Programming
14
4.1 PROGRAM STEPS
Step
Comment
Scaling Factor - whole numbers.
Scaling Factor - digits after the decimal point.
The Scaling Factor is the pulses per unit of measure
(e.g.pulses/litre, pulses/gallon, etc). The Scaling Factor
can be programmed in the range of 0.0001 - 999,999.
Decimal Point for Total Display.
The total and preset quantity can be displayed with 0, 1,
2 or 3 decimal point places.
Start Time Delay.
The time in seconds (0-9 sec) when Output 2 will
switch "on" once the RUN key is pressed.
Prestop Quantity
The quantity at which Output 2 will switch "off"
before the end of the batch (Eg. If the Preset quantity
is 100 litres and the Prestop quantity is 2 litres,
Output 2 will switch off after 98 litres.)
Signal Timeout.
A time period between 0-99 seconds during which,
if there is no flow measured, the Outputs will both
switch "off" and the PAUSE message will be
displayed.
Batch Limit.
This value determines the maximum preset value
that may be entered by the operator. A value of
zero for the batch limit disables this feature.
Software Version.