Rev.01 03-27-17
Page 56 of 67
Compu-Aire
11.1.1
Available Alarms
Alarm
Function
Temperature H/L Alarm
High low alarm set under Setpoint
Humidity H/L Alarm
Humidity high/low set under setpoints
Compressor Alarm
Compressor fail
Air Flow Alarm
Air flow loss
Smoke Detect Alarm
Smoke is detected in the system
Dirty Filter Alarm
Filter is dirty, need replacement
Fire Stat Alarm
Temperature reaches 125°F
Table 13 - Global alarms
The alarm status is notated by its current setting. To set the alarm, change the setting to either
“ON/OFF” by tapping the screen
and toggling via the virtual keyboard.
The CONTROLLER controller implements time out sensor delays to insure smooth operation.
Each delay is dictated in second unless otherwise noted.
Default Setting
•
RMT/OAH Sensor:
0s
•
FC/OAT/B10:
0s
•
Fire Stat:
ON
Temp: 125.0°F
•
Fire Stat Alarm Delay: 0s
•
Offline Alarm Delay:
60s
•
Alarm Buzzer:
OFF
•
T/H Alarm Delay:
15M
•
All Alarm Switchover: OFF
•
Disc Cool/Heat:
0.2°F 0s