Terminals Power Supply Terminals Power Supply 19 20 0 110V 100 125Vac 50 60Hz 19 21 20 60Vac 24 72Vdc 19 21 85 230Vac 90 250Vdc 19 21 0 230V 220 240Vac 50 60Hz 1...

Page 3: ...28 29 30 31 32 33 34 35 36 EMM D4hp 485 EMM D4hp 485 A S2 S2 S1 S1 VL3 VL2 VL1 N S1 S2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 CURRENT INPUT S VOLTAGE INPUTS IL1 IL2 IL3 S2 S1 In 400V COM 230V B...

Page 4: ...measure voltage inputs auxiliary power supply P1 P1 P1 P2 S1 S1 S1 S2 N L1 L2 L3 S2 S2 S2 S1 S1 S1 I1 I2 I3 VL1 VL2 VL3 N measure current inputs measure voltage inputs 0 110 230 400 auxiliary power su...

Page 5: ...s Using the A and B keys the display indicates the maximum and average values G display for the visualization of the electrical measure indicated in LED E energy counters excluded The voltage values a...

Page 6: ...nchronism 50 type 60 version with digital output seT PUL SE 10 0 kW kVAr pulse Set pulse weight 01 0 kW kVAr pulse 0 10 kW kVAr pulse 0 01 kW kVAr pulse version with digital output seT TPL Increase fr...

Page 7: ...g Programming of the average time seT AVG T After the programming phase previously described pressing another time the A key on the F display will appear the message AVG T and the average time settabl...

Page 8: ...B key at the same time If the password is wrong the message PASS ERR will appear on F display and the instrument go back to the measures visualization To input the password when required by the instr...

Page 9: ...R HI and ALR LO With ALR SYS 123 the digital output will function as alarm verifying that the maximum value of the single phases doesn t exceed the maximum threshold set ALR HI and that the minimum va...

Page 10: ...the set SET THE HIGH AND THE LOW THRESHOLDS On F display will appear the message ALR Hi with the high threshold value confirming with the A key on the same display will appear the message ALR LO with...

Page 11: ...ng the C key the message SET AN OUT will appear on the F display To accede to the menu programming press the A key the message SET will appear on the G display on the F display and on D led bar will a...

Page 12: ...ge appears in F displays on the first part L1 the status of digital input on the second part L2 the status of the first digital output DO1 on the third part L3 the status of the second digital output...

Page 13: ...the segment of the right digit of the G display in correspondence of h on the front panel turn on to indicate the visualization of the apparent energy counter To complete the visualization the led k o...

Page 14: ...1 max avg I L2 max avg I L3 max avg I N max avg max maxD avg maximum of average phase and neutral currents max demand three phase power W max avg VAr max avg VA max avg max maxD avg maximum of average...

Page 15: ...nnect various instruments in the same network The maximum suggested length for a RS485 connection is 1200m For longer distances provide the use of low attenuation cables or signal amplifiers On the sa...

Page 16: ...OUTPUTS digital outputs Two outputs with common optomos 12 230Vac dc max 150mA insulation 3kV for 60 seconds Pulse Function Weight programmable 0 01 0 1 1 10 kWh pulse Pulse duration 100 200 300 400...

Reviews: