INSTALLATION CONSIDERATIONS 

The ComFit fiber optic links in this series are supplied as a Standalone/

Rack module. The FVT1D1/M is supplies as a Standalone/Surface-mount 

module. Units should be installed in dry locations protected from 

extremes of temperature and humidity.

C1-US, C1-EU, C1-AU OR C1-CH CARD CAGE RACKS

 

CAUTION:

 Although the units are hot-swappable and may be installed 

without turning power off to the rack, ComNet recommends that the 

power supply be turned off and that the rack power supply is disconnected 

from any power source. 

Note:

 Remove electrical connector before 

installing in card cage rack.

1.  Make sure that the card is oriented right side up, and slide it into the 

card guides in the rack until the edge connector at the back of the card 

seats in the corresponding slot in the rack’s connector panel. Seating 

may require thumb pressure on the top and bottom of the card’s front 

panel.

CAUTION:

 

Take care not to press on any of the LEDs.

 

2.  Tighten the two thumb screws on the card until the front panel of the 

card is seated against the front of the rack.

WARNING

:  Unit is to be used with a listed Class 2 power supply.

IMPORTANT SAFEGUARDS: 

A)  Elevated Operating Ambient

 - If installed in a closed or multi-unit rack 

assembly, the operating ambient temperature of the rack environment may 

be greater than room ambient. Therefore, consideration should be given to 

installing the equipment in an environment compatible with the maximum 

ambient temperature (Tma) specified by the manufacturer.

B)  Reduced Air Flow

 - Installation of the equipment in a rack should be such 

that the amount of air flow required for safe operation of the equipment is not 

compromised.

MECHANICAL INSTALLATION INSTRUCTIONS

FIGURE A

Dimensions are for a standard ComNet one slot module

.156 [3.96 mm]

.313 [7.95 mm]

FIGURE B

Dimensions are for a ComNet

 small size module

Summary of Contents for FVT1D11

Page 1: ...ule is universally compatible with major CCTV camera manufacturers Plug and play design ensures ease of installation and no electrical or optical adjustments are ever required Each unit incorporates a bi color Red Green indicating LED for monitoring proper system operation See Figure 9 on Page 6 for LED Indicator explanations The ComFit units in this series may be directly plugged into the ComNet ...

Page 2: ...T1D1 TRANSMITTER FIGURE 1 FVT1D1 TRANSMITTER INSTALLATION AND OPERATION MANUAL FVT FVR1D1 M S 1 M FVR2D2 M S 2 REAR PANEL FRONT PANEL TECH SUPPORT 1 888 678 9427 BLACK BLACK WITH WHITE STRIPE RED Power Supply Surface Mount 9 36 VDC 3W Rack Mount From Rack NOTE Remove Electrical Connector for Rack Mount Units ...

Page 3: ...ACK WITH WHITE STRIPE RED Power Supply Surface Mount 9 36 VDC 3W Rack Mount From Rack NOTE Remove Electrical Connector for Rack Mount Units FIGURE 4 FVR1D1 RECEIVER FIGURE 3 FVR1D1 RECEIVER INSTALLATION AND OPERATION MANUAL FVT FVR1D1 M S 1 M FVR2D2 M S 2 REAR PANEL FRONT PANEL TECH SUPPORT 1 888 678 9427 ...

Page 4: ... FVR2D2 RECEIVER FIGURE 5 FVR2D2 RECEIVER INSTALLATION AND OPERATION MANUAL FVT FVR1D1 M S 1 M FVR2D2 M S 2 REAR PANEL FRONT PANEL TECH SUPPORT 1 888 678 9427 BLACK BLACK WITH WHITE STRIPE RED Power Supply Surface Mount 9 36 VDC 3W Rack Mount From Rack NOTE Remove Electrical Connector for Rack Mount Units ...

Page 5: ...LACK WITH WHITE STRIPE RED Power Supply 9 36 VDC 3W 24VAC AC pins 1 and 2 DC pins 2 and 3 FIGURE 8 FVT1D1 M TRANSMITTER FIGURE 7 FVT1D1 M TRANSMITTER INSTALLATION AND OPERATION MANUAL FVT FVR1D1 M S 1 M FVR2D2 M S 2 REAR PANEL FRONT PANEL TECH SUPPORT 1 888 678 9427 ...

Page 6: ...ch Position 2 Wire RS485 485 2W RS422 Simplex Contact Closure 422 2W 4 Wire RS485 485 4W 4 Wire RS422 Duplex 422 4W FIGURE 9 LED INDICATORS LINK VIDEO DATA GREEN Communication link has been established over optical fiber An active video signal is present on the BNC connector An active data signal is present on the input pins of the data connector RED Communication link has not been established OFF...

Page 7: ...M S 2 RS485 2W RS485 2W RS485 4W OR RS422 4W RS485 4W OR RS422 4W RS422 2W CONTACT CLOSURE RS422 2W CONTACT CLOSURE NC NC GND DATA A DATA B NC NC GND DATA A DATA B DATA OUT DATA OUT GND DATA IN DATA IN DATA OUT DATA OUT GND DATA IN DATA IN NC CONTACT IN GND CONTACT IN DATA OUT DATA OUT CONTACT OUT CONTACT OUT GND DATA IN DATA IN 5 4 3 2 1 5 4 3 2 1 5 4 3 2 1 5 4 3 2 1 5 4 3 2 1 5 4 3 2 1 O O O O O...

Page 8: ...cage rack 1 Make sure that the card is oriented right side up and slide it into the card guides in the rack until the edge connector at the back of the card seats in the corresponding slot in the rack s connector panel Seating may require thumb pressure on the top and bottom of the card s front panel CAUTION Take care not to press on any of the LEDs 2 Tighten the two thumb screws on the card until...

Reviews: