MODEL
Voltage/Phase/
Hertz
INSTALLED
POWER
(kWatt)
Nominal
Ampacity
(Amp)
MCA (A)
ELECTRICAL
PROTECTION CLASS
ACCORDING IEC
TOTAL
LRA (A)
Fuse
(Amp)
MH-US-15
115/1P/60
0,69
7,45
8,6
IP 54
26
8
MH-US-25
115/1P/60
0,69
7,57
8,8
IP 54
29
8
MH-US-35
115/1P/60
0,88
9,61
11,5
IP 54
36
12
MH-US-50
115/1P/60
0,5
10,75
13,4
IP 54
46
15
MH-US-75
115/1P/60
0,95
11
13,4
IP 54
46
15
MH-US-100
115/1P/60
1,16
13,18
15,8
IP 54
51
15
6.2 ELECTRICAL DIAGRAMS