Comfortflame CGDV32NR (PR)-3 Installation Manual Download Page 4

INSTALLING GAS PIPING TO

FIREPLACE LOCATION

  WARNING:  A  qualified 

service  person  must  connect 

fireplace

 to gas supply. Follow 

all local codes.

  CAUTION:  For  propane/LP 

units, never connect 

replace di-

rectly to the propane/LP supply. 

This heater requires an external 

regulator (not supplied). Install 

the external regulator between 

the 

replace  and  propane/LP 

supply. 

  WARNING:  For  natural 

gas,  never  connect  heater  to 

private (non-utility) gas wells. 

This gas is commonly known 

as wellhead gas.

Installation Items Needed

Before  installing 

fireplace

,  make  sure  you 

have the items listed below.

 

external regulator (supplied by installer)

 

piping (check local codes)

 

sealant (resistant to propane/L

P

 gas)

 

equipment shuto

ff valve *

 

test gauge connection *

 

sediment trap

  tee joint

 

pipe wrench

 

approved

 

flexible

 gas line with gas 

connec

-

tor (if allowed by local codes)

* A  CSA  design-

c

erti

ed 

equipment

  shutoff 

valve with 

1/8"

 NPT 

tap

 is an 

acceptable

 al-

ternative to test gauge 

connection.

 

Purchase 

the  CSA 

design-cer

t

ified

 

equipmen

t  shutoff 

valve from your retailer.
For 

propane/L

connection

 only, the installer 

must 

supply

  an  external  regulator. The  ex-

ternal  regulator  will 

reduce

 

incoming

  gas 

pre

ssure.  You  must  redu

c

e  in

c

oming  gas 

pressure

 to between 1

1"

 and 

14"

 of water. If 

you  do  not  redu

c

e  in

c

oming  gas 

pre

ssure, 

Figure 31 - External Regulator with Vent 

Pointing Down (Propane/LP Only)

Propane/L

Supply

 Tank 

External 

Regulator 

with Vent 

Pointing 

Down

firep

l

ace

 regulator damage 

co

uld 

occ

ur. Install 

external regulator with the vent 

poin

ting down 

as shown in Figure 31. Pointing the vent down 

protects it from freezing rain or sleet.

  CAUTION:  Use  only  new, 

black  iron  or  steel  pipe.  Inter-

nally-tinned copper tubing may 

be used in certain areas. Check 

your  local  codes.  Use  pipe  of 

1/2" inside diameter or greater to 

allow proper gas volume to 

fire

-

place. If pipe is too small, undue 

loss of volume will occur.

Installation must in

c

lude an 

equipmen

t shutoff 

valve, union and 

plugged

 1

/8"

 NPT t

ap

Loca

te 

NPT 

tap

 within 

reach

 for test gauge hook 

up. 

NPT t

ap

 must be 

up

stream from 

fireplac

e (see 

Figure 32, page 21).

IMPORTANT:

 Install main gas valve 

(equip

-

ment shutoff 

valve)

 in an 

accessible

 

location. 

The main gas valve is for turning on or shutting 

of

f the gas to the appliance.

Che

ck

  your  building 

c

odes  for  any  s

pec

ial 

requirements for 

locating

 

equipment

 shutoff 

valve to fireplaces.
Apply

 

pipe

 joint sealant lightly to male NPT 

threads. This will 

preven

excess

 sealant from 

going into 

pipe.

 

Excess

 sealant in 

pipe

 

could 

result in clogged fireplace valves.

  WARNING:  Use  pipe  joint 

sealant that is resistant to liquid 

petroleum (LP) gas. 

FIREPLACE INSTALLATION

Continued

Summary of Contents for CGDV32NR (PR)-3

Page 1: ...ed service person to do this WARNING Ifthereisaduplex electrical outlet installed in the right side of the bottom of the fireplace base area be sure that theelectricalpowertotheoutletis turnedoffbeforeproceedingwith blower installation Failure to do this may result in serious injury Model BK Installation Follow all instructions provided in blower accessory kit 1 Attach power cord to blower motor by...

