2 a) Electrical: Electrical work must be performed by a qualified Electrician
and comply with the Canadian Electrical Code or the American National
Standard Electrical Code lnforce.
Table 02. The wire sizes to be used are as follows:
For installation see Wiring Schematic figure 03.
FIGURE 03. Wiring Schematic
In Accordance with The Electrical Code in effect
b)
A green coloured terminal (or a wire connector marked “C”,“GP”. “Ground”
or “Grounding”) is provided within the control box. To reduce the risk
of electric shock, connect this terminal or connector to the grounding
terminal of the electric service or supply panel with a continuous green
insulated copper wire equivalent in size to the circuit conductors
4
Model
Amps
Fuse
(240V G.F.L. Size)
Wire Size
(90’ Copper Only)
Collector
Ground Wire
(Copper Only)
K-5
21A
30A
10
10
K-10
42A
60A
6
6
K-15
63A
80/100A
Use Supply conductor
suitable for 75º C
Use Supply conductor
suitable for 75ºC
supplying this equipment. Addition, bonding lugs are provided and marks
“Bonding Lugs”. To reduce the risk of electric shock connect the bonding lugs
in accordance with the Canadian Electric Code, Part 1.
c)
It is mandatory that all Electrical
Heaters be installed with
Leakage Collectors at the water outlet of filtration system and at
the outlet of heaters.
SAVE THESE INSTRUCTIONS
Warning:
Ensure that the unit is properly grounded at the provided lug within the unit
and that the leakage collectors are separately grounded at the main entrance.
Improper installation may be a potential cause of fire, electric shock, personal
injury or health hazards and great care should be taken to avoid these. Make
sure that all wiring is secure.
OPERATING INSTRUCTIONS
1.
Must be strictly followed for warranty to be valid.
Before energizing the heater, activate the pump and make sure that
the air is out of the heater chamber (no air bubbles will enter the pool
/spa
from the heater). Water circulation must be ensured at all times when
unit is energized.