
UM-15090500-AA1
Page
34
Object name
Type &
Instance
Readable/
Writable
Description
Range and Definition
Current Dew Point
AI 5
R
Current Dew Point (
221CH
models only
)
-999~9999: -99.9
~
999.9
°C/°F
Current CO
2
Reading
AI 6
R
Current CO
2
Reading
0~3000: 0~3000 ppm
Control Valve
Feedback
AI 7
R
Control Valve Feedback
0
~
1000 (0.0%
~
100.0%)
Modulating/
Floating Output 1
AI 8
R
Modulating/ Floating Output
1
0~100: 0
~
100 %
Modulating/
Floating Output 2
AI 9
R
Modulating/ Floating Output
2
0~100: 0
~
100 %
Modulating Fan
Output
AI 10
R
Modulating Fan Output
0~100: 0
~
100 %
CO2 Control Output
Percentage
AI 11
R
CO2 Control Output
Percentage
0~100: 0
~
100 %
Voltage Input Value
AI 12
R
Voltage Input Value
0
~
150 (0.0
~
15.0 VDC)
AI 1
Percentage
AI 13
R
Analog Input 1 Percentage
Value
0
~
1000 (0.0%
~
100.0%)
AI 2
Percentage
AI 14
R
Analog Input 2 Percentage
Value
0
~
1000 (0.0%
~
100.0%)
AI 3
Percentage
AI 15
R
Analog Input 3 Percentage
Value
0
~
1000 (0.0%
~
100.0%)
Cooling Temperature
Setpoint
AV 0
R/W
Cooling Temperature Set
Point
°C :0~500 (0.0
~
50.0
℃
)
°F: 320~1220
(32.0~122.0°F)
Space
Temperature
Via BACnet
AV 1
R/W
BACnet
Assigned Current
Temperature
-999~9999
(-99.9
~
999.9
℃
/°F)
Timer Off
AV 2
R/W
Timer Off (Only for Models
with Countdown Timer
Function
Available).
0~24: 0~24 Hours Count
Down
0: Disable
Heating Temperature
Setpoint
AV 3
R/W
Heating Temperature Set
Point
-999~9999: -99.9
~
999.9
℃
/°F
Hr-Running Time
AV 4
R/W
Running Time of Valve (Hr.)
0~65535 (Hr.) For
Reading But 0~30000 (Hr.)
For Writing.
M-Running Time
AV 5
R/W
Running Time of Valve
(M.)
0~59 (Minute)
Sec-Running
Time
AV 6
R/W
Running Time of Valve
(Sec.)
0~59 (Sec.)
Deadband
AV 7
R/W
Deadband
°C: 0~100 (0.0~10.0 °C)
°F: 0~180 (00~18.0 °F)
Unoccupied Cool
Setpoint
AV 8
R/W
Unoccupied Cooling Setpoint
°C: 250~300 (25.0~30.0°C)
°F: 770~860 (77.0~86.0°F)
Unoccupied Heat
Setpoint
AV 9
R/W
Unoccupied Heating
Setpoint
°C: 100~220 (10.0~22.0°C)
°F: 500~715(50.0~71.5°F)