Install and Connect the Subrack Cards
Optical Link Loss
Optical loss is calculated by adding the attenuation due to the length of the fiber optic cable, the number of
connectors in the link, and the number of splices. If there are other optical devices in the link, then their
attenuation needs to be included as well (mux, demux, add/drop, etc.).
Optical Link Loss = fiber length(km) * optical attenuation/km
+ Splice Loss * Number of splices
+ Connector Loss * Number of Connectors
Minimum Performance Levels
The values below are the minimum performance specifications for fiber optic components noted in
ANSI/TIA/EIA-568-C.3 Optical Fiber Cabling Components, with key performance specifications shown in
below.
Table 12.
Minimum Performance of Optical Components
Parameter
Minimum Performance
1
Mated connector pair
0.75 dB
Splice
0.3 dB
1
Actual performance may be better than the minimum
performance values noted.
Table 13.
10 Gbps Ethernet Standards for Optical Link Budget
SFP+ Module Type
10GBASE-SR
10GBASE-LR
10GBASE-ER
Fiber Class
OM3
OM4
G.652
G.652
Maximum Distance (m)
300
400
10,000
1
40,000
1
Wavelength of Operation (nm)
850
850
1310
1550
Loss per km @ wavelength (dB)
3.5
3.5
0.5
0.5
Allowed Measured Loss (dB)
2.6
2.9
6.0
11.0
Allowed Back Reflection (dB)
-20
-20
-26
-26
1
Maximum Distance may require < 0.5dB/km loss. Most high quality single mode cables
are so rated.