3. BASIC SETTINGS

After the appliance is connected, the measured temperature is shown on the display when the appli

-

ance is switched on. You can change the default settings as written below.

3.1. Change the mode of control (F1/F2/F3)

The device can be used in three modes, which are detailed as follows:

-  

F1 (factory default) - Control of a heating system’s circulating pump:

 the output is turned on

if the measured temperature is higher than the set temperature. The switching sensitivity is taken into 

account when switching.

-  

F2 - Control of a cooling system’s circulating pump:

 the output is turned on

if the measured temperature is lower than the set temperature. The switching sensitivity is taken into 

account when switching.

-  

F3 - Manual mode:

 regardless of the measured temperature, the output is permanently switched 

on/off according to the setting.

To switch between modes, press and hold the   button for 4 seconds. The currently selected F1, F2, 

or F3 value is displayed. 

Summary of Contents for WPR-100GC

Page 1: ...COMPUTHERM WPR 100GC Pump controller with wired temperature sensor Operating Instructions...

Page 2: ...age of 230 V or other electrical appliance within the load capacity limits can be easily controlled The pump controller is responsible for turning the pump on and off at the set and measured temper at...

Page 3: ...g to set temperature and the switching sensitivity 1 LOCATION OF THE DEVICE It is recommended to place the pump controller near the heat ing cooling pipe or boiler on which the control is based so tha...

Page 4: ...is displayed when the output of the appliance is switched on Make sure that the wires are properly connected and that that there is no risk of electric shock or short circuit Connect your device as fo...

Page 5: ...zivatty szivatty vez rl Warning Always take into account the loadability of the controller relay when connecting 10 A 3 Inductive load and follow the instructions of the manufacturer of the pump which...

Page 6: ...s turned on if the measured temperature is higher than the set temperature The switching sensitivity is taken into account when switching F2 Control of a cooling system s circulating pump the output i...

Page 7: ...ches the connected pump on off below above the set temperature The lower this value is the more constant the temperature of the circulating fluid will be The switching sensitivity can be set between 0...

Page 8: ...the function is on the output will turn on every 5 days for 15 seconds if the output has not been turned on in the last 5 days During this time will appear on the display instead of the measured temp...

Page 9: ...e measured temperature reach es 5 C again to protect the pump and the heating system During this time the display alternates between and the measured temperature When the frost protection function is...

Page 10: ...itching sensitivity of 1 0 C the pump connected to it switches ON and at temperatures below 39 0 C the output switches OFF the pump connected to it switches OFF In F2 mode the output switches exactly...

Page 11: ...t accuracy 1 0 C Power supply 230 V AC 50 Hz Output voltage 230 V AC 50 Hz Loadability max 10 A 3 Inductive load Environmental protection IP40 Immersion sleeve connector size G 1 2 8x60 mm Length of h...

Page 12: ...he requirements of standards EMC 2014 30 EU LVD 2014 35 EU and RoHS 2011 65 EU Manufacturer QUANTRAX Kft H 6726 Szeged F lem le u 34 Telefon 36 62 424 133 Fax 36 62 424 672 E mail iroda quantrax hu We...