Instruction Sheet
Page 5 of 9
Step 2
– Install Shelf and Connect Panel Bus Jumper
1. Mount the shelf in the rack using the four mounting screws provided.
For a 19-inch (483mm) rack, mount shelf to rack using the pre-installed mounting brackets and four
12-24 x 1/2-inch screws provided.
For a 23-inch (584mm) rack, use the 600-23BRKT accessory kit (ordered separately) and install one
conversion bracket on each side of shelf using four 10-32 x 3/8-inch screws included in the kit. Mount
shelf to rack using four 12-24 x 1/2-inch screws provided.
For an ETSI rack, use the 600-23BRKT accessory kit (ordered separately) and install one conversion
bracket on one side of the shelf using two of the four 10-32 x 3/8-inch screws included in the kit. Mount
shelf to rack using four M6 x 12 screws (not provided). The shelf will not be centered in the rack.
2. Connect the keyed female 10-pin connector on the panel bus jumper into the nearest cable bus port on
panel bus as shown.
3. Install spare port built into jumper cordage into panel bus frame by turning it at an angle, inserting into
frame, and turning it back perpendicular to frame.