background image

INSTALLATION AND OPERATION MANUAL 

CNGE3FE7MS4

ELECTRICAL SUBSTATION-RATED  

MANAGED ETHERNET SWITCH WITH (7) 10/100T(X)  

+ (3) CONFIGURABLE 10/100/1000T(X)/100/1000FX PORTS 

The ComNet

  CNGE3FE7MS4 is a substation-rated and industrially hardened fully 

managed layer 2 gigabit Ethernet switch. Fully compliant with the requirements of IEC 
61850-3, IEEE 1613 Class 2, UL 508 Class 1/ Division 2 (Groups A, B, C, & D for hazardous 
environments), EN50155, and NEMA TS-1/ TS-2, it is designed for deployment 
in environments where high levels of electromagnetic noise and interference 
(EMI) and severe voltage transients and surges are routinely encountered, such as 
electrical utility substations and switchyards, heavy manufacturing facilities, trackside 
and roadside electronic equipment, and other difficult out-of-plant applications. 
Providing (7) 10/100 BASE-TX ports, the (3) 10/100/1000TX or 100/1000BASE-FX 
user-configurable combo gigabit uplink ports support conventional CAT-5e/CAT-6 
copper or optical transmission media by selection of the appropriate ComNet SFP 
module. Featuring an internal/self-contained 85-264 VAC/88-373 VDC power supply, 
the CNGE3FE7MS4 is DIN-rail or wall-mountable, and is ideal for mission-critical 
applications where very high levels of reliability and network availability are of 
the utmost importance. Utilizing exclusive ComNet C-Ring technology, the fastest 
recovery redundant ring available, network recovery time of <10 ms is provided 
for protection from network faults or temporary interruptions. ComChain permits 
additional redundant network rings of different redundancy protocols to function 
together as a larger and more robust network topology. eConsole, a Windows-based 
utility, is included for centralized/remote management and configuration of all 
functions of the CNGE3FE7MS4. 

Rev. 4.30.14

Summary of Contents for CNGE3FE7MS4

Page 1: ...Providing 7 10 100 BASE TX ports the 3 10 100 1000TX or 100 1000BASE FX user configurable combo gigabit uplink ports support conventional CAT 5e CAT 6 copper or optical transmission media by selection...

Page 2: ...y Indications 9 Hardware Installation 10 Installing Switch on DIN Rail 10 Mount Series on DIN Rail 11 Wall Mounting Installation 12 Mounting the CNGE3FE7MS4 on a Wall 12 Hardware Overview 13 Front Pan...

Page 3: ...g 25 Switch Setting 25 Admin Password 25 IP Setting 26 Time Setting 27 PTP Client 29 LLDP 29 Auto Provision 30 Backup Restore 31 Upgrade Firmware 31 Redundancy 32 DHCP Server 32 DHCP Server Setting 32...

Page 4: ...ased 54 SNMP 56 SNMP Agent Setting 56 SNMPV3 57 SNMP Trap Setting 58 Traffic Prioritization 59 QoS policy 59 Port base priority 60 COS 802 1p 61 TOS DSCP 62 Security 63 Management Security 63 Static M...

Page 5: ...Commands Set 85 Commands Set List Trunk command set 87 Commands Set List VLAN command set 88 Commands Set List Spanning Tree command set 89 Commands Set List QoS command set 90 Commands Set List IGMP...

Page 6: ...ations or repairs done by persons other than ComNet approved personnel and this warranty does not apply to ComNet products that are misused abused improperly installed or damaged by accidents Please r...

Page 7: ...switches can work under a wide temperature range dusty environment and humid condition WEB based TELNET Console port or other third party SNMP software can manage the CNGE3FE7MS4 as well The switch c...

Page 8: ...tification by Email SNMP trap and Relay Output Web based Telnet Console CLI configuration Enable disable ports MAC based port security Port based network access control 802 1x VLAN 802 1Q to segregate...

Page 9: ...ity 5 to 95 non condensing Casing Aluminum 10 100BASE T X Ethernet port 10 100 1000BASE T X Gigabit Ethernet port combo 100 1000BASE X on SFP port combo Console Port Dimensions W D H 96 4 148 5 154 mm...

Page 10: ...ON MANUAL CNGE3FE7MS4 TECH SUPPORT 1 888 678 9427 Hardware Installation Installing Switch on DIN Rail Each switch has a Din Rail kit on the rear panel The DIN Rail kit affixes the switch to the DIN Ra...

Page 11: ...TALLATION AND OPERATION MANUAL CNGE3FE7MS4 TECH SUPPORT 1 888 678 9427 Mount Series on DIN Rail Step 1 Tilt the switch and mount the metal spring to DIN Rail Step 2 Push the switch toward the DIN Rail...

Page 12: ...wall mount kit can be found in the package The following steps show how to mount the switch on the wall Mounting the CNGE3FE7MS4 on a Wall Step 1 Remove Din Rail kit if it is attached to the switch S...

Page 13: ...he labels on the CNGE3FE7MS4 Port Description 10 100 RJ 45 fast Ethernet ports 7 10 100BASE T X RJ 45 fast Ethernet ports support auto negotiation Default Setting Speed auto Duplex auto Flow control d...

Page 14: ...00Base X combo ports 2 LNK ACT LED for Gigabit LAN ports 3 LNK status LED for Ethernet LAN ports 4 Ethernet LAN ports 5 ACT status LED for LAN ports 6 Power LED 7 PW1 LED 8 PW2 LED 9 R M status LED 10...

Page 15: ...n C Ring Master Ring Green On C Ring enabled Slowly blinking C Ring topology has fault Fast blinking C Ring works normally Fault Amber On Fault relay Power failure or Port down fail 10 100BASE T X Fas...

Page 16: ...h wires should be kept separate The rule of thumb is that wiring sharing similar electrical characteristics can be bundled together 7 You should separate input wiring from output wiring 8 It is advise...

Page 17: ...Rev 4 30 14 PAGE 17 INSTALLATION AND OPERATION MANUAL CNGE3FE7MS4 TECH SUPPORT 1 888 678 9427 Rear Panel The components in the rear of CNGE3FE7MS4 are shown as below 1 Screw holes for wall mount kit 2...

Page 18: ...refer to the following table for cable specifications Cable Type Max Length Connector 10BASE T CAT3 CAT4 CAT5 100 UTP 100m 328ft RJ 45 100BASE TX CAT5 100 UTP UTP 100m 328ft RJ 45 1000BASE TX CAT5 CA...

Page 19: ...elow shows the 10BASE T 100BASE TX MDI and MDI X port pin outs Pin Number MDI port MDI X port 1 TD transmit RD receive 2 TD transmit RD receive 3 RD receive TD transmit 4 Not used Not used 5 Not used...

Page 20: ...t the TX port of Switch A should be connected to the RX port of Switch B Switch A Switch B Console Port Cable CNGE3FE7MS4 switches can be managed by the console port The DB 9 to RJ 45 cable can be fou...

Page 21: ...ed from DCE Device 3 Transmitted Data Transmitted from DTE Device Received Data Received by DCE Device 4 DTE Ready Transmitted from DTE Device DTE Ready Received by DCE Device 5 Signal Ground Signal G...

Page 22: ...site resides in the flash memory on the CPU board It contains advanced management features and allows you to manage the switch from anywhere on the network through a standard web browser such as Micro...

Page 23: ...ubnet Mask 255 255 255 0 Default Gateway 192 168 10 254 User Name admin Password admin System Login 1 Launch Internet Explorer 2 Type http 192 168 10 1 and the IP address of the switch Press Enter 3 T...

Page 24: ...nformation System Information interface System Information The system information will display the configuration of Basic Setting Switch Setting page Enable Location Alert Select Enable Location Alert...