Page 2: ...Decal 12 in Front of Blower Speed Control Control Shaft Locknut Control Knob Switch Bracket Blower Plug In Duplex Outlet Located underneath firebox floor against lower right outside wall Model BKT Installation Note When installing BKT thermostati cally controlled blower you must first secure thermal switch bracket to blower if it has not already been factory installed 1 Place green ground wire with r...

Page 3: ...h Bracket Power Cord Air Flow Direction Magnetic Strips Figure 30 Blower Wiring Diagram for Thermostat Controlled Models Blower Wiring Diagram CAUTION Label all wires prior to disconnection when servicingcontrols Wiringerrors can cause improper and dan gerous operation Verify proper operation after servicing Blue Variable Fan Switch Fan Switch N O Green White On 110 115 V A C Blower Motor Black Of...

Page 4: ...re to between 11 and 14 of water If you do not reduce incoming gas pressure Figure 31 External Regulator with Vent Pointing Down Propane LP Only Propane LP Supply Tank External Regulator with Vent Pointing Down fireplace regulator damage could occur Install external regulator with the vent pointing down as shown in Figure 31 Pointing the vent down protects it from freezing rain or sleet CAUTION Use...

Page 5: ...gshow a leak Correct all leaks at once PRESSURE TESTING GAS SUPPLY PIPING SYSTEM Test Pressures In Excess Of 1 2 PSIG 3 5 kPa 1 Disconnectfireplaceanditsindividualequip ment shutoff valve from gas supply piping system Pressures in excess of 1 2 psig 3 5 kPa will damage fireplace gas regulator 2 Cap off open end of gas pipe where equip ment shutoff valve was connected 3 Pressurize supply piping syste...

Page 6: ...ee Figure 35 or Figure 36 Apply noncorrosive leak detection fluid to all joints Bubbles forming show a leak Correct all leaks at once 5 Light fireplace see Operation page 26 Check all other internal joints for leaks 6 Turn off fireplace see To Turn Off Gas to Appliance page 27 INSTALLING OPTIONAL WALL MOUNT SWITCH GWMS2 1 Connect one terminal of 25 ft wire for wall switch to TPTH terminal on valve Co...

Page 7: ...see Figure 40 2 Attach terminal wires to battery Place battery into battery housing 3 Replace battery cover onto remote control unit Figure 40 Installing Battery in Hand Held Remote Control Unit 9 Volt Battery Battery Housing Battery Cover Terminal Wires Remote Control Unit REMOVING REPLACING GLASS DOOR CAUTION Do not operate thisfireplacewithabrokenglass door panel or without the glass door panel ...

Page 8: ...2 Removing Replacing Glass Door Lock Unlock Glass Frame Assembly Screw Hinge Latch INSTALLING OPTIONAL BRICK LINER MODEL BL32D WARNING If fireplace has been running turn off and un plug fireplace Let cool before installing brick liner This brick liner kit is optional You may pur chase brick liner from your local retailer or see page 37 CAUTION Always handle brick panels with two hands Do not force b...

Page 9: ... Do not modify logs Only use logs supplied with fireplace Open louvers remove screen unlock door latches and open glass door See steps 1 and 2 of Removing Glass Door page 24 Install logs according to instructions for fireplace model numbers 1 Place log 1 rear log on top of grate Make sure notches in bottom of log fit over grate see Figure 45 2 Rest log 2 large front log on pins on front part of grate...

Page 10: ...AD BEFORE LIGHTING WARNING If you do not fol low these instructions exactly a fire or explosion may result causing property damage per sonal injury or loss of life A This appliance is equipped with an ignition device which automatically lights the pilot Do not try to light the pilot by hand B BEFORE LIGHTING smell all around the appliance area for gas Be sure to smell next to the floor because some ...

Reviews: