3.3.5 Grounding

Equipment grounding requirements must be checked in accordance with applicable regulations and standards before work 
is started. The module frame or array must be grounded to avoid the hazards of electric shock or fire. The position of 
possible grounding connections can be found in Fig. 3-1. An equipment grounding conductor can be fixed to the holes in the 
frame (4 hole locations, each with 5.5mm diameter). A #12 AWG copper ground wire or equivalent should be used. 

Observe all applicable regulations. 
Follow the steps below for a correct grounding connection. 

1. The copper wire with M5 cupped washer should be placed through the bolt; 
2. Put the cut washer through the bolt , and the bolt must be put through the hole fixed in the aluminum frame; 
3. Use the nut and cut washer to fix all the parts. The copper wire can not be attached to the aluminum. 
4. Use a tightening torque around 210±20 N·cm.

4 Maintenance and care

 
Conergy PH modules are low-maintenance. However, Conergy recommends that you carry out a visual inspection and a 
check of the mechanical and electrical connections for damage once a year. Dirt on the modules reduces the output and 
the yield. If the photovoltaic modules are installed with an inclination angle of more than15°, they will generally be 
adequately cleaned by rain. 

Prevent damage to the module surface by scratching or extreme differences in temperature. 

|  Use only pH neutral liquid cleaners, even if there is excessive dirt build-up. 
|  Do not use abrasive cleaning agents. 
|  Ensure cleaning solutions are at roughly the same temperature as the module surface. 
|  Wipe the module surface with water and a soft cloth. 

5 Removal

 
Risk of electric shock. 
|  Do not touch any bare electrical connection parts. 
|  Use only insulated tools. 

1. Disconnect the inverter from the utility power on the AC side so that the photovoltaic system has no load. 
2. Disconnect the photovoltaic system from the inverter at the cut-off point on the DC side. 
3. Make sure that the system is not supplied with voltage. 
4. Remove the photovoltaic system in the same way as it was installed; observe the safety instructions. 

6 Disposal

Please ask your installer, dealer or Conergy, Inc. about disposal.

Summary of Contents for PH 175-200M

Page 1: ...Conergy PH Series Modules Solar module user manual ...

Page 2: ...oderate injury Denotes an extraordinarily hazardous situation Disregard of this instruction may lead to serious irreversible injury or death 1 3 Standards and technical directives Conergy PH modules comply with the following standard ULC ORD C1703 01 UL 1703 1 4 Intended use Conergy PH modules are designed for use in photovoltaic systems Any other use is deemed to be not as intended Intended use a...

Page 3: ...nd etc The modules have been evaluated by UL for mounting using the 4 provided mounting holes in the frame Make sure that no other system components will impair the mechanical or electrical function of the Conergy PH modules Do not drill holes in the module frame or in the glass surface and do not carry out any welding work on or near the Conergy PH modules Comply with the applicable occupational ...

Page 4: ...4 A 1580 mm B 50 mm C 300 mm A 1652 mm B 50 mm C 300 mm Fig 3 1 Dimensions mm Conergy PH 175 200M Conergy PH 220 255P and Conergy PH 230 260M BL Variable clamping range ...

Page 5: ...e 2 Insert four stainless steel bolts M6 through the holes 7x11 5mm in the frame For maximum security against strong winds and snow falls all six mounting holes should be used to secure the modules 3 Secure each bolt to the frame with 2 stainless steel washers a stainless steel spring washer or toothed lock washer and a stainless steel nut M6 4 To tighten a torque wrench is recommended to produce ...

Page 6: ... is adequate protection against contact with live conductors Use only insulated tools 3 3 3 Parallel and series connection Modules of the same type can be connected in parallel or in series Modules or series strings of modules connected in parallel may require overcurrent protection in each series string The maximum series fuse ratings for Conergy PH modules are as follows PH 175 200M 10A PH 230 2...

Page 7: ...ends that you carry out a visual inspection and a check of the mechanical and electrical connections for damage once a year Dirt on the modules reduces the output and the yield If the photovoltaic modules are installed with an inclination angle of more than15 they will generally be adequately cleaned by rain Prevent damage to the module surface by scratching or extreme differences in temperature U...

Page 8: ...6A 29 16V 8 06A 240Wp 37 77V 8 59A 29 54V 8 13A 245Wp 37 98V 8 62A 29 92V 8 20A 250Wp 38 19V 8 65A 30 30V 8 27A 255Wp 38 40V 8 69A 30 68V 8 33A The electrical characteristics are within 10 percent of the indicated values of Isc Voc and Pmax under standard test conditions irradiance of100mW cm2 AM 1 5 spectrum and a cell temperature of 25 C 77 F Conergy PH 230 260M BL Maximum Power Pmax Open Circui...

Page 9: ...G Y Conergy Global Headquarters Anckelmannsplatz 1 20537 Hamburg Germany Phone 49 0 40 27 142 1000 www conergy com Conergy US Headquarters 2460 West 26th Avenue Suite 280C Denver CO 80211 US Toll Free 888 396 6611 www conergy us Conergy Canada Headquarters 17815 111 Ave Edmonton AB T5S 2X3 Canada Toll Free 1 888 489 3701 In Canada www conergy ca ...

Reviews: