background image

2. Mounting With Clamping Hardware

|

If module clamps are used to secure the module, the torque on the clamp bolt

should be around 8–10 Nm.

|

A minimum of four module clamps should be used, two on each long frame side,

in the general clamping areas denoted by the wide arrows on the drawing.

|

Depending on the local wind and snow loads, additional module clamps may be

required.

All dimensions in mm

3. Other

|

Other mounting methods are acceptable as long as the minimum requirement

as described under 2. Mounting with clamping hardware are met.

Electrical Installation

Grounding

|

All module frames must be properly grounded.

|

Observe all local electric codes and regulations. 

|

A bonding or toothed washer is required to make proper and reliable electrical

grounding connection with the anodized aluminum frame.

|

Devices listed and identified for grounding metallic frames of PV modules are

permitted to ground the exposed metallic frames of the module to grounded

mounting structures. Per NEC 250.136, electrical equipment secured to and in

electrical contact with a metal rack or structure provided for its support and

grounded by one of the means indicated in 250.134 shall be considered 

effectively grounded.

|

Consider using a lay-in lug, rated for outdoor use (Illsco

GBL4 DBT or equivalent), if the module grounding conductor

is to be larger than #10 AWG.

|

When using lay-in lugs, the grounding conductor should

be inserted into the opening indicated in the figure, and

secured using the set screw.

General electrical installation

|

Do not use modules of different configurations in the same system.

|

This module is supplied with Multi Contact connectors for electrical connections. 

|

Refer to Section 690.31 of the NEC to determine appropriate types and 

temperature ratings of conductors. Wiring should be #12 AWG, 4 mm² 

(minimum) and must be temperature rated at 90 °C (minimum).

|

Completely cover system modules with an opaque material to prevent 

electricity from being generated while disconnecting conductors.

|

Refer to Sections 690.8 and 310 of the NEC to determine overcurrent, 

conductor ampacity and size requirements.

|

In Canada, installation shall be in accordance with CSA C22.1, Safety

Standard for Electrical Installations, Canadian Electrical Code, Part 1.

|

For best performance, ensure that positive and negative DC wires run 

closely together avoiding loops.

WARNING! 

Electrical shock hazard! Do not touch bare conductors 

or other potentially energized parts.

Maintenance

Conergy recommends the following maintenance items to ensure optimum 

performance of the module:

|

Clean the glass surface of the module as necessary. Use water and a soft

sponge or cloth for cleaning. A mild, non-abrasive cleaning agent can be

used if necessary. Do not use dishwasher detergent.

|

Electrical and mechanical connections should be checked periodically by

qualified personnel to verify that they are clean, secure and undamaged.

|

Check the electrical and mechanical connections periodically to verify that

they are clean, secure and undamaged.

|

Problems should only be investigated by qualified personnel.

|

Observe the maintenance instructions for all other components used in the

system.

Shutting down the system

|

Completely cover system modules with an opaque material to prevent 

electricity from being generated while disconnecting conductors.

|

Disconnect system from all power sources in accordance with instructions 

for all other components used in the system.

|

The system should now be out of operation and can be dismantled. In doing

so, observe the all safety instructions as applicable to installation.

Electrical ratings of the concerned modules:

S 180MU

175MU

Q 85MU

Maximum Power (P

MPP

180 W

175 W

85 W

Output Tolerance 

–2/+ 3 %

–2/+ 3 %

+/- 5 %

Rated Voltage (V

MPP

35.6 V

35.2 V

17.6 V

Rated Current (I

MPP

)

5.05 A

4.95 A

4.83 A

Open Circuit Voltage (V

OC

44.4 V

44.2 V

21.9 V

Short Circuit Current (I

SC

5.4 A

5.2 A

5.14 A

Maximum System Voltage 

600 V

600 V

600 V

Maximum Series Fuse Rating 

15 A

15 A

15 A

Fire Class 

C

C

C

The electrical characteristics are within ±10 % of the indicated values of I

SC

, V

OC

, and P

max

under Standard Test

Conditions (irradiance of 1000 W/m

2

, AM 1.5 spectrum, and a cell temperature of 25°C/77°F)

Disclaimer of liability

Because the use of this manual and the conditions or methods of installation, 

operation, use and maintenance of photovoltaic products are beyond Conergy's

control, Conergy does not accept responsibility and expressly disclaims liability

for loss, damage, or expense arising out of or in any way connected with such

installation, operation, use or maintenance. No responsibility is assumed by

Conergy for any infringement of patents or other rights of third parties, which may

result from use of the PV product. No license is granted by implication or otherwise

under any patent or patent rights. 

The information in this manual is based on Conergy's knowledge and experience

and is believed to be reliable, but such information including product specification

(without limitations) and suggestions does not constitute a warranty, expressed 

or implied. Conergy reserves the right to change the manual, the product, the 

specifications, or product information sheets without prior notice. 

Information about manufacturer:

Conergy Inc.

1730 Camino Carlos Rey, Suite 103

Santa Fe, NM 87507

USA

www.conergy.us

Please consult your dealer or the manufacturer concerning the warranty of your

modules. If you have any further questions, your dealer will gladly assist you.

Subject to technical modifications without notice. 2007 © Conergy, Inc.

MODUL_Installation-UL-IM-ENG-0705

www.conergy.com  |  2007 © Conergy AG

Installation | Safety instructions | Maintenance

Photovoltaic modules user manual

Conergy S 175/180MU/Conergy Q 85MU

each 

900 mm

cable

150

485

485

150

485

150

485

150

Page 2/2

Reviews: