SERIAL LINE CONNECTIONS 

As shown in the diagram, it is necessary to place a serial RS232/485 converter between the RS232 PC's outlet and 
the EMM instrument/s. 
In serial line over 500 mt, it’s necessary to insert a line termination resistance (Rt=100÷120 ohm) between the twisted 
pair of cables, placing it between the converter and the end of the network (last instrument connected). With a 
shielded cable it’s necessary to connect the shield to earth. Use always twisted cables with minimum section of 
0,36mm

2

 (22AWG) and lower capacity of 60 pF/m (i.e.: BELDEN cable type EIA RS485-Ref.3105A). 

Should it be the case of long distance networks, ambiences where there have been placed energy transporting cables 
or ambiences subject to be electrically disturbed, it is suggested to use 100÷120ohm 1/2W resistors, placed between 
the common of the RS485 outlet and the shielded cable. 
For other information on the serial line it’s better to see the manual of EMI1 serial converter. 

EIA485 INTERFACE COMUNICATION (RS485) 

It is possible to exchange information between the instrument and a PC, PLC or other compatible system, through the 
asynchronous serial line RS485. 
The interface EIA485 allows a multi-drop connection, in order to connect various instruments in the same network. 
The maximum suggested length for a RS485 connection is 1200m. 
For longer distances provide the use of low attenuation cables or signal amplifiers. 
On the same RS485 it is possible to install up to 32 units, beyond this number of units it is required to place a signal 
repeater, each one of them will be able to manage up to 32 instruments. 
The higher is the number of connected instruments on the same serial line, the lower will be their response speed. 

RS485/232 converter 

RS485/232 converter 

Max 32 EMM; max  300 meters

Max 32 EMM; max  1200 meters

R=120

A1
B1

A2

B2

serial converter EMI1

C1

R1*

R2*

C2

LINE 1

LINE 2

]

]

RS232

RS485

R=120

A1
B1

A2

B2

serial converter EMI1

C1

R1*

R2*

C2

LINE 1

LINE 2

]

]

RS232

RS485

CONNECTION WITH NOT SHIELDED CABLE

CONNECTION WITH SHIELDED CABLE

Summary of Contents for EMM-4h

Page 1: ... output alternative to digital input option digital output serial output RS485 insulated current inputs neutral current input digital input alternative to analog Output option MEASURED PARAMETERS parameters unit of measurement initial identification phase and three phase voltages V kV V L1 N V L2 N V L3 N Σ V L N phase to phase and three phase system voltages V kV V L1 L2 V L2 L3 V L3 L1 Σ V L L p...

Page 2: ... 240Vac 50 60Hz 1 4 0 400V 380 415Vac 50 60Hz 1 3 20 60Vac 24 72Vdc 1 3 85 230Vac 90 250Vdc It s possible for example to take the auxiliary power supply between phase and neutral in a 4 wires system or phase phase in a 3 wires system without neutral or from a VT in a medium voltage application measure voltage inputs 4 terminals are available for the connection to the 3 phase and neutral of the net...

Page 3: ... measure voltage inputs auxiliary power supply P1 P1 P1 P2 S1 S1 S1 S2 N L1 L2 L3 S2 S2 S2 S1 S1 S1 I1 I2 I3 VL1 VL2 VL3 N measure current inputs measure voltage inputs 0 110 230 400 auxiliary power supply N B on line with 3 wires without neutral or with neutral not supplied the N terminaln must not be connected INSERTION ON THREE PHASE LINE WITH 4 WIRES EMM imeasure voltage inputs Voltage inserti...

Page 4: ...ing the A and B keys the display indicates the maximum and average values G display for the visualization of the electrical measure indicated in LED E energy counters excluded The voltage values are referred to the three phase system The k LED displays the reading in kilo x 1000 Using the C key the display indicates the type of the energy displayed Using the A and B keys the displays indicate the ...

Page 5: ...synchronism 50 type 60 version with digital output seT PUL SE 10 0 kW kVAr pulse Set pulse weight 01 0 kW kVAr pulse 0 10 kW kVAr pulse 0 01 kW kVAr pulse version with digital output seT TPL Increase from 100 to 500 mS in step by 100 mS Decrease version with serial output seT ID ADR Increase Set address of network from 001 to 247 Decrease seT SER BDR Set baud rate 19200 baud 19 2 serial interface ...

