6. Installer mode

6.1 DIP switches parameters

To enter installer parameters please follow steps below. Please refer to parameters table description before any changes. Use     button to move through 
parameters. Use     or     for adjustements. Every change/selection confirm by     button. 

DIP switches are used to set chosen control algorithm. They are located under back cover of the thermostat (please refer to the picture below): 

The position of the DIP switches determines the type of control algorithm:

PLEASE NOTE! 

TPI algorithm is recommended for underfloor heating. It can be adjusted between a low comfort level (6 CPH) and a higher 

comfort level (9 CPH). „CPH” means cycles per hour and it relates to the frequency of the measurement cycles performed by thermostat.

DETAILED TABLE WITH ALL INSTALLER PARAMETERS:

Press and hold     +     +     

simultanously for about 3 seconds to 

enter the installer mode.

Use     button to move through 

parameters. Use     or     for 

adjustements. Every change/selection 

confirm by     button. 

1

2

3 sec

3 sec

3 sec

dxx

Function

Parameter

Default

value

d01

Temperature display accuracy

0.1°C or 0.5°C

0.5°C

d02

Temperature offset

+/- 3.0°C

0.0°C

d03

Frost Protection setpoint temperature

5.0°C - 17.0°C

5.0°C

9CPH

±0.25°C

6CPH

Span

TPI

ON

1

2

1

2

Cooling *

Heating

Default value

ON

ON

Hyst/- 0.25 

Hyst/- 0.25

OFF

ON

Hyst/- 1.5

Hyst/- 0.5

ON

OFF

Hyst/- 1.0

TPI 9 CPH

OFF

OFF

Hysteresis

+/- 0.5

TPI 6 CPH

* Function available only from firmware version 2.1

Summary of Contents for Salus Controls RT310SPE

Page 1: ...RT310SPETHERMOSTAT FULL USER MANUAL...

Page 2: ...scription 10 4 3 First power up sequence and configuration 11 5 User settings 12 5 1 Manual mode changing temperature setpoint 12 5 2 Frost protection mode 13 5 3 Sleep mode 13 5 4 Heat Cool mode 14 6...

Page 3: ......

Page 4: ...tions in accordance with standards and regulations in force in the given country and in the EU Never try to connect the device other than as described in the manual Before assembly repair or maintenan...

Page 5: ...mperature You won t have to adjust the thermostat further Any adjustment above this setting will waste energy and cost you more money If your heating system is a boiler with radiators there will usual...

Page 6: ...an t be exposed to sunlight or any extreme conditions like for example draft Because of fire and explosion risk there is not allowed to use thermostat in atmosphere of explosive gases and flammable li...

Page 7: ...crews at the bottom Wiring configuration 1 2 3 COM NO NC Fit the front housing Press lightly Fix the backplate to the wall Align the front housing at the top edge Content used for thermostat mounting...

Page 8: ...d installing the device in places directly exposed to water moisture and air condensation Smart plug receiver has designed LED diode together with the main button Here is description what a single col...

Page 9: ...A SPE868 L AC 230V N RT310TX COM lub NO N N L N N COM NO RXRT510 RXRT510 N MAX 16 5 A POD CZENIE KOT A 3V 2 x AA R T 3 1 0 T X C O M N O N N L N R X R T 5 1 0 P O D C Z E N I E K O T A 3 V 2 x A A L N...

Page 10: ...dicator only in RT310RF 4 Low battery status 5 Temperature unit 6 Room setpoint temperature PLEASE NOTE The LCD screen can be activated by using any button 1 TurnontheLCDbacklight 2 HEAT COOL modescha...

Page 11: ...stat will display following sequence 1 2 4 3 Remove the protection foil and insert 2xAA batteries by removing front cover then thermostat will display the software version After that thermostat will a...

Page 12: ...a constant temperature set by the user To set temperature setpoint follow steps below 1 2 4 3 First thermostat is displaying actual room temperature Now wait 2 seconds timeout to approve the changes...

Page 13: ...again To activate deactivate sleep mode follow steps below TO DEACTIVATE SLEEP MODE TO ACTIVATE SLEEP MODE Press button to turn ON OFF frost protection Press and hold buttons simultanously to turn ON...

Page 14: ...about 3 minutes To set selected mode please follow steps below HOWTO SET COOLING MODE HOWTO SET HEATING MODE By default thermostat is in HEATING mode flame icon is displaying To change the thermostat...

Page 15: ...level 9 CPH CPH means cycles per hour and it relates to the frequency of the measurement cycles performed by thermostat DETAILEDTABLEWITH ALL INSTALLER PARAMETERS Press and hold simultanously for abou...

Page 16: ...minutes Attention Forcing the pairing process will generate a new communication code All receivers previouslypairedwiththethermostat will be irretrievably deleted from its memory The word PAIRING in...

Page 17: ...ack to the ON position The red LED will start blinking which will confirm that the receiver has entered the pairing mode A B C 8 RT310TX thermostat pairing with few other receivers The word PAIRING in...

Page 18: ...WILL GLOW CONSTANTLY RED SPE868 PLUG RXRT510 RECEIVER SR868 RELAY TEST PAIRING TEST PAIRING 3sec Press and hold TEST PAIRING button for 3 seconds to end pairing process Thermostat will go back to the...

Page 19: ...of communication between the transmitterandthereceiverinanopenareaisupto60m Theradiotransmissionisinfluencedbymanyfactorsthatcanshortentheworkingdistance such asthickwalls drywallcoveredwithaluminumf...

Page 20: ...he batteries without pressing any button Wait 2 minutes and insert the batteries again Your device will be restarted 1 When you want to change the batteries your device will use the internal memory to...

Page 21: ...x 96 x 27 receiver 42 x 77 x 42 The RT310SPE requires no special maintenance Periodically the outer casing can be wiped clean using a dry cloth please DO NOT use solvents po lishes detergents or abra...

Page 22: ...twillbefreefromanydefectinmaterialsorworkmanship andshallperforminaccordancewithitsspecification foraperiodoffiveyearsfromthedateofinstallation SALUSControlssoleliabilityforbreachofthiswarrantywillbe...

Page 23: ......

Page 24: ...OLS Sp z o o Sp k ul Rolna 4 43 262 Kobielice www salus controls eu SALUS Controls is a member of the Computime Group Maintaining a policy of continuous product development SALUS Controls plc reserve...

Reviews: