Conrad CC-4100 Manual Download Page 2

2

Alarm sensitivity setting:

Conforms to EN 50291-1:2018

30PPM Without alarm before 120 minutes

50PPM: Alarm between 60 to 90 minutes

100PPM: Alarm between 10 to 40 minutes

300PPM: Alarm within 3 minutes

NOTE: Refer to “3. What to do if the alarm sounds” when you hear 

the sounds of the CO alarm warning.

3.4 CO alarm warning silence

During the device under CO alarm mode, pressing the TEST/SILENCE 

button, it will be paused alarm sound of the device about 10 minutes. 

-

tes the device is running into the CO alarm silence mode.

NOTE: The audible alarm signal will reactivate about 10 minutes 

from the time the TEST/SILENCE button is operated where the con-

centration of CO surrounding the

alarm remains at 50 PPM or greater.

NOTE: The audible alarm signal cannot to silence if the alarm at 

concentration above 200 PPM.

NOTE:  The  alarm  silencing  activation  to  once  throughout  a  CO 

alarm period.

WARNING! Before enable feature of CO alarm warning silen-

-

rous levels of carbon monoxide and the dwelling should be 

ventilated.

3.5 Low battery voltage warning

If the device chirps once every 40 seconds, with FAULT indicator (yel-

-

ways displays „          „. 

NOTE: When the low battery voltage warning is occur, the device 

has capable of producing a CO alarm signal for at least 4 min or 30 

days of low battery voltage warning signal operation.

NOTE: The device will not protect against the risk of carbon mono-

xide poisoning when the battery has drained.

3.6 Low battery voltage warning silence

When  the  device  is  under  the  low  battery  warning,  pressing  the 

TEST/SILENCE button, it will come into a low battery voltage warning 

silence status for about 9 hours, meanwhile it will appear „  „  on 

NOTE: The silence feature of low battery voltage warning is tempo-

battery as soon as possible.

3.7 Fault warning

If the device chirps twice every 40 seconds with FAULT indicator (yel-

-

tion. The LCD displays „ Err „, that means your CO alarm have no de-

tecting function and no respond CO.

NOTE: Maybe the sensor is missing, replace the device immediate-

ly. Please contact us to more service.

2. Product overview

2.1 POWER indicator

The POWER indicator (green LED) is used to indicate power status of 

2.2 FAULT indicator

The FAULT indicator (yellow LED) is used to indicate fault or warning 

status of the CO alarm.

2.3 ALARM indicator

The ALARM indicator (red LED) is used to indicate alarm status of the 

CO alarm.

2.4 TEST/SILENCE button

The TEST/SILECNE button is used to test the unit. Press and hold to 

enable TEST function.

2.5 Alarm sounder

The alarm sounder is used to send out CO alarm warning and fault 

warning information.

2.6 LCD screen

Indicates CO concentration and alarm status.

3. Understanding your CO alarm

3.1 Start up

This is preheated state, 60 seconds later the POWER indicator (green) 

The LCD displays all segments 4s and count down. When the

countdown is „0“, the product goes into normal operation.

3.2 Normal operation

LCD  alternately  displays  current  CO  concentration  and  temperatu-

re every 40s. CO concentration display range: 0~999PPM. If the CO 

concentration is under 20PPM, the LCD will display „0PPM“. If the CO 

concentration overruns 999PPM, the LCD will display „999PPM“. Tem-

perature display range:-9~50

℃.

 If CO concentration overruns 20PPM, 

the function of temperature display will be

disable.

3.3 CO alarm warning

When the device detects a dangerous level of CO, the device will emit 

a loud alarm pattern. The alarm signal pattern is 4 beeps followed by 

pattern. This cycle repeats as long as a dangerous CO condition exists.