TC-96307-IP
Page 11
© 2022
CommScope
. All Rights Reserved.
2.4 Blades
Propel blades have rails that guide Propel connection components into lanes. Each blade has 12
lanes labeled A to L.
shows a fully occupied blade. The components shown are 3 of the
available 4 sizes. As shown in
, Propel components can be installed from front or rear.
Figure 5. Fully Loaded Blade
Note:
For a component to be installed from the front, the front cable management clip(s) must
be removed to provide access to the desired installation lane(s).
Table 4. Available MPO Modules and Adapter Packs
Catalog
#
8-fiber modules/
adapter packs
12-fiber modules/
adapter packs
16-fiber modules/
adapter packs
24-fiber modules/
adapter packs
PPL-1U
up to 6 per blade/18
per panel
up to 4 per blade/12
per panel
up to 3 per blade/9
per panel
up to 2 per blade/6
per panel
PPL-2U
up to 6 per blade/36
per panel
up to 4 per blade/24
per panel
up to 3 per blade/18
per panel
up to 2 per blade/12
per panel
PPL-4U
up to 6 per blade/72
per panel
up to 4 per blade/48
per panel
up to 3 per blade/36
per panel
up to 2 per blade/24
per pane
Each blade has 12 lanes
Requires 2 lanes
Requires 3 lanes
Requires 4 lanes
Requires 6 lanes