background image

ADCP-90-451 • Rev C • October 2020

Page 14

© 2020, CommScope, Inc.

7.2

Attenuators

Attenuators decrease the optical power in a fiber by a specific or adjustable amount. Once the
desired level of attenuation is determined, fixed attenuators may be inserted in the fiber optic
line to deliver a precise output. Optional attenuators are installed on tab side of the sliding
adapter packs. See 

Figure 9

.

7.3

12-Position Termination and Splice Tray

 

Termination and splice trays provide 12 termination and splice positions. Install the cables for a
12-position termination and splice tray as follows: 

1. Break out the cable corresponding to the dimensions provided in 

Figure 11

.

2. Route the cables into the tray as shown in 

Figure 12

, and perform the splices outside the

tray at an adjacent work area, as shown. Perform the splices following local practice.
Refer to pigtail installation drawing (provided with FMT) for pigtail connection scheme. 

3. Loop the cables three times around the radius limiters as shown in 

Figure 13

.

Figure 11. 12-Position Termination and Splice Tray Breakout Dimensions

4. Carefully position the tray within the splice area as shown in 

Figure 14

. Make certain that

the pre-terminated and customer fiber bundles are properly routed around the appropriate
radius limiters as they enter the FMT (see 

Figure 14

).

5. Use the kurly locks provided to bundle fibers together as needed. Place kurly locks at

locations indicated in 

Figure 15

.

6. Verify that the completed tray looks as shown (see 

Figure 15

).

Note: 

Splicing instructions are not included. For splicing instructions, follow local practice.

Note: 

Tie off the cable at the tie off point shown in 

Figure 13

, using a one-inch section of

soft wall jacket per the breakout dimensions shown in 

Figure 11

.

48 IN. (121.9 CM)

1 IN. (2.5 CM)

16967-A

133 IN. (337.8 CM)

SOFT WALL

PIGTAIL BUNDLE

SECTION OF

SOFT WALL

JACKET

900 MICRON

JACKETED

FIBERS

Summary of Contents for FMT-D

Page 1: ...ng Bulkhead Plate Adapters 20 8 4 Closing the Tray 20 9 CUSTOMER INFORMATION AND ASSISTANCE 20 INTRODUCTION This manual describes the CommScope Fiber Management Tray D FMT D and provides all information required to install and use this product The FMT is a fiber optic tray that provides a variety of rack mount and functional options All options are covered in this manual to the extent of relevance...

Page 2: ...cable discrete slack storage 32 48 or 60 cable bulk slack storage capacity dependent on cable diameter Rack mount and recess options include EIA or WECO reversible 19 or 23 inch 48 26 or 58 42 cm with mounting brackets for mounting in 40mm or 5 inch recess Danger Danger is used to indicate the presence of a hazard that will cause severe personal injury death or substantial property damage if the h...

Page 3: ... clockwise Edge Protectors Protect cables from sharp angles at bend points Release Tabs Allows the FMT tray to open Lock Open Latch Allows the technician to lock open the FMT while working in the tray Rear Radius Limiters Left and Right Maintain a protective minimum bend radius for cables routed into panel Tie Lances Provide anchor points for securing fibers Storage Radius Limiters Provide service...

Page 4: ...Each adapter pack provides easy access for connecting cables and cleaning connectors Product offerings for adapters connectors include most industry standard multimode and singlemode types Figure 2 shows a closed tray with the sliding radius limiter in a closed position Also shown with the optional lock Figure 2 FMT Features Closed Tray Shown LOCK OPTIONAL MOUNTING BRACKET ONE EACH SIDE 23739 A SL...

Page 5: ...ray Figure 3 FMT Dimensions 1 71 IN 4 34 CM 11 05 IN 28 05 CM 19 INCH FMT 17 21 IN 43 7 CM TOP VIEW FRONT VIEW RECESS OPTIONS 23740 A 40 mm 2 2 INCH 5 INCH 6 5 INCH 1 535 IN 3 07 IN 5 0 IN 6 5 IN 3 9 CM 7 8 CM 12 7 CM 16 5 CM ETSI 19 INCH EIA WECO 23 INCH EIA WECO 20 28 IN 18 31 IN 22 32 IN 51 5 CM 46 5 CM 56 7 CM RACK WIDTH OPTIONS ETSI WECO EIA 0 98 IN 1 0 IN 1 25 IN 2 5 CM 2 5 CM 3 25 CM RACK T...

Page 6: ...ires shipment at a future date Table 1 Fiber Management Tray Specifications ITEM DESCRIPTION Dimensions H W D See Figure 3 on page 5 Approximate Weight 7 9 lbs 3 98 Kg Configuration Options and Capacity Termination storage 12 or 24 terminations Termination storage 4 MicroVAMs Termination storage Universal bulkhead 12 24 or 48 Termination splice Universal bulkhead 12 24 or 48 Bulk storage 3 mm O D ...

Page 7: ...ar and side of the panel see Figure 5 bonding locations are used to bond or ground the panel to the frame or office earth ground When grounding the panel follow local practices or use the instructions provided with the grounding kit Do not ground the OSP cable to the panel The cable must be grounded to either the frame or office ground If non metallic OSP cable is used connect the office or frame ...

Page 8: ... black Table 2 summarizes possible uses of VCGs for various combinations of rack width and recess 1 If the rack width is 19 inches 48 26 cm or ETSI 20 28 inches 51 5 cm and Table 2 Possible Uses of VGCs RACK WIDTH RECESS VERTICAL CABLE GUIDE 19 inches 48 26 cm 40 mm 1 54 inch 2 2 inch 5 59 cm Figure 6 3 1 inch 7 9 cm 5 inch 12 7 cm 6 5 inch 16 5 cm Figure 7 23 inches 58 42 cm 40 mm 1 54 inch 2 2 i...

Page 9: ...ch Rack Mount b Recess is 3 1 inch 7 9 cm 5 inch 12 7 cm or 6 5 inch 16 5 cm and Mount the VCGs on the FMT using the VCG mounting bracket Secure VCG and VCG mounting bracket to the FMT using the holes located at the front of the FMT Refer to Figure 7 2 If rack width is 23 inches 58 42 cm and is recessed mounted with cable routed down mount the VCGs on the FMT using the VCG mounting bracket Secure ...

Page 10: ...pe Inc Figure 7 Installing VCGs 3 1 5 or 6 5 inch recess 19 Inch Rack Mount Figure 8 Installing VCGs 3 1 5 or 6 5 inch recess 23 Inch Rack Mount MOUNTING BRACKET VCG MOUNTING BRACKET 23755 A VERTICAL CABLE GUIDE VCG MOUNTING BRACKET VERTICAL CABLE GUIDE ...

Page 11: ... and connect the cables within the FMT as required by the configuration Refer to the installation procedure that corresponds to the FMT configuration 6 Adjust the cables within the FMT until all excess slack is removed or stored 7 Secure the cables to the back of the FMT at the rear tie off point see Figure 9 and Figure 10 Note that a tie off point is provided on both the left and right side 8 Use...

Page 12: ...ring Cable Typical Configuration for IFC Stranded Cable 23742 A ROUTE CABLE INTO FMT THROUGH SLIDING RADIUS LIMITER CABLE CLAMP AND MOUNTING BRACKET CABLE CLAMP AND MOUNTING BRACKET DETAIL OF CABLE TIE OFF POINT PLACE OPTIONAL ATTENUATOR ON THIS SIDE OF SLIDING ADAPTER PACK TIE LANCE ...

Page 13: ...ion for Ribbon Cable 23745 A ROUTE PROTECTIVE TUBING INTO FMT THROUGH SLIDING RADIUS LIMITER CABLE CLAMP AND MOUNTING BRACKET CABLE CLAMP AND MOUNTING BRACKET RIBBON BLOCKING KIT RIBBON BLOCKING KIT DETAIL OF CABLE TIE OFF POINT PLACE OPTIONAL ATTENUATOR ON THIS SIDE OF SLIDING ADAPTER PACK TIE LANCE RIBBON CABLE ...

Page 14: ... Refer to pigtail installation drawing provided with FMT for pigtail connection scheme 3 Loop the cables three times around the radius limiters as shown in Figure 13 Figure 11 12 Position Termination and Splice Tray Breakout Dimensions 4 Carefully position the tray within the splice area as shown in Figure 14 Make certain that the pre terminated and customer fiber bundles are properly routed aroun...

Page 15: ...020 Page 15 2020 ComScope Inc Figure 12 Cable Routing for 12 Position Termination and Splice Tray Step 2 CUSTOMER FIBER BUNDLE TIE OFF SPLICE TRAY CUSTOMER FIBER BUNDLE PRE TERMINATED FIBER BUNDLE 20344 A TO SLIDING ADAPTER PACKS ...

Page 16: ...12 Position Termination and Splice Tray Step 3 LOOP THREE TIMES CUSTOMER FIBER BUNDLE TIE OFF CUSTOMER FIBER BUNDLE PRE TERMINATED FIBER BUNDLE SPLICE TRAY 20345 A TO SLIDING ADAPTER PACKS CUSTOMER FIBER TIE OFF POINT TIE OFF POINT PRE TERMINATED FIBER PRE TERMINATED FIBER CUSTOMER FIBER ...

Page 17: ...le Routing for 12 Termination and Splice Tray Step 4 Figure 15 Completed Cable Routing for 12 Position Termination and Splice Tray CUSTOMER FIBER BUNDLE TIE OFF 20346 A TO SLIDING ADAPTER PACKS 20205 A KURLY LOCK 3 PLACES TIE OFF CUSTOMER PATCHCORDS CUSTOMER FIBER BUNDLE ...

Page 18: ...er to the routing diagrams provided in Section 7 Installing and Routing Cables For instructions on accessing adapters refer to the following instructions 8 1 Opening Tray To open the FMT tray slide the release tabs inward with both hands and pull the drawer straight out as far as it goes The latch locks the tray in the open position as shown in Figure 16 Figure 16 Tray Locked in Open Position Caut...

Page 19: ...Close the tray Danger Infrared radiation is invisible and can seriously damage the retina of the eye Do not look into the ends of any optical fiber Do not look directly into the optical adapters of the adapter packs Exposure to invisible laser radiation may result An optical power meter should be used to verify active fibers A protective cap or hood MUST be immediately placed over any radiating ad...

Page 20: ...iber kinks or microbends occur as a result of fiber routing 9 CUSTOMER INFORMATION AND ASSISTANCE To find out more about CommScope products visit us on the web at www commscope com For technical assistance customer service or to report any missing damaged parts visit us at http www commscope com SupportCenter For information on patents refer to http www cs pat com Danger Infrared radiation is invi...

Reviews: