4.14 How to mount the feet (Accessory) (ZOCC)
All
+%$XQLWVFDQEHVXSSOLHGZLWKIHHWRSWLRQWREHGLUHFWO\PRXQWHGRQWKHÀRRU
This accessory is supplied spare, in a separate carton box.
&RQGHQVDWHGUDLQLQJFRQQHFWLRQV
Condensate
GUDLQLQJVKRXOGEHGRQHXVLQJÀH[LEOHUXEEHUSLSHDERXWPWORQJQRWVXSSOLHG7KHSLSHZLOOSDVVWKURXJKWKHFRQGHQ
-
sate drain hole located either on the rear panel of the unit or on the base frame. On the condensate discharge pipe it must be installed a
syphon with a minimum height equal to the suction pressure of the fan.
6OLGHWKHXQLWRXWRIWKHSDOOHWDQG¿[WKH¿UVWIHHWZLWKWKHVXS
-
plied screws.
5HPRYHWKHSDOOHWDQG¿[WKHVHFRQGIHHW
Discharge pipe
ø 20 mm modd. 75÷200
ø 16 mm mod. 50
Condensate discharge on
the rear panel.
The metallic feet (ZOCC) can’t be installed if its installed the inlet plenum (PMBH).
7KHFRQGHQVDWHGUDLQOLQHVKRXOGKDYHDZDWHUWUDSZKLFKPD\KDYHPLQLPXPÀ\LQJKHLJKWHTXDOWRWKHVXFWLRQRI
the fan, in any case never less than 35 mm.