Humidification and Evaporative Cooling

2585293

-K

  EN

  2202

Gateway Board for 

BACnet and LonWorks

Supplemental Installation and Operation Manual

For use with RS, EL, DL, and 

ME humidifiers with  

Software version 5.9.x.x and 5.10.x.x

Summary of Contents for 2582290

Page 1: ...n and Evaporative Cooling 2585293 K EN 2202 Gateway Board for BACnet and LonWorks Supplemental Installation and Operation Manual For use with RS EL DL and ME humidifiers with Software version 5 9 x x...

Page 2: ...ta of Condair Ltd Neither this document nor the information contained herein shall be reproduced used or disclosed to others without the written authorization of Condair Ltd except to the extent requi...

Page 3: ...ommunication 15 3 3 1 3 BMS Timeout and Modbus settings 16 3 3 2 Gateway configuration 17 3 3 2 1 Requirements for gateway configuration 17 3 3 2 2 Configure the IP settings 18 3 3 2 3 Modifying the B...

Page 4: ...trained technical personnel Please read this manual thoroughly before installing and configuring the BACnet or LonWorks based network If you have questions after reading this documentation please cont...

Page 5: ...available in various languages Please contact your Condair representative for information 1 2 Functions overview The following table gives you an overview of the supported protocols and functions Opti...

Page 6: ...ations on work safety and the prevention of accidents Intended use The optional LonWorks or BACnet gateway boards are intended exclusively for connecting the Condair Integrated Controller to a LonWork...

Page 7: ...ure such systems against ac cidental power up Prohibited modifications to the unit No modifications must be undertaken on the optional LonWorks or BACnet gateway boards and on the Condair Integrated C...

Page 8: ...est version before installing the gateway board Please contact your Condair distributor regarding a software update of the Integrated Controller The following protocol options are available and must b...

Page 9: ...BACnet network The principle diagram below shows the connection of the Condair Integrated Controller to an Ethernet network Principle BACnet IP network Abb 1 Principle BACnet IP network Ethernet BACne...

Page 10: ...t MS TP network Abb 2 Principle BACnet MS TP network Ethernet BACnet IP GND BACnet MS TP to BACnet IP Router RS485 Network BACnet MS TP Shielded twisted pair cable 120 Ohm impedance Terminate shield a...

Page 11: ...e Condair Integrated Controller to a LonWorks network via a shielded twisted pair cable Abb 3 Principle LonWorks network Network via shielded twisted pair cable LonWorks Device LonWorks Device LonWork...

Page 12: ...to prevent damage to electronic components A wrist strap should be worn to connect the maintenance specialist with a common ground point For more information refer to ANSI ESD S20 20 3 Open the contr...

Page 13: ...pectively 2 Connect network cable according to the following wiring diagrams BACnet Abb 5 BACnet IP network connection Abb 6 BACnet MS TP network connection LonWorks Abb 7 LonWorks network connection...

Page 14: ...er board inside the control unit Note If you want the Condair Integrated Controller to be controlled via a hardwired analog control signal set Signal Source to Analog and set the other control setting...

Page 15: ...d communication via the bus system is also monitored The control signal must be periodically updated within the time set in BMS Timeout If the control signal is not updated within the set time warning...

Page 16: ...tion submenu as shown below Password 0335 3 Select BMS Timeout tab and set BMS Timeout to the desired values Factory setting 300 s Setting range 1 300 s 4 Select Modbus Parameter tab and set Modbus se...

Page 17: ...0 Analog Input 521 Analog Output The Condair RS consists of two analog input objects Unit A and unit B The second analog input object holds only the SNVT s of unit B 3 3 2 1 Requirements for gateway c...

Page 18: ...232 72 172 Subnet mask 255 255 0 0 Default gateway 10 232 72 1 To configure a new IP address subnet mask and default gateway via the integrated FS GUI of the gateway board proceed as follows 1 Connec...

Page 19: ...n at the bottom right of the screen If the login screen screen appears Enter admin as the username and the password can be found on the sticker of the gateway board Then confirm your entries with the...

Page 20: ...assword The password on the sticker of the gateway board is no longer valid after the alteration 7 Select the menu point Setup Security in the Navigation Tree in order to select the security mode the...

Page 21: ...to the FS GUI Press the Create User button Enter a Username Select the security group under Security Groups Admin Can modify and view any settings on the FS GUI Operator Can modify and view specific d...

Page 22: ...IP Address Netmask Gateway Domain Name Server 1 and Domain Name Server 2 to be assigned via a DHCP server activate the Enable DHCP 1 mode 1 Depending on the date of manufacture also called DHCP Client...

Page 23: ...tion on your laptop BACnet IP settings 3a Open the configuration file config csv with a text editor Change in the section Server Side Nodes of the window the Node_ID to the appropriate value Range 0 4...

Page 24: ...appropriate value Default Node_ID 1001 Range 1 16777215 Server Side Nodes Nodes Node_Name Node_ID Protocol Description Virtual_BCU_DL 1001 Bacnet_MSTP Humidifier DL Change a Master unit to a Slave un...

Page 25: ...e is finished a corresponding message appears in the upper part of the window Click on the button System Restart to restart the system with the new settings After restart the Node ID or MAC address is...

Page 26: ...intenance and malfunctions status 1 Service Info 2 Warning 3 Activation Code 4 Out of Commissioning 5 Refill Disinfection 6 Service 7 Fault 8 Replace Ag Cartridge 9 Disinfection MI 02 R MI_HumType Dev...

Page 27: ...e DL operation manual Object Name Description Range Object Type Object ID Read R Write W AV_SetPointHum Humidity setpoint 0 95 AV 01 R W AV_PropBand Proportional band 6 65 AV 02 R W AV_IntTime Integra...

Page 28: ...0 Closed 1 Open BI 05 R BI_StageValveY5 Y5 valve spray circuit 0 Closed 1 Open BI 06 R BI_StageValveY6 Y6 valve spray circuit 0 Closed 1 Open BI 07 R BI_StageValveY7 Y7 valve spray circuit 0 Closed 1...

Page 29: ...m 1 Hum FC 2 Hum RO C 3 Hum FC off SNVT_count 8 4 nvoErrorCode Error code 2 0 no Error SNVT_count 8 5 nvoOperatHours Operating hours 0 65535 h SNVT_time_hour 124 6 nvoHoursToServ Next service 0 10000...

Page 30: ...oRemoteFlush nviRemoteFlush Remote flush Read 0 Off 2 Flushing active Write 0 Stop flushing 1 Start flushing SNVT_count 8 27 28 nvoCerWashOver nviCerWashOver Ceramic wash over Read 0 Off 2 Ceramicwash...

Page 31: ...tch 95 37 nvoStageY5 Y5 valve spray circuit 0 Closed 1 Open SNVT_switch 95 38 nvoStageY6 Y6 valve spray circuit 0 Closed 1 Open SNVT_switch 95 39 nvoStageY7 Y7 valve spray circuit 0 Closed 1 Open SNVT...

Page 32: ...0 no Error AI 01 R AI_OperatHours Operating hours 0 1 200 000 h AI 02 R AI_NextSySvc Next service 0 10000 h AI 03 R AI_NextUVSvc Next UV bulb exchange 0 450 d AI 04 R AI_NextAgSvc Next PureFlo Ag exc...

Page 33: ...the ME operation manual Object Name Description Range Object Type Object ID Read R Write W AV_SetPointHum Humidity setpoint 0 95 AV 01 R W AV_PropBandH Proportional band humidity control 6 65 AV 02 R...

Page 34: ...1 Ok BI 07 R BI_Pump2Err Fault pump 2 0 Fault 1 Ok BI 08 R BI_Pump3Err Fault pump 3 0 Fault 1 Ok BI 09 R BI_Pump4Err Fault pump 4 0 Fault 1 Ok BI 10 R BI_Pump5Err Fault pump 5 0 Fault 1 Ok BI 11 R BI_...

Page 35: ...5 h SNVT_time_hour 124 5 nvoNextSySvc Next service 0 10000 h SNVT_time_hour 124 6 nvoNextUVSvc Next UV bulb ex change 0 450 d SNVT_count 8 7 nvoNextAgSvc Next PureFlo Ag exchange 0 350 d SNVT_count 8...

Page 36: ...e SNVT SNVT Index nvoSetPointHum nviSetPointHum Humidity setpoint 0 95 SNVT_lev_percent 81 31 32 nvoPropBandH nviPropBandH Proportional band humidity control 6 65 SNVT_lev_percent 81 33 34 nvoIntTimeH...

