Step 6 – Checking the Panel Bus Jumper
Make sure that the panel bus jumper is still firmly connected to the faceplate (Figure 13).
Important:
The connector is keyed. The polarized tab on the panel connector fits into the opening in the header
connector on the back of the faceplate.
Step 7 – Installing the Cover
Install the 184U1 Cover (provided) to shield the shelf from foreign particles. The cover, which is made of clear,
flame-retardant plastic, slides on and off the shelf.
To install the cover:
Slide the cover through the flanges on the shelf until the cover reaches the back wall of the shelf (Figure 13).
Important:
Dust covers are installed in the ports to protect the fibers connected to the back of the faceplate. Do
not remove the dust cover from a port until you connect a patch cord to that port. If you remove a patch cord
later, replace the dust cover in the port.
Figure 13 Checking the Panel Bus Jumper and Installing the Cover on the Shelf
Flange
Dust cover
Panel bus jumper
Back of faceplate
Polarized tab on panel connector
Inside of shelf
Cover