Page 6: ...g Programming of the average time seT AVG T After the programming phase previously described pressing another time the A key on the F display will appear the message AVG T and the average time settable from 1 to 30 minutes To increase the value press the B key To decrease it press the C key To confirm it press the A key The average time is the time used to calculate the average parameters avg and ...

Page 7: ...B key at the same time If the password is wrong the message PASS ERR will appear on F display and the instrument go back to the measures visualization To input the password when required by the instrument at the enter of the setup use the A B and C keys as the same way done previously The menu is cyclic After the last setting the instrument go back to the first page of Setup SETUP It s always poss...

Page 8: ... HI and ALR LO With ALR SYS 123 the digital output will function as alarm verifying that the maximum value of the single phases doesn t exceed the maximum threshold set ALR HI and that the minimum value of the single phases doesn t come down the minimum threshold set ALR LO The activation of the alarm output will come after some seconds of delay set ALR DL In the REMOTE mode the output status will...

Page 9: ...the set SET THE HIGH AND THE LOW THRESHOLDS On F display will appear the message ALR Hi with the high threshold value confirming with the A key on the same display will appear the message ALR LO with low threshold value The B to increase and C to decrease keys are used to set the high and the low thresholds values The range depends by the parameter and it is linked to the CT and VT ratios Pressing...

Page 10: ...sing the C key the message SET AN OUT will appear on the F display To accede to the menu programming press the A key the message SET will appear on the G display on the F display and on D led bar will appear the parameter to link to the analog output and selectable pressing more time the B key Pressing the A key to confirm the parameter selected SET THE HIGH AND THE LOW THRESHOLD Now it s necessar...

Page 11: ...age appears in F displays on the first part L1 the status of digital input on the second part L2 the status of the first digital output DO1 on the third part L3 the status of the second digital output DO2 The visualization of the digital input status activated that is supplied and deactivated that is not supplied depends of the type of energy visualization NORMAL TOT PAR e TB1 TB2 With NORMAL the ...

Page 12: ...he voltage values are of the three phase system the frequency is of the L1 channel Visualization energy and hours counters With the C key it s possible to visualize on F display the active reactive and apparent energy counters One segment of the right digit of the G display in correspondence of the kWh and KVArh on the front panel turn on to indicate the visualization of the active and reactive en...

Page 13: ...L3 max avg I N max avg phase and neutral currents maximum of average phase and neutral currents max demand max maxD avg Σ W max avg Σ VAr max avg Σ VA max avg three phase power maximum of average three phase powers maximum demand max maxD avg I L1 avg I L2 avg I L3 avg I N avg phase and neutral currents average phase and neutral currents max maxD avg Σ W avg Σ Var avg Σ VA avg three phase power av...

Page 14: ...on the serial line it s better to see the manual of EMI1 serial converter EIA485 INTERFACE COMUNICATION RS485 It is possible to exchange information between the instrument and a PC PLC or other compatible system through the asynchronous serial line RS485 The interface EIA485 allows a multi drop connection in order to connect various instruments in the same network The maximum suggested length for ...

Page 15: ...ual IM442 U v0 7 pag 15 DIMENSIONS 96 96 81 14 9 90 92 92 R3 cut out panel flush mounting for panel DIN 43700 M L1 L2 L3 k k kWh kVArh h max avg V A P F W VAr VA V L N L L VL N Hz C VL L A N ΣL EMM 4h electrical multi meter ...

Page 16: ...UTS OUTPUTS digital outputs Two outputs with common optomos 12 230Vac dc max 150mA insulation 3kV for 60 seconds Pulse Function Weight programmable 0 01 0 1 1 10 kWh pulse Pulse duration 100 200 300 400 500 milliseconds selectable DO1 active energy pulse output accumulated Tb1 Tb2 DO2 reactive energy pulse output accumulated Tb1 Tb2 digital Input Changing time band function or reset partial counte...

Reviews: