Continental Hydraulics CEM-AC-E0-A Installation Manual Download Page 5

                    Continental Hydraulics Installation Manual                                

Page 5 of 8

CEM-AC-A

CHI 1013472    April 2012

Command input with Voltage:

The CEM-AC-E0 can accept voltage signals for commanding valve performance.

An analog command source voltage may be either “differential” or “ground referenced”.

             

2

4

+24v

1

3

Power Supply

Gnd

Line

AC

DC

Analog Command Source
"Differential Voltage"

(PLC, Digitial Motion
Controller, etc.)

+

-

CEM-AC-

E0

             

2

3

4

+24v

1

3

Power Supply

Gnd

Line

AC

DC

Analog Command Source
"Ground Referenced Voltage"

(PLC, Digitial Motion
Controller, etc.)

Gnd

+

CEM-AC-

E0

-

All ground based reference voltages must have a connection to Pin 3.

          

2

3

4

+24v

1

3

Power Supply

Gnd

Line

AC

DC

Gnd

CEM-AC-

E0

+10v

potentiometer

( 5k ohm typical)

Gnd

External

Voltage

Reference

Command input with current:

The CEM-AC-E1 can accept current signals for commanding valve performance.

The CEM-AC-E1 has a 390 ohm resistor inserted across terminals 2 and 4.  This resistor
converts the current to a voltage.  This voltage is measured by the differential amplifier to become
the module command.

Input current range is 0 to +/- 20 mA, and is  typically used at 4 to 20mA.  This current is
converted to voltage, and software scale and offset parameters are applied to meet system
requirements.

2

4

+24v

1

3

Power Supply

Gnd

Line

AC

DC

CEM-AC-

E1

4 to 20mA

Transmitter

A

Line

AC

DC

Loop Monitor

(optional)

Power Supply

Summary of Contents for CEM-AC-E0-A

Page 1: ...riety of system requirements All variables are user adjusted with easy to use software on your Microsoft Windows laptop Control variables are stored in non volatile memory internal to the module All v...

Page 2: ...0v or 4 to 20 mA Communication Gray Ground via DIN plug Command Return Black CEM AC E0 voltage input CEM AC E1 current input u c w Wiring Example 3 1 2 5 4 communications 12 30vDC Ground 0 to 10v Grou...

Page 3: ...ference such as motor controllers and high power contactors Power Supply This amplifier module is designed to operate on DC power from a regulated power supply ranging from 12 to 30 volts Match valve...

Page 4: ...ule has a software adjustable dead zone near zero termed TRIGGER With a command in this near zero area neither solenoid will be energized Trigger is intended to keep small noise signals on the analog...

Page 5: ...ages must have a connection to Pin 3 2 3 4 24v 1 3 Power Supply Gnd Line AC DC Gnd CEM AC E0 10v potentiometer 5k ohm typical Gnd External Voltage Reference Command input with current The CEM AC E1 ca...

Page 6: ...ult Setting POL to will change the 0 to 100 valve operation to 100 to 0 Adjustment of SENS internal monitoring function SENS parameter has two options ON default and OFF The CEM AC E0 is able to monit...

Page 7: ...hin this 20v range A B allows for a decimal scaling factor These two numbers are chosen to provide a gain to the input signal A and B are positive or negative whole numbers up to 10000 Default A 1000...

Page 8: ...are actually time to ramp for a 0 to 100 signal change For example a value of 2000 will give a ramp time of 2 seconds for a 0 to 100 step command The ramp time will be 1 second for a step command of 0...