TECP-92-159 • Rev D • May 2018
Page 16
© 2018
CommScope
. All Rights Reserved.
3.6
Preparing and Connecting a Pre-Connectorized Cable
This section tells how to prepare and connect a multi-fiber cable. The cable being installed must
conform to the breakout dimensions provided.
Use the following procedure.
1. If the cable is being connectorized:
a.
for breakout dimensions for variables L2 to L5.
b. Associate these variables to the breakout diagrams given in
(IFC Stranded)
(IFC Ribbon), or
(OSP) for the cable type being installed.
2. Determine the correct clamp and grommet combination required to secure the cable to the
panel. For details on the cable clamp itself, refer to
.
3. Determine the cable entry location. Cables may enter the panel from either top or bottom
and may be clamped to either the left or right side.
O
S
P/IFC
CABLE
FANOUT LENGTH
‘L3’ +0.0 IN./-6.0 IN.
(+0.0 CM/-15.2 CM)
BREAKOUT LENGTH
‘L2’ +0.0 IN./-6.0 IN.(+0.0 CM/-15.2 CM)
MULTIFIBER
S
UBUNIT
S
CONNECTOR
S
HEAT
S
HRINK
6.0 IN. (15.2 CM)
CLAMP
25717-A
CLAMP PO
S
ITION
‘L5’ +0.0 IN./-6.0 IN.(+0.0 CM/-15.2 CM)
Figure 17. IFC Stranded Cable Breakout Dimensions
Table 2. Breakout Dimensions
(NOTE: Dimensions are the same for 1RU and 2RU panels.)
CABLE TYPE
FIGURE
L2
L3
L4
L5
IFC Stranded
52.0 in
(132.1 cm)
25.25
(64.1 cm)
N/A
53.25
(135.3 cm)
IFC Ribbon
50.75 in
(128.9 cm)
24.75 in
(62.9 cm)
26 in
(66 cm)
53.25
(135.3 cm)
OSP Ribbon
Cable
52.75 in
(134 cm)
24.75 in
(62.9 cm)
28 in
(71.1 cm)
54.75 in
(139.1 cm)