background image

104463-01E

For more information, visit www.desatech.com

For more information, visit www.desatech.com

5

5

AIR FOR COMBUSTION AND
VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR
HEATER LOCATION

Determining if You Have a Confined or
Unconfined Space

Use this work sheet to determine if you have a confined or uncon-
fined space.

Space:

 Includes the room in which you will install heater plus any

adjoining rooms with doorless passageways or ventilation grills
between the rooms.

1.

Determine the volume of the space (length x width x height).

Length x Width x Height = _________ cu. ft. (volume of space)

Example:

  Space size 20 ft. (length) x 16 ft. (width) x 8 ft.

(ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills
or openings, add the volume of these rooms to the total vol-
ume of the space.

2.

Multiply the space volume by 20 to determine the maximum
Btu/Hr the space can support.

_________________ (volume of space) x 20 = (maximum

Btu/Hr the space can support)

Example:

  2560 cu. ft. (volume of space) x 20 = 51,200 (maxi-

mum Btu/Hr the space can support)

3.

Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

_______________ Btu/Hr

Gas water heater*

_______________ Btu/Hr

Gas furnace

_______________ Btu/Hr

Vented gas heater

_______________ Btu/Hr

Gas fireplace logs

_______________ Btu/Hr

Other gas appliances*

+ ______________ Btu/Hr

Total

= ______________ Btu/Hr

* Do not include direct-vent gas appliances. Direct-vent draws
combustion air from the outdoors and vents to the outdoors.

Example:

Gas water heater

40,000

Btu/Hr

Vent-free heater

+

30,000

Btu/Hr

Total

=

70,000

Btu/Hr

 WARNING: If the area in which the heater may be

operated is smaller than that defined as an uncon-
fined space or if the building is of unusually tight
construction, provide adequate combustion and ven-
tilation air by one of the methods described in the
National Fuel Gas Code, ANSI Z223.1/NFPA 54, Sec-
tion 5.3 or applicable local codes.

4.

Compare the maximum Btu/Hr the space can support with the
actual amount of Btu/Hr used.

_____________ Btu/Hr (maximum the space can support)

_____________ Btu/Hr (actual amount of Btu/Hr used)

Example:

51,200 Btu/Hr (maximum the space can support)

70,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the
actual Btu/Hr used is more than the maximum Btu/Hr the space can
support. You must provide additional fresh air. Your options are as
follows:

A. Rework worksheet, adding the space of an adjoining room. If

the extra space provides an unconfined space, remove door to
adjoining room or add ventilation grills between rooms. See
Ventilation Air From Inside Building, page 6.

B. Vent room directly to the outdoors. See Ventilation Air From

Outdoors, page 6.

C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room

unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space
can support, the space is an unconfined space. You will need no
additional fresh air ventilation.

AIR FOR COMBUSTION AND VENTILATION

Determining Fresh-Air Flow for Heater Location

Summary of Contents for SL30NT Series

Page 1: ...ncy or the gas supplier WARNING This is an unvented gas fired heater It uses air oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be pro vided...

Page 2: ...id any drafts that alter burner flame patterns Ceiling fans can create drafts that alter burner flame patterns Altered burner patterns can cause sooting WARNING Do not use a blower insert heat exchang...

Page 3: ...n burner box or on adjacent walls or furniture 10 This heater needs fresh outside air ventilation to run properly This heater has an Oxygen Depletion Sensing ODS safety shutoff system The ODS shuts do...

Page 4: ...orless passageways or ventilation grills between them WARNING This heater shall not be installed in a confined space or unusually tight construction unless provisions are provided for adequate com bus...

Page 5: ...ent gas appliances Direct vent draws combustion air from the outdoors and vents to the outdoors Example Gas water heater 40 000 Btu Hr Vent free heater 30 000 Btu Hr Total 70 000 Btu Hr WARNING If the...

Page 6: ...unconfined space When ventilating to an adjoining unconfined space you must provide two permanent openings one within 12 of the ceiling and one within 12 of the floor on the wall connecting the two s...

Page 7: ...from floor ceil ing and adjoining side and back walls Carefully follow the instructions below This stove is a freestanding unit designed to set directly on the floor IMPORTANT You must maintain minimu...

Page 8: ...include 1 Stove bottom 4 Legs 1 Bottom door 1 Top grate 1 Hardware kit bag with fasteners 6 Carefully lay stove body on back to attach bottom components to stove body see Figure 6 Rest stove on drop...

Page 9: ...8 page 8 Use an adjustable wrench or a 12mm socket The catch bolt has two hex nuts attached to it see Figure 12 The top nut is a bolt stop and the bottom nut is for door leveling adjustment 12 Check g...

Page 10: ...rough stove bottom Connect hex nut to bolt on underside of stove bottom The bolt hex head is for a 5 16 socket and the hex nuts are for a 3 8 socket If sockets are not available use adjustable wrenche...

Page 11: ...Purchase the optional CSA design certified equipment shutoff valve from your dealer See Accessories page 19 The gas inlet connection for the stove heater is located on the lower right hand side of the...

Page 12: ...ct all leaks at once 6 Reconnect heater and equipment shutoff valve to gas supply Check reconnected fittings for leaks Test Pressures Equal To or Less Than 1 2 PSIG 3 5 kPa 1 Close equipment shutoff v...

Page 13: ...cluding near the floor If you smell gas STOP Fol low B in the safety information above If you don t smell gas go to the next step 5 Turn control knob counterclockwise C clockwise to the PI LOT positio...

Page 14: ...aning easier 1 Shut off the unit including the pilot Allow the unit to cool for at least thirty minutes 2 Inspect burner pilot and primary air inlet holes on injector holder for dust and dirt see Figu...

Page 15: ...ND MAINTENANCE Continued CLEANING AND MAINTENANCE Logs Main Burner SPECIFICATIONS 4 Check the injector holder located at the end of the burner tube again Remove any large particles of dust dirt lint o...

Page 16: ...trol valve 6 Thermocouple damaged 7 Control valve damaged REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Replace ignitor cable 4 Repl...

Page 17: ...d let warm up for a minute 2 Operate burner until air is removed from line Have gas line checked by local natural gas company 3 Observe minimum installation clear ances see page 7 4 Clean burner see C...

Page 18: ...s a clicking ticking noise just after burner is lit or shut off Heater produces unwanted odors Heater shuts off in use ODS operates Gas odor even when control knob is in OFF position Gas odor during c...

Page 19: ...ur model and serial numbers of your heater ready You can also visit DESA International s technical service web site at www desatech com SERVICE HINTS When Gas Pressure Is Too Low pilot will not stay l...

Page 20: ...r more information visit www desatech com For more information visit www desatech com 20 ILLUSTRATED PARTS BREAKDOWN SL30NT 14 16 3 4 15 5 11 6 12 7 10 15 8 9 1 17 2 18 18 18 13 ILLUSTRATED PARTS BREA...

Page 21: ...Gas Regulator 1 6 104425 01 Inlet Tube 1 7 104424 01 Outlet Burner Tube 1 8 099056 26 Burner Orifice Injector 1 9 111124 01 Burner Retainer Spring 1 10 102980 01 Burner 1 11 101329 21 Control Valve 1...

Page 22: ...For more information visit www desatech com For more information visit www desatech com 22 ILLUSTRATED PARTS BREAKDOWN CISC CISG 7 4 6 4 5 4 5 1 5 2 3 5 3 5 4 2 1R 1C 1L ILLUSTRATED PARTS BREAKDOWN CI...

Page 23: ...een 1 3 104174 03 Stove Dropped Bottom 1 4 104970 01 One Leg Charcoal 4 Total Per Stove 1 104970 02 One Leg Forest Green 4 Total Per Stove 1 5 104971 01 Hardware Kit 1 5 1 Door Hinge Step Bolt With Sh...

Page 24: ...9 Adams Street Bowling Green KY 42103 3414 270 846 1199 1 800 654 8534 Fax 1 800 846 0090 franktalk aol com Master Parts Dist 1251 Mound Ave NW Grand Rapids MI 49504 2672 616 791 0505 1 800 446 1446 F...

Page 25: ...Completed College Completed Graduate School 13 Age of Purchaser Under 20 20 29 30 39 40 49 50 59 60 or Over 14 Buyer s total annual household income Under 15 000 15 000 to 19 999 20 000 to 34 999 35 0...

Page 26: ...104463 01E For more information visit www desatech com For more information visit www desatech com 26 2701 Industrial Drive P O Box 90004 Bowling Green KY 42102 9004 TM Postage Required TAPE TAPE...

Page 27: ...________________________________________________________ _______________________________________________________________________________________________ _______________________________________________...

Page 28: ...ement parts voids this warranty The heater MUST be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit This warranty does not apply to parts...

Reviews: