Contemporary Controls CTRLink EISC-100T Installation Manual Download Page 6

 

TD021000-0IF 

 

Operation 

Switching 

The  EISC  uses  an  8K-address  look-up  table  augmented  with  64  entries  of 
Content Addressable Memory.  A hashing algorithm is used to update the table.  
Addresses are aged in about 300 seconds.  Runt packets (less than 64 bytes) and 
oversize packets (greater than 1536 bytes) are discarded. 

Data Storage 

Data storage buffer for Ethernet packets consists of 156 k bytes of SSRAM. 

Data Forwarding 

An entire Ethernet packet must be received before forwarding occurs. 

Flow Control 

Each  port  automatically  negotiates  flow  control  for  either  half-  or  full-duplex 
operation,  if  auto-negotiation  is  enabled.    In  full-duplex  mode,  the  PAUSE 
function  is  supported.    In  half-duplex  mode,  the  backpressure  method  is  used.  
When  flow  control  is  disabled,  the  destination  port  of  an  incoming  packet  is 
checked and, if found to be congested, the packet is discarded to avoid blocking 
the packet stream. 

Broadcast Storm Control 

Using  a  storm-control  counter,  each  port  will  pass  64  continuous  broadcast 
packets before dropping extra ones.  The counter will reset every 800 ms or after 
receiving a packet whose Device ID is other than ff ff ff ff ff ff. 

LED Indicators 

P

 (green) 

Power

.  Glows when power is supplied to the EISC. 

(Numbered LEDs)

  

(green/yellow) 

Link/Activity

.    Each  port  has  an  LED  that  glows  if  a  link 

exists: 

green

  for  100  Mbps  operation  or 

yellow

  for  10 

Mbps operation.  It flashes as data transfer occurs. 

S

 (green)

 

Fault Relay Status

.  This LED functions in accordance with 

its configuration setting.  See the User Manual for details. 

Ports 

All ports are wired MDIX — allowing DTE equipment to connect via straight-
through cables — except that Port 16X is wired MDI to permit the cascading of 
switches without the need of a crossover cable.   Note that Port 16 and Port 16X 

cannot be used simultaneously

Advanced Operation 

Advanced  operation  (requiring  a  null-modem  cable)  is  explained  in  the  User 
Manual located on the provided CD-ROM. 

Summary of Contents for CTRLink EISC-100T

Page 1: ...versatile of Industrial Ethernet switches available Configuration is accomplished via a console port connected to a Windows based configuration program included with the product Modbus protocol and r...

Page 2: ...re 0 C to 60 C Storage temperature 40 C to 85 C Humidity non condensing 10 to 95 Functional Aging typical 300 seconds Compliance ANSI IEEE 802 3 RJ 45 Connector Pin Assignments PIN MDI X Port 16X 1 TD...

Page 3: ...e enclosure with two 4 40 pan head screws If the clip is removed the unit can be panel mounted by extending the top and bottom brackets which are shipped in retracted position The extended brackets ca...

Page 4: ...maximum current value commensurate with 12 watt power consumption Power conductors should be sized accordingly Ground is directly connected to zero volts and the equipment chassis is isolated from ze...

Page 5: ...e AI XFMR is for 120 VAC The AI XFMR E is for use with 230 VAC Figure 4 AC Powered Figure 5 AC Powered with Grounded Secondary AC Powered with Battery Backup The EISC can also operate in the AC mode w...

Page 6: ...ed to avoid blocking the packet stream Broadcast Storm Control Using a storm control counter each port will pass 64 continuous broadcast packets before dropping extra ones The counter will reset every...

Page 7: ...s delivered and does not cover repair of products that have been damaged by abuse accident disaster misuse or incorrect installation User modification may void the warranty if the product is damaged b...

Page 8: ...TD021000 0IF 8 This page is deliberately left blank...

Reviews: