Operator Interface
Nortec GS
2583701_C_EN_1812_Nortec-GS_OM
Multi-Unit Operation Tab
–
Linkup:
allows you to enable or disable the Linkup function, which
allows up to six humidifier to connect and operate together from
a single set of control signals. It also allows you to designate the
humidifier to operate as a "Main" or "Extension" unit.
Options:
Main
– designated as the main (master) unit.
Ext 1-5
– designated as the first extension
unit, second, third, fourth, or fifth extension
unit.
Off
– disables Linkup. The humidifier per
-
forms as a single unit.
Factory setting:
Off
Note:
The remaining settings in this tab and the next are only avail
-
able on the main unit when the Linkup function is enabled.
–
Linkup Units:
allows you to set the number of humidifiers in the
Linkup chain.
Setting range:
1-6
Factory setting:
1
–
Linkup Type:
allows you to select the mode of operation of the
humidifier in the Linkup chain.
Options:
Parallel
– the humidity demand (from a single
zone) is distributed evenly on all humidifiers
in the Linkup chain.
Series
– the main unit operates to its maxi
-
mum capacity, and as demand increases the
extension units generate steam in sequential
order. Each unit scales steam production in
small increments. Series setting maximizes
turndown.
Factory setting:
Series
–
Sequence Rotation:
allows you to enable or disable the function
that manages the starting order to balance operating hours of all
linked humidifiers.
Note:
This setting is available only if
is set to "Series".
Options:
On
or
Off
.
Factory setting:
On