INSTALLATION

Wiring Considerations

The wire type is noncritical for most applica-
tions.  If the wiring is located in an electrically
noisy environment, or longer than 60 feet  a twisted
pair with shield is recommended.  Connect the shield
to ground at one end only, see Figure 6. The insula-
tion should be sunlight resistant. Polyethylene or
polyvinyl chloride insulation is recommended.

Before proceeding verify that the maximum
resistance of the current loop including the
wiring and sensing element does not exceed the
maximum given by Formula 1. If this resistance
is exceeded the loop current will not attain full
scale.

Formula 1
Maximum Loop Resistance

R - Maximum Loop Resistance in Ohms
V - DC Excitation Voltage

R = (V - 10 Vdc) X 50

The resistance of various gages of copper wire is
given in Table 1.

Table 1

Wire Gage

Resistance in

AWG

Ohms per foot

12

.0016

14

.0026

16

.0041

18

.0065

20

.0103

22

.0165

24

.0262

A70-DL POWER SUPPLY

Proper operation of the Transmitter requires that
the power supply provide a voltage in the range
of 12-24 VDC.  Voltage ripple must be less than
100 volts per second for proper operation.  The
Transmitter is designed so that the loop current
will not exceed approximately 30 ma under any
circumstances.

A 12 volt power supply can drive a current loop
with a total resistance of 150 ohms.  A 16 volt
power supply can drive a current loop with a
total resistance of 450 ohms.

Figure 8

Graph of Maximum Loop Resistance

voltage

Excitation

Minimum

Excitation Voltage

 10       14       18       22       26

300

100

0

200

Resistance

Total Loop

600

400

500

  Ohms

A96-100P Surge Arrestor

Summary of Contents for A70-DL0

Page 1: ...1 INSTRUCTION MANUAL for WIND DIRECTION TRANSMITTER MODELA70 DL0 DOCUMENT 1147 Version K Model A70 DL __XX____ 360o Range ______ 540o Range A75 302 Wind Vane Track Mounted Transmitter...

Page 2: ...he same wire pair Two wind direction ranges 0 360 o and 0 540 o are available The 540 o range is recom mended if a mechanical chart recorder will record wind direction This range reduces transitions f...

Page 3: ...nics 1 Sensor See Separate Specs Loop Resistance Excit Voltage 9 X 50 ohms Max Temperature Range Electronics 0 o 60 o C standard 20 o 70 o C extended Sensor See Separate Specs Dimensions NEMA 12 Box 3...

Page 4: ...verts the output voltage from the wind vane which is proportional to azimuth to a dc current The current varies linearly from 4 ma at zero degrees azimuth to 20 ma at 360 degrees azimuth The Transmitt...

Page 5: ...5 Figure 5 Direction Vane Mounting Diagram...

Page 6: ...6 Figure 6 Transmitter Connection Diagram...

Page 7: ...7 Figure 7 MultipleTransmitters with One PowerSupply...

Page 8: ...Excitation Voltage R V 10 Vdc X 50 The resistance of various gages of copper wire is given in Table 1 Table 1 Wire Gage Resistance in AWG Ohms per foot 12 0016 14 0026 16 0041 18 0065 20 0103 22 0165...

Page 9: ...forty or fifty feet high a tower commonly used for TV antenna support consisting of concentric pieces oftubingapproximatelytenfeetlong guyedateach section issuitable Abovethisheightself supporting org...

Page 10: ...10 Figure 9 Poor Wind Sensor Placement Over Vertical Wall Figure 10 NorthAlignment Mark...

Page 11: ...bottom of the wind vane housing Attach the sensor cable to these studs being careful to tighten only the outer 4 hex nut to 3 inch pounds torque If the inner nut is loosened or the nuts are tightened...

Page 12: ...rmula 2 Figure 11 Graph ofWind DirectionTransfer Function 360o Range 0 180 360 4 12 20 Loop Current in mA Wind Azimuth Degrees N E S W N 540 Degree Wind Direction Scale The wind direction may be deter...

Page 13: ...0 0 4 1 2 2 0 Voltage Loop Current milliamperes ICING Under some conditions operation of the wind vane will be degraded by the presence of ice This most often occurs as the result of freezing rain The...

Page 14: ...the wind direction gain WIND DIRECTION TRANSMITTER The adjustments may be sealed with electronic grade silicon rubber to prevent tampering by unauthorized personnel 1 Connect a jumper between terminal...

Page 15: ...is fuel in the tank before replac ing the engine If the electronic equipment doesn t function verify that it has power and is turned on Systems containing parts which can be quickly interchanged are...

Page 16: ...ion is open or the signal terminal is short circuited to the positive excitation terminal If the output is constantly just East of North then the positive excitation terminal is open or the signal ter...

Page 17: ...resistance between the direction vane signal lead and either of the excitation terminals should be less than 10000 10K ohms If the resistance values differ radically from the above then the vane or t...

Page 18: ...aced removed or otherwise changed d the damage has not been caused by acts of nature including windstorm and hail beyond those specified as within the range of operating conditions e the damage has no...

Page 19: ...em 4 If the equipment is packaged in a plastic case wrapitinaluminumfoilorotherconductive material Thiswillprotectitfromstaticelectricity aswellaspreventthepackingmaterialfrom jammingmechanicalparts s...

Page 20: ...20 WWW COMPTUS COM Phone 603 726 7500 Fax 603 726 7502...

Page 21: ...1 Protective boot _______ 1 Instruction Manual _______ 2 Hose Clamps _______ 1 Certificate of Calibration _______ IMPORTANT Please check your order on receipt to be certain all listed accessories are...

Page 22: ...22 WWW COMPTUS COM Phone 603 726 7500 Fax 603 726 7502...

Reviews: