![Continental Fireplaces CEFL50H Installation And Operating Instructions Manual Download Page 9](http://html1.mh-extra.com/html/continental-fireplaces/cefl50h/cefl50h_installation-and-operating-instructions-manual_2657126009.webp)
Measurements are taken from the body.
Sides, back and top 0"
A.
Once the rough opening has been prepared, and the power has been routed to the left side of the
recess, the appliance may be installed.
B.
Lift the appliance up to the opening, maintaining the 0.5" (12.7mm) clearance to the sides.
C.
The electrical connection must be made prior to sliding the appliance into place. (See "HARD WIRE
INSTALLATION" section.)
D.
Using the 4 screws provided, level the appliance and use the retaining brackets to secure the
appliance to the to the wall.
NOTE: In order to avoid the possibility of exposed insulation or vapour barrier coming in contact
with the appliance body, it is recommended that the walls of the appliance enclosure be "fi nished"
(ie. drywall/sheetrock), as you would fi nish any other outside wall of a home. This will ensure that
clearance to combustibles is maintained within the cavity.
17 1/2"
445mm
45"
1143mm
3 1/2"
89mm
17 1/2"
445mm
45"
1143mm
MIN
Finishing Material
Due to the many different fi nish materials used on walls, it is highly recommended that you consult your local
builder before you install this appliance in the wall.
Select a location that is not prone to moisture and is located at least 36" (914.4mm) away from combustible
materials such as curtain drapes, furniture, bedding, paper etc.
3.4 RECESSING
INSTALLATION
3.4.1 MINIMUM CLEARANCE TO COMBUSTIBLES
3.4.2 FRAMING
(NON-LOAD
BEARING)
EN
W415-1527 / 07.16.15
9