Page 37: ...t 1 Ok SNVT_switch 95 56 nvoPump3Err Fault pump 3 0 Fault 1 Ok SNVT_switch 95 57 nvoPump4Err Fault pump 4 0 Fault 1 Ok SNVT_switch 95 58 nvoPump5Err Fault pump 5 0 Fault 1 Ok SNVT_switch 95 59 nvoPump...

Page 38: ...pped 4 Break 5 Level test 6 Standby 7 Humidifying 8 Filling 9 Idle 10 Draining 11 Remote off 12 Keep Warm MI 02 R MI_ServStatusA Maintenance and malfunctions status unit A 1 Service Info 2 Warning 3 R...

Page 39: ..._CylMaxCapB Max capacity unit B 1 5 40 kg h 10 90 lb hr AI 10 R AI_ActCapHum Actual capacity 1 0 160 kg h 0 360 lb hr AI 11 R AI_CylActCapA Actual capacity unit A 1 0 40 kg h 0 90 lb hr AI 12 R AI_Cyl...

Page 40: ...it B 0 Off 1 On ready BI 02 R BI_ExtSChStaA External safety loop unit A 0 Open 1 Closed ok BI 03 R BI_ExtSChStaB External safety loop unit B 0 Open 1 Closed ok BI 04 R BI_IntSChStaA Internal safety lo...

Page 41: ...Closed 1 Open BI 20 R BI_DrainA1 Drain cool valve unit A 0 Closed 1 Open BI 21 R BI_DrainB1 Drain cool valve unit B 0 Closed 1 Open BI 22 R BI_DrainA2 Complete drain valve unit A 0 Closed 1 Open BI 2...

Page 42: ...3 Break 4 Level test 5 Standby 6 Humidifying 7 Filling 8 Idle 9 Draining 10 Remote off 11 Keep Warm SNVT_count 8 3 nvoServStatusA Maintenance and malfunctions status unit A 0 Service Info 1 Warning 2...

Page 43: ...nt_f 51 19 nvoActCapHum Actual capacity 1 0 160 kg h 0 360 lb hr SNVT_count_f 51 20 nvoCylActCapA Actual capacity unit A 1 0 40 kg h 0 90 lb hr SNVT_count_f 51 21 nvoCylActCapB Actual capacity unit B...

Page 44: ...StaB External safety loop unit B 0 Open 1 Closed ok SNVT_switch 95 46 nvoIntSChStaA Internal safety loop unit A 0 Open 1 Closed ok SNVT_switch 95 47 nvoIntSChStaB Internal safety loop unit B 0 Open 1...

Page 45: ...1 Drain cool valve unit B 0 Closed 1 Open SNVT_switch 95 64 nvoDrainA2 Complete drain valve unit A 0 Closed 1 Open SNVT_switch 95 65 nvoDrainB2 Complete drain valve unit B 0 Closed 1 Open SNVT_switch...

Page 46: ...t MS TP Slave MS TP slave devices can not be detected automatically via the Who is BACnet service and therefore have to be manually added to the network Condair Integrated Controller will not respond...

Page 47: ...parameter Register se quence according to chapter 3 3 1 3 Error code 0 is shown though a fault is present on the Integrated Controller Check software version of the Integrated Controller Error codeind...

Page 48: ...Offline LED lights up on power up and goes off 15 seconds after power up If the Node Offline LED stays on solid a Node Offline condition has occurred nocommunicationbetweenIntergratedControllerand ga...

Page 49: ...LED stays on solid a Node Offline condition has occurred no communication between Intergrated Controller and gateway board or no network output variable nvo of the LonWorks gateway board has been bind...

Page 50: ...the board LON RX LED On normal operation of the board the RX LED will flash when a message is received on the Lon port of the board LON SERVICE LED next to Lon port The LON SERVICE LED will flash if t...

Page 51: ...ble AO Analog Output Analogue control signal readable and writable with priority AV Analog Value Analogue setting readable and writable BI Bin r Input Binary state value readable BV Bin r Value Binary...

Page 52: ...Cnet only BACnet IP Default Gateway Address Name BACnet MS TP BACnet Node ID Device Instance LonWorks Network Number Subnet Mask Module IP Address Settings for BACnet MS TP only MAC Address BACnet MS...