Night setback – NSB function

The NSB (Night Set Back) function enables automatic reduction of the 

temperature setpoint on the daily thermostats, via the programmable 

thermostat connected to the wiring centre. The temperature change takes 

place between day and night temperatures. When the night mode is activated, 

the programmable thermostat sends a voltage signal to the daily thermostats 

via the wiring centre. Then, the HTR230(20) thermostat automatically reduces 

the temperature setpoint on the knob by 2° or 4° (as set on the SETBACK 

jumper). In heating mode, the temperature is lowered when 230 V AC voltage 

appears at the NSB input.

Note:

For the proper NSB function work, an appropriate cable 

connection is required. TThe connection description is on the previous 

page. 

Technical informations

Operation algorithm selection

The thermostat gives a possibility to choose the mode of controlling the room 

temperature by PWM algorithm (default) or hyst/-0.5°C. The PWM 

algorithm is designed for underfloor heating (for heating systems with high 

inertia) – to precisely maintain the room temperature.

Set the jumper to ON – 

 to enable or OFF – 

 to disable the 

function. This function activates the thermostatic valve for 5 minutes once a 

week to prevent valve against stuck (caused by limescale).

Selecting the heating or cooling mode

Cooling blocking function.

Cooling on: Set the jumper to ON 

. The thermostat will work 

in cooling mode if 230V AC will appear at the CO terminal. The 

LED lights up blue when the thermostat sends a signal for cooling.

4

Power supply

230V AC 50 Hz

Max. load

TRIAC 0.5 A

Output signal

230V AC 50 Hz

Temperature control range

5 – 30°C

Control method

PWM or

Hysteresis: ±0.5°C

Communication

Wired

Dimension [mm]

85 x 85 x 30

Jumpers for additional settings

Valve Protection

The functions of the HTR230(20) thermostat can be switched on and off by 

jumpers. Please refer to the table below:

Jumpers 1 to 5 correspond to the number of actuators connected. This jumper 

is factory set to position 1, which means that the thermostat controls one 

actuator. Depending on the number of actuators used, the jumper position 

must be changed to ensure optimal operation of the temperature thermostat. 

Montage

1

2

3

Make sure that the thermostat is not connected to the 230V AC. Remove the 

knob by pulling it towards you, and then open the front cover as shown in the 

figure above.

Connect the thermostat. Please refer to “Connection Description” section. 

Mount the thermostat using the designed screw holes.

Fold front and back housing  of thermostat. The thermostat is configured.  

Use the knob to set the temperature setpoint.

Jumper

Function

ON

OFF

CO

Heating / Cooling mode

 – NSB

Temperature reduction value  

in NSB mode

PWM

PWM algorithm

VP

Valve Protection

2°C

4°C

Heating or cooling mode is based on the voltage sent to the CO terminal. 0V 

AC at the CO terminal – the thermostat is in heating mode. 230V AC at the CO 

contact – the thermostat is in cooling mode. 