10 CROSS-CONNECTING DISTRIBUTION PORTS
This section provides instructions for installing a cross-connect patch cord between two
distribution ports. Cross-connecting two distribution ports may be required in certain
applications where the fibers from two cables need to be patched together. Use the
216B key tool to un-latch and open the cabinet door as needed for this procedure.
Use the following procedure to install a cross-connect patch cord between two
distribution ports:
1. Check the designation label on the cabinet doors to determine the port numbers
that will be cross-connected.
2. Locate the sliding adapter packs that contain the bulkhead adapters for the ports
identified in step 1.
3. Pull upward on the small tab on top of both sliding adapter packs and lift each
adapter pack to the raised position as shown in
Figure 61. Adapter Pack Raised to Access Position
4. Remove the dust caps from the two bulkhead adapters that required cross-
connecting.
5. Obtain a 1.5 meter (59 inches) reduced bend radius patch cord terminated with
APC/SC connectors.
Warning: Infrared radiation is invisible and can seriously damage the retina of the eye. Do not
look into the ends of any optical fiber. Do not look directly into the optical adapters or
connectors. Exposure to invisible laser radiation may result. An optical power meter should be
used to verify active fibers. A protective cap or hood MUST be immediately placed over any
radiating adapter or optical connector to avoid the potential of dangerous amounts of radiation
exposure. This practice also prevents dirt particles from entering the adapter or connector.
1. PULL UPWARD ON
TAB AND LIFT TO
RAISED POSITION
2. REMOVE
ADAPTER
DUST CAP
3. REMOVE FERRULE
DUST CAP
4. CLEAN AND
INSERT CONNECTOR
24320-A