Page 25: ...witch System Location Assign the switch physical location The maximum length is 64 bytes System Contact Enter the name of contact person or organization Admin Password This page allows you to configur...

Page 26: ...alog shows up to inform when the DHCP client is enabling The current IP will lose and you should find a new IP on the DHCP server IP Address Assign the IP address that the network is using If the DHCP...

Page 27: ...ble or disable daylight saving time function When daylight saving time is enabling you need to configure the daylight saving time period UTC Time zone Set the switch location time zone The following t...

Page 28: ...ADT Alaskan Daylight 8 hours 4 am ALA Alaskan Standard 9 hours 3 am HAW Hawaiian Standard 10 hours 2 am Nome Alaska 11 hours 1 am CET Central European FWT French Winter MET Middle European MEWT Middle...

Page 29: ...can be achieved with this protocol when using hardware generated timestamps Label Description PTP Client Enable Disable PTP Client LLDP LLDP Link Layer Discovery Protocol function allows the switch t...

Page 30: ...Provision allows you to automatically update the switch firmware You can put the firmware or configuration file on TFTP server When you reboot the switch it will upgrade automatically Before updating...

Page 31: ...ile Name Fill the file name Restore Select Restore to restore the configurations Form Local PC User can select file restore not need TFTP server Restore File Name Fill in the file name Restore Select...

Page 32: ...ress is the beginning of the dynamic IP assignments range For example dynamic IP assignment range is from 192 168 1 100 to 192 168 1 200 192 168 1 100 will be the Start IP address End IP Address The d...

Page 33: ...client information and display in here DHCP Server Client Entries interface DHCP Server Port and IP bindings You can assign the specific IP address that is in the assigned dynamic IP range to the spec...

Page 34: ...forwarding server DHCP packets to a DHCP client Label Description DHCP Relay Enable Disable DHCP Relay Agent DHCP Server IP Address and VID Specify the IP address and VID of DHCP server 0 0 0 0 means...

Page 35: ...he port Speed Duplex Set Auto negotiation 100 full 100 half 10 full or 10 half mode Flow Control Support symmetric and asymmetric mode to avoid packet loss when congestion occurred Security Enabling p...

Page 36: ...ulticast and flooded unicast You can also set Ingress or Egress to limit traffic received or transmitted bandwidth Rate Limit interface Label Description Ingress Limit Frame Type Set the mode of the I...

Page 37: ...nterface Label Description Group ID Select port to join a trunk group Type Support static trunk and 802 3ad LACP Work Port Select the number of active ports in dynamic group LACP The default value of...

Page 38: ...interface Label Description Group ID Trunk Group number Trunk Member Show Group port info C Ring C Ring is the most powerful Redundant Ring in the world The recovery time is less than 10ms It can red...

Page 39: ...l switches when network topology changes It is a good application for connecting two Rings Coupling Port Link to Coupling Port of the switch in another ring Coupling Ring need four switch to build an...

Page 40: ...ver from the failure The switch supports the function and interface for setting the switch as the ring master or not The ring master can negotiate and place command to other switches in the X Ring gro...

Page 41: ...another vendor s managed switch ComRing interface Label Description Enable Enable the COM Ring function Vendor Select the vendor whose ring you want to join 1st Ring Port Select the port that connects...

Page 42: ...undant ring technology invented by ComNet Different from standard STP RSTP the recovery time of C RSTP is 10ms and supports more nodes of connection in a ring topology C RSTP interface The application...

Page 43: ...lue has the highest priority and is selected as the root If the value changes You must restart the switch The value must be a multiple of 4096 according to the protocol standard rule Max Age Time 6 40...

Page 44: ...INS_CNGE3FE7MS4_REV Rev 4 30 14 PAGE 44 INSTALLATION AND OPERATION MANUAL CNGE3FE7MS4 TECH SUPPORT 1 888 678 9427 View the RSTP algorithm results at this table...

Page 45: ...r the port concerned can only be connected to exactly one other bridge i e It is served by a point to point LAN segment or it can be connected to two or more bridges i e It is served by a shared mediu...

Page 46: ...Protocol MSTP is a standard protocol base on IEEE 802 1s The function is that several VLANs can be mapped to a reduced number of spanning tree instances because most networks do not need more than a...

Page 47: ...ccording to the protocol standard rule Max Age Time 6 40 Time in seconds a bridge will wait to receive Spanning tree Protocol configuration messages before attempting a reconfiguration Enter a value 6...

Page 48: ...bridge at the specified port Enter a number 1 through 200000000 Admin P2P Some of the rapid state transactions that are possible within RSTP are dependent upon whether the port in question can only be...

Page 49: ...f the value changes You must reboot the switch The value must be a multiple of 4096 according to the protocol standard rule Apply Select Apply to activate the configurations MSTP Instance Port interfa...

Page 50: ...t carry multicast traffic It provides the ability to prune multicast traffic so that it travels only to those end destinations that require that traffic and reduces the amount of traffic on the Ethern...

Page 51: ...With multicast filtering network devices only forward multicast traffic to the ports that are connected to registered end stations Multicast Filtering Interface Label Description IP Address Assign a m...

Page 52: ...802 1Q VLAN Setting IEEE 802 1Q Tagged based VLAN is an IEEE 802 1Q specification standard and it is possible to create a VLAN across devices from different switch vendors IEEE 802 1Q VLAN uses a tec...

Page 53: ...o configure Link type Select Link Type from the following options Access Link Single switch only allows grouping of ports by setting the same VID Trunk Link Extended application of Access Link allows...

Page 54: ...f the same vlan group vlan port based startup set in the same group of the port can be a normal transmission packet without restricting the types of packets VLAN Configuration Port Base interface 1 Th...

Page 55: ...27 VLAN Configuration Port Base interface 2 The following table describes the labels in this screen Label Description Group Name VLAN name VLAN ID Specify the VLAN ID Add Select port to join the VLAN...

Page 56: ...elated information by Agent Setting Function SNMP Agent setting interface Label Description SNMP agent Version Three SNMP versions are supported such as SNMP V1 SNMP V2c and SNMP V3 SNMP V1 SNMP V2c a...

Page 57: ...the user name that you have set up in user table Group Name set up the group name Select Add to add context name Select Remove to remove unwanted context name Access Table Configure SNMP v3 access ta...

Page 58: ...l be issued Create a trap manager by entering the IP address of the station and a community string To define management stations as a trap manager and enter SNMP community strings and select the SNMP...

Page 59: ...he output priority is determined by COS only TOS only the output priority is determined by TOS only COS first the output priority is determined by COS and TOS but COS first TOS first the output priori...

Page 60: ...ERATION MANUAL CNGE3FE7MS4 TECH SUPPORT 1 888 678 9427 Port base priority Port based Priority interface Priority Assign Port with one of four available priority queues High Middle Low and Lowest Apply...

Page 61: ...It describes that the output priority of a packet is determined by the user priority field in 802 1Q VLAN tag The priority value is supported 0to7 COS value map to 4 priority queues High Middle Low a...

Page 62: ...field in the IP header of a packet This TOS field is also used by Differentiated Services and is called the Differentiated Services Code Point DSCP This field can determine the output priority of a p...

Page 63: ...Security Only IP in the Secure IP List can manage the switch through your defined management mode WEB Telnet SNMP IP Security interface Label Description IP security MODE Enable Disable the IP securit...

Page 64: ...s to hardware forwarding database If port security is enabled at Port Control page only the frames with MAC addresses in this list will be forwarded otherwise will be discarded Port Security interface...

Page 65: ...rwarding to specific MAC addresses in list Any frames forwarding to MAC addresses in this list will be discarded Thus the target device will never receive any frame MAC Blacklist interface Label Descr...

Page 66: ...Disable 802 1X Radius Server function Radius Server IP The IP address of the authentication server Server port Set the UDP port number used by the authentication server to authenticate Account port S...

Page 67: ...nt response to an EAP request Server Timeout Set the period of time the switch waits for a Radius server response to an authentication request Max Requests Set the maximum number of times to retry sen...

Page 68: ...1x authorized mode of each port 802 1x Port Authorize interface Label Description Port Authorized Mode Reject force this port to be unauthorized Accept force this port to be authorized Authorize the s...

Page 69: ...E7MS4_REV Rev 4 30 14 PAGE 69 INSTALLATION AND OPERATION MANUAL CNGE3FE7MS4 TECH SUPPORT 1 888 678 9427 802 1x Port Authorized Mode Show 802 1x port authorized state 802 1x Port Authorize State interf...

Page 70: ...h through selected system events Warning Fault Relay Alarm When any selected fault event happens the Fault LED in switch panel will light and the electric relay will signal at the same time System War...

Page 71: ...interface Label Description E mail Alart Enable Disable transmission system warning events by Email SMTP Server IP Address Setting up the mail server IP address Mail Subject The subject line of the Em...

Page 72: ...ox cannot be checked when SYSLOG or SMTP is disabled System Warning Event Selection interface Label Description Device cold start When the device executes cold start the system will issue a log event...

Page 73: ...destination MAC address is to be forwarded through a given potential transmission port MAC Address Table interface Label Description Port NO Show all MAC addresses mapping to a selected port in table...

Page 74: ...how port link status State Show ports enable or disable TX GOOD Packet The number of good packets sent by this port TX Bad Packet The number of bad packets sent by this port RX GOOD Packet The number...

Page 75: ...ports out to a selected RX destination port as well as sending the frame where it normally would have gone Keep all source ports unchecked in order to disable port monitoring Port monitoring interfac...

Page 76: ...s DDM function measure the temperature of the apparatus and manage and set up event alarm module through DDM WEB System Event Log If system log client is enabled the system event logs will be shown in...

Page 77: ...on will be lost when power is turned off or the system is reset System Configuration interface Label Description Save Save all configurations Help Show help file Factory Default Factory Default interf...

Page 78: ...gement You can use console or telnet to management switch by CLI CLI Management by RS 232 Serial Console 9600 8 none 1 none Before Configuring by the RS 232 serial console use an RJ45 to DB9 F cable t...

Page 79: ...INS_CNGE3FE7MS4_REV Rev 4 30 14 PAGE 79 INSTALLATION AND OPERATION MANUAL CNGE3FE7MS4 TECH SUPPORT 1 888 678 9427 Step 2 Input a name for new connection Step 3 Select to use COM port number...

Page 80: ...8 678 9427 Step 4 The COM port properties setting 9600 for Bits per second 8 for Data bits None for Parity 1 for Stop bits and none for Flow control Step 5 The Console login screen will appear Use the...

Page 81: ...IP Address 192 168 10 1 Subnet Mask 255 255 255 0 Default Gateway 192 168 10 254 User Name admin Password admin Follow the steps below to access the console via Telnet Step 1 Telnet to the IP address...

Page 82: ...Privileged this mode to Display advance function status save configures Global configuration Enter the configure command while in privileged EXEC mode switch config To exit to privileged EXEC mode ent...

Page 83: ...ription System Description G Set switch system description string switch config system description xxx system contact System Contact G Set switch system contact window string switch config system cont...

Page 84: ...for DHCP clients by port switch config interface fastEthernet 2 switch config if dhcpserver ipbinding 192 168 1 1 show dhcpserver configuration P Show configuration of DHCP server switch show dhcpser...

Page 85: ...Enable security of interface switch config interface fastEthernet 2 switch config if security enable no security I Disable security of interface switch config interface fastEthernet 2 switch config i...

Page 86: ...specify the state mode of operation for Ethernet ports Use the disable form of this command to disable the port switch config interface fastEthernet 2 switch config if state Disable show interface co...

Page 87: ...ma ex 2 3 6 Workport The amount of work ports this value could not be less than zero or be large than the amount of member ports switch config aggregator group 1 1 4 lacp workp 2 or switch config aggr...

Page 88: ...ag 2 3 6 99 or switch vlan vlan 8021q port 3 trunk link tag 3 20 vlan 8021q port PortNumber hybrid link untag UntaggedVID tag TaggedVID List V Assign a hybrid link for VLAN by port if the port belong...

Page 89: ...to specify the interval between hello bridge protocol data units BPDUs switch config spanning tree hello time 3 spanning tree forward time seconds G Use the spanning tree forward time global configura...

Page 90: ...ing tree no spanning tree G Disable spanning tree switch config no spanning tree Commands Set List QoS command set Commands Level Description Example qos policy weighted fair strict G Select QOS polic...

Page 91: ...uery auto G Set IGMP query to auto mode switch config Igmp query auto Igmp query force G Set IGMP query to force mode switch config Igmp query force show igmp configuration P Displays the details of a...

Page 92: ...c address table P Show all MAC address table switch show mac address table show mac address table static P Show static MAC address table switch show mac address table static show mac address table fil...

Page 93: ...trings public right RO or switch config snmp community strings public right RW snmp snmpv3 user User Name password Authentication Password Privacy Password G Configure the user profile for SNMPV3 agen...

Page 94: ...TX destination port of monitor function switch config monitor tx show monitor P Show port monitor information switch show monitor monitor RX TX Both I Configure source port of monitor function switch...

Page 95: ...tch config 8021x system sharekey 123456 8021x system nasid words G Use the 802 1x system nasid global configuration command to change the NAS ID switch config 8021x system nasid test1 8021x misc quiet...

Page 96: ...d the file name of image switch config restore flash restore_cfg upgrade flash upgrade_ fw G Upgrade firmware by TFTP and need to specify the IP of TFTP server and the file name of image switch config...

Page 97: ...e both event systemlog Link UP Link Down Both I Set port event for system log switch config interface fastethernet 3 switch config if event systemlog both event smtp Link UP Link Down Both I Set port...

Page 98: ...fig sntp daylight period 20060101 01 01 20060202 01 01 sntp daylight offset Minute G Set offset of daylight saving time if SNTP function is inactive this command can t be applied switch config sntp da...

Page 99: ...ing Port G Configure 1st 2nd Ring Port switch config ring ringport 7 8 Ring couplingport Coupling Port G Configure Coupling Port switch config ring couplingport 1 Ring controlport Control Port G Confi...

Page 100: ...dresses Priority Queues 4 Processing Store and Forward Switch Properties Switching latency 7 us Switching bandwidth 7 4 Gbps Max Number of Available VLANs 4096 IGMP multicast groups 1024 Port rate lim...

Page 101: ...n C Ring Master mode Fault indicator Amber Indicate unexpected event occurred 10 100BASE T X RJ45 Port Indicator Green Link Act Amber Duplex Collision 10 100 1000BASE T X RJ45 Port Indicator Green Lin...

Page 102: ...vals EMI FCC Part 15 CISPR EN55022 class A EN50155 EN50121 3 2 EN55011 EN50121 4 EMS EN61000 4 2 ESD EN61000 4 3 RS EN61000 4 4 EFT EN61000 4 5 Surge EN61000 4 6 CS EN61000 4 8 EN61000 4 11 Shock IEC6...

Page 103: ...INS_CNGE3FE7MS4_REV Rev 4 30 14 PAGE 103 INSTALLATION AND OPERATION MANUAL CNGE3FE7MS4 TECH SUPPORT 1 888 678 9427...

Page 104: ...CH SUPPORT 1 888 678 9427 INFO COMNET NET 8 TURNBERRY PARK ROAD GILDERSOME MORLEY LEEDS UK LS27 7LE T 44 0 113 307 6400 F 44 0 113 253 7462 INFO EUROPE COMNET NET MECHANICAL INSTALLATION INSTRUCTIONS...