CSCMA-APH-6-SM1907A
R410A All DC Inverter Mini VRF
Specifications & Performance 47
CSCMA-APH007-6SB
Cooling
Combination
(%)
(Capacity
index)
Outdoor
temperature
(°F DB)
Indoor temperature(°F DB/WB)
DB:69.4,WB:57.2
DB:73.9,WB:60.8
DB:78.4,WB:64.4
DB:80.6,WB:66.2
DB:82.7,WB:68
DB:87.3,WB:71.6
DB:89.6,WB:75.2
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
50%
23
5.23
0.73
6.26
0.85
7.25
0.97
7.75
1.02
8.25
1.07
9.24
1.22
10.3
1.32
28.4
5.23
0.74
6.26
0.86
7.25
0.98
7.75
1.03
8.25
1.09
9.24
1.24
10.3
1.33
32
5.23
0.75
6.26
0.88
7.25
1
7.75
1.05
8.25
1.11
9.24
1.26
10.3
1.36
35.6
5.23
0.76
6.26
0.89
7.25
1.02
7.75
1.06
8.25
1.12
9.24
1.26
10.3
1.38
39.2
5.23
0.77
6.26
0.9
7.25
1.03
7.75
1.07
8.25
1.15
9.24
1.29
10.3
1.42
42.8
5.23
0.78
6.26
0.92
7.25
1.04
7.75
1.1
8.25
1.17
9.24
1.31
10.3
1.46
46.4
5.23
0.8
6.26
0.93
7.25
1.06
7.75
1.12
8.25
1.18
9.24
1.34
10.3
1.51
50
5.23
0.82
6.26
0.94
7.25
1.08
7.75
1.14
8.25
1.22
9.24
1.37
10.3
1.53
53.6
5.23
0.82
6.26
0.96
7.25
1.1
7.75
1.16
8.25
1.24
9.24
1.39
10.3
1.55
57.2
5.23
0.83
6.26
0.97
7.25
1.11
7.75
1.19
8.25
1.26
9.24
1.42
10.3
1.58
60.8
5.23
0.85
6.26
0.98
7.25
1.13
7.75
1.21
8.25
1.28
9.24
1.44
10.3
1.61
64.4
5.23
0.86
6.26
1
7.25
1.15
7.75
1.22
8.25
1.3
9.24
1.47
10.3
1.64
68
5.23
0.87
6.26
1.01
7.25
1.16
7.75
1.24
8.25
1.33
9.24
1.49
10.3
1.67
69.8
5.23
0.88
6.26
1.02
7.25
1.18
7.75
1.25
8.25
1.34
9.24
1.51
10.3
1.69
73.4
5.23
0.89
6.26
1.04
7.25
1.19
7.75
1.28
8.25
1.36
9.24
1.53
10.3
1.72
77
5.23
0.9
6.26
1.05
7.25
1.22
7.75
1.3
8.25
1.41
9.24
1.61
10.3
1.84
80.6
5.23
0.92
6.26
1.1
7.25
1.29
7.75
1.39
8.25
1.49
9.24
1.72
10.3
1.96
84.2
5.23
0.97
6.26
1.16
7.25
1.36
7.75
1.47
8.25
1.59
9.24
1.83
10.3
2.09
87.8
5.23
1.02
6.26
1.22
7.25
1.44
7.75
1.57
8.25
1.69
9.24
1.94
10.3
2.22
91.4
5.23
1.08
6.26
1.3
7.25
1.53
7.75
1.66
8.25
1.79
9.24
2.06
10.3
2.36
95
5.23
1.15
6.26
1.37
7.25
1.62
7.75
1.75
8.25
1.89
9.24
2.19
10.3
2.51
98.6
5.23
1.21
6.26
1.45
7.25
1.72
7.75
1.86
8.25
2.01
9.24
2.33
10.3
2.67
102.2
5.23
1.27
6.26
1.53
7.25
1.82
7.75
1.97
8.25
2.13
9.24
2.47
10.3
2.83
105.8
5.23
1.33
6.26
1.59
7.25
1.88
7.75
2.06
8.25
2.22
9.24
2.6
10.3
2.96
109.4
5.23
1.41
6.26
1.7
7.25
1.95
7.75
2.15
8.25
2.28
9.24
2.73
10.3
3.1
Note:
1
.
is tested under our standard condition.
2. Avoid to run the unit when the temperature is above 109.4
℉
(43
℃
).
3. The above table shows the average value of conditions may operate.
4. It is recommended to connect less than 130%.