The first service level page shows the runtime meters and runtime reset buttons for the following components (in
hours):
l
Time since process air filter was changed.
l
Time since reactivation air filter was changed.
l
Time since rotor seals were replaced.
l
Process air fan runtime.
l
Reactivation air fan runtime.
l
Drive motor runtime.
The second service level page shows the adjustable interval period for the process air filter, reactivation air filter,
and the rotor seal, before an alarm is activated.
If you are using a humidity sensor, the page also shows the PID controller settings:
l
P-band
- range above and below the humidity set point.
l
I-time
- controls the speed of the controller.
l
PID output
- displays the dehumidication demand between 0-100 (stop = 0, start = 30).
IMPORTANT!
The PID settings should not be changed. Consult your Condair representative.
In addition to this, the second service level page shows buttons that will allow you to clear the alarm history (refer
to
), and turn on/off the rotor rotation guard (if available).
7.1.5.4 Communication Settings
Password: 4498
The Communication Settings page displays settings for Modbus TCP/IP and RS485 connections, as long as a
communication card is installed.
Note:
The Modbus data points are located here:
.
Modbus Network ID
Default: 35
RS 485
Choose between six different combinations, then save.
Modbus TCP/IP
Enter the IP Address, Gateway, and Subnet, then save.
Condair DA
2593630_A_EN_2003_DA_IOM
User Interface | 35