45
Operator Interface
Nortec EL
2582954_D_EN_1811_Nortec-EL_OM
Modbus Parameters Tab
–
Modbus:
allows you to enable or disable the Modbus
communications protocol. Enabling or disabling Modbus
always requires a power cycle of the unit.
Options:
On
or
Off
Factory setting:
Off
The following settings appear only if
–
Modbus Address
: allows you to set the Modbus ad
-
dress of the humidifier on the network.
Setting range:
1-247
Factory setting:
10
–
Parity
: allows you to set the parity bit for the data
transfer.
Options:
None, Even
or
Odd
Factory setting:
Even
–
Baudrate
: allows you to set the baudrate for the data
transfer.
Options:
110, 300, 600, 1200, 2400, 4800,
9600, 19200, 38400, 57600, 76800
or 115200
Factory setting:
9600
BACnet Parameters Tab
–
BACnet:
allows you to enable or disable the BACnet com
-
munications protocol. Enabling or disabling BACnet always
requires a power cycle of the unit.
Options:
BACnet/IP
– enables BACnet/IP over
the RJ45 (Ethernet) interface
.
MSTP
– enables BACnet MSTP
over the RS485 interface.
Note:
The
Nortec EL humidifier is a slave-only
BACnet MSTP device.
Off
– disables BACnet communica
-
tions protocol.
Factory setting:
Off
Summary of Contents for Nortec EL-Series
Page 74: ...74 Maintenance 2582954_D_EN_1811_Nortec EL_OM Nortec EL This page intentionally left blank...
Page 84: ...84 Fault Isolation 2582954_D_EN_1811_Nortec EL_OM Nortec EL This page intentionally left blank...
Page 88: ...88 Wiring Diagrams 2582954_D_EN_1811_Nortec EL_OM Nortec EL This page intentionally left blank...
Page 93: ...Notes...
Page 94: ......