1.5  RX Controller Location 

It  is  essential  the  Controller  is  positioned  in  the 
same room as the air curtain. It should be where its 
temperature  will  not  be  change  with    local  effects. 
Avoid: 

• 

Draughty places near windows or doors 

• 

Places near the air curtain itself or any other 
heat sources in the room 

• 

Place where the sun will shine on it 

• 

Places where it may get wet 

 

 

 

 

 

1.6 Controller standard models 

The  RAC1306  and  RAC1309  heaters  are  supplied 
with  a  remote  controller.  The  remote  control  unit 
houses 3 single pole and 1 change over 10A rocker 
switches. The controller is wired to the base unit via 
0.75mm² 5 core PVC flexible cable.  
 

 

 

1.7  Clearance Distances

 

 

It  is  recommended  that  a  minimum  clearance  of 
100mm  is  allowed  around  the  case  and  55mm 
above.  The  clearance  allows  for  cable  entry  and 
prevents combustible surfaces overheating.  

 

The minimum mounting height (floor to grille) is 2m. 
The  maximum  mounting  height  for  RAC1306  is 
2.8m and for RAC1309 is 3.4m. 

1. General Information 

1.1  Introduction 

The heaters are designed for discreet positioning in 
a suspended ceiling or bulkhead in the doorways of 
retail  or  commercial  premises.  Overall  energy  sav-
ing  is  likely  when  the  heater  is  sited  above  a  fre-
quently  opened  external  door  as  the  airstream  can 
prevent  heat  loss.  Will  fit  a  recess  as  shallow  as 
195mm. 

1.2  General

 

All  installations  must  be  in  accordance  with  the 
regulations in force in the country of use. 

These  instructions  must  be  handed  to  the  user  on 
completion of the installation. 

Installers  and  service  engineers  must  be  able  to 
demonstrate  competence  and  be  suitably  qualified 
in  accordance  with  the  regulations  in  force  in  the 
country of use. 

To ensure continued and safe operation it is recom-
mended that the appliance is serviced annually.  

The heater outlet / inlet must not be obstructed dur-
ing use. 

1.3  Electrical Supply 

 

Electrical  supply  for  RAC1306  and  RAC1309  is  ei-
ther  230V  single  phase  or  415V  three  phase,  Neu-
tral and Earth. Max cable inlet size is 4mm² for 1 - 4 
terminals and  6mm² for L and N terminals.

 

 

Electrical  supply  for  RAC1306RX  is  230V  single 
phase only. Max cable inlet size is 4mm².  

 

It  is  recommended  that  the  electrical  supply  to  the 
base  unit  in  the  air  curtain  is  via  an  appropriate 
switched  isolator  having  a  contact  separation  of 
greater than 3mm on all poles. 

BMS  control,  time  switches,  room  thermostats  and 
door interlocks can be installed at the discretion and 
responsibility of the installer. 

 

All  units  must  be  wired  in  accordance  with  I.E.E 
regulations for the Electrical Equipment of Buildings 
and the installer should ensure that a suitable isolat-
ing switch is connected in the mains supply. 

1.4 Controller `RX` models 

The  RAC1306RX  heater  is  supplied  without  a  con-
troller.  The  `RX`  models  will  not  work  without  the 
CRX2  wireless  controller.  See  section  5.1  for  more 
details.

 

CONSORT Wireless CRX2 controller 

Summary of Contents for ScreenZone RAC 1309

Page 1: ...692172 Fax 01646 695195 Email technical consortepl com Web www consortepl com SCREENZONE RECESSED WARM AIR CURTAINS CATALOGUE NUMBERS RAC1306 RAC1309 RAC1306RX INSTALLATION AND OPERATING MANUAL INDEX...

Page 2: ...neral All installations must be in accordance with the regulations in force in the country of use These instructions must be handed to the user on completion of the installation Installers and service...

Page 3: ...41001453 Iss 02 3 2 Dimensions 2 1 Air Curtain Dimensions...

Page 4: ...to each other to cover the full door opening across wider entrances The weight of the RAC13 heaters is 17kg 3 2 Clearance Distance It is recommended that a minimum clearance of 55mm is allowed around...

Page 5: ...catenary wire can be used to fasten the air curtain to the ceiling support structure The height between the ceiling face and the top of the air curtain case needs to be adjusted to circa 140mm to ena...

Page 6: ...y means other than the remote switch supplied eg BMS then the heat output can be selected by connecting the appropriate terminals WIRED TERMINALS RAC1306 RAC1309 2 3 4 or 5 6000W 9000W 2 4 or 5 2000W...

Page 7: ...nd switch marked on off To change the fan speed use fan boost switch When the heat 1 switch only marked with a single bar is depressed the heat output is of full heat RAC1306 2kW RAC1309 3kW When the...

Page 8: ...his happens the thermal cut outs effectively switch off the appliance by disconnecting power to the control circuit The appliance will not operate until the thermal cut outs are manually reset This sh...

Page 9: ...41001453 Iss 02 9 Fig 18 Wiring diagram standard models...

Page 10: ...41001453 Iss 02 10 Fig 19 Wiring diagram models for wireless controls...

Reviews: