Shielded patch panels are designed to protect the

internal electronic components from electromagnetic

interference (EMI).

1. Using the screws, mount the patch panel onto

the rack. Refer to Figure 1.
2. Plug a connector (from the trunk cable) into

each MRJ21 receptacle (at the back of the patch

panel). Refer to Figure 2. Make sure to align the

keying features of the connector and receptacle.

Ensure that the connector is fully seated, 

then

using a small cross–recessed tipped screwdriver,

turn the jack screws of the connector 

clockwise

and tighten to a maximum torque of 0.23 Nm

[2 lbf–in.].

3. For AMPTRAC patch panels, plug the connector

of an I/O cable assembly (PN 1499507–[ ]) from

the analyzer into each HDP–22 connector (at the

back of the patch panel). See Figure 2.
4. Install the retro–fit kit onto the rack according to

Instruction Sheet 408–10170. Using cable ties or

similar fasteners, attach the cables to the tie–down

bar. It is recommended to maintain a minimum

bend radius of 50.8 mm [2 in.] when securing and

routing cables. See Figure 2.

For port–to–cable pair cross–reference, refer to

Figure 3.

Figure 2

Figure 3

Patch panels are not repairable. DO NOT use a

damaged patch panel or one with damaged or

defective connectors.