A remote push-button key can be connected to the Logic Inputs as shown
below in Figure 10.
Figure 10 Logic Inputs Connection Diagram
Outputs
The advanced option for the instrument provides two opto-isolated output
ports. Either or both can be used for 4-20 mA or pulse outputs.
CAUTION
Due to the dual-purpose nature of the outputs, take care not to
set the output as an open collector pulse type signal when
connected to a 4-20 mA loop circuit.
4-20 mA Output Connection
Figure 11 shows the connections for a 4-20 mA output. Output channel 1
uses terminals 27 (+) and 28 (-), output channel 2 uses terminals 29 (+) and
30 (-).
Maximum Load Resistance = (Supply-9) / 0.02 ohms
C-
23
Logic Input
22
24
25
26
1+
2+
3+
4+
Signal Ground