background image

Comfortflame.US.com

900563-00NC

8

AIR FOR COMBUSTION AND VENTILATION  

Confined and Unconfined Space

The National Fuel Gas Code, ANSI Z223.1/NFPA 54 defines a confined 

space as a space whose volume is less than 50 cubic feet per 1,000 

Btu per hour (4.8 m

3

 per kw) of the aggregate input rating of all ap-

pliances installed in that space and an unconfined space as a space 

whose volume is not less than 50 cubic feet per 1,000 Btu per hour 

(4.8 m

3

 per kw) of the aggregate input rating of all appliances installed 

in that space. Rooms communicating directly with the space in which 

the appliances are installed*, through openings not furnished with 

doors, are considered a part of the unconfined space.
* Adjoining rooms are communicating only if there are doorless 

passageways or ventilation grills between them.

DETERMINING FRESH-AIR FLOW FOR FIREBOX LOCATION
Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or uncon-

fined space.

Space:

 Includes the room in which you will install heater plus any 

adjoining rooms with doorless passageways or ventilation grills 

between the rooms.
1.  Determine the volume of the space (length x width x height).
  Length x Width x Height = __ cu. ft. (volume of space)
  Example: Space size 22 ft. (length) x 18 ft. (width) x 8 ft. (ceiling 

height) = 3168 cu. ft. (volume of space)

  If additional ventilation to adjoining room is supplied with grills 

or openings, add the volume of these rooms to the total volume 

of the space. 

2.  Multiply the space volume by 20 to determine the maximum Btu/

Hr the space can support.

   _____ (volume of space) x 20 = (Maximum Btu/Hr the space can 

support)

  Example: 3168 cu. ft. (volume of space) x 20 = 63,360 (maximum 

Btu/Hr the space can support)

3.  Add the Btu/Hr of all fuel burning appliances in the space.
  Vent-free heater 

 ______Btu/Hr

  Gas water heater*   ______Btu/Hr
  Gas furnace 

 ______Btu/Hr

  Vented gas heater   ______Btu/Hr
  Gas fireplace logs   ______Btu/Hr
  Other gas appliances* + ____Btu/Hr
 Total 

= _____Btu/Hr

  * Do not include direct-vent gas appliances. Direct-vent draws 

combustion air from the outdoors and vents to the outdoors.

  Example:
  Gas water heater     40,000 Btu/Hr
  Vent-free heater  + 39,000 Btu/Hr
 Total 

79,000 Btu/Hr

4.  Compare the maximum Btu/Hr the space can support with the 

actual amount of Btu/Hr used.

   ________ Btu/Hr (maximum the space can support) 
   ________ Btu/Hr (actual amount of 
   

Btu/Hr used)

  Example:  63,360 Btu/Hr (maximum the space can support) 

   

  79,000 Btu/Hr (actual amount of Btu/Hr used)

 WARNING: This heater shall not be installed in a 

room or space unless the required volume of indoor 

combustion air is provided by the method described 

in the National Fuel Gas Code, ANSI Z223.1/NFPA 54, 

the International Fuel Gas Code, or applicable local 

codes. Read the following instructions to insure proper 

fresh air for this and other fuel-burning appliances in 

your home.

Today’s homes are built more energy efficient than ever. New materi-

als, increased insulation and new construction methods help reduce 

heat loss in homes. Home owners weather strip and caulk around 

windows and doors to keep the cold air out and the warm air in. 

During heating months, home owners want their homes as airtight 

as possible.
While it is good to make your home energy efficient, your home needs 

to breathe. Fresh air must enter your home. All fuel-burning appliances 

need fresh air for proper combustion and ventilation.
Exhaust fans, fireboxes, clothes dryers and fuel burning appliances 

draw air from the house to operate. You must provide adequate fresh 

air for these appliances. This will insure proper venting of vented 

fuel-burning appliances.

PROVIDING ADEQUATE VENTILATION 

The following are excerpts from National Fuel Gas Code, ANSI Z223.1/

NFPA 54, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three following ventilation 

classifications:
1.  Unusually Tight Construction
2.  Unconfined Space
3.  Confined Space
The information on page 8 through 10 will help you classify your 

space and provide adequate ventilation. 

Unusually Tight Construction

The air that leaks around doors and windows may provide enough 

fresh air for combustion and ventilation. However, in buildings of 

unusually tight construction, you must provide additional fresh air.

Unusually tight construction is defined as construction where:
a.  walls and ceilings exposed to the outside atmosphere have a 

continuous water vapor retarder with a rating of one perm (6 x 

10

-11

 kg per pa-sec-m

2

) or less with openings gasketed or sealed 

and

b.  weather stripping has been added on openable windows and 

doors and

c.  caulking or sealants are applied to areas such as joints around 

window and door frames, between sole plates and floors, be-

tween wall-ceiling joints, between wall panels, at penetrations 

for plumbing, electrical and gas lines and at other openings. 

If your home meets all of the three criteria above, you must provide 

additional fresh air. See Ventilation Air From Outdoors, page 9. 
If your home does not meet all of the three criteria above, proceed 

to Determining Fresh-Air Flow for Firebox Location. 

Summary of Contents for Cumberland32XWS

Page 1: ... codes This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for use with other gases WARNING For use only with a listed gas fired unvented decorative room heater not to exceed 40 000 Btu H Do not build a wood fire WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death or property...

Page 2: ...ervice 17 Replacement Parts 17 Accessories 18 Parts 20 Warranty 27 TABLE OF CONTENTS Thank you for your purchase We appreciate your business Please carefully read and follow all instructions in this manual Pay special attention to all warnings and safety information Following these safety care and operation instructions will help ensure many years of dependable and enjoyable service from your fire...

Page 3: ...sary if installed in place LOCAL CODES Install and use heater with care Follow all local codes In the absence of local codes use the latest edition of The National Fuel Gas Code ANSI Z223 1 NFPA 54 Firebox must be electrically grounded in accordance with the National Electrical Code ANSI NFPA70 latest edition Available from American National Standards Institute Inc 25 West 43rd Street 4th floor Ne...

Page 4: ... of the fireplace or vent free gas logs OPTIONAL FIBER AND PORCELAIN LINERS For a vintage look the fiber panels give a old masonry brick look and are light weight and easy to install For a modern look the porcelain panels accessory have a black sleek finish that reflects the glow of the flame OPTIONAL OUTSIDE AIR KIT The optional AK4 and AK4F air kit provides additional outdoor air to improve burn...

Page 5: ...s 32 Models 32 MODELS 7 5 8 6 7 8 6 7 8 8 1 8 13 1 8 3 1 4 3 1 2 3 1 2 10 1 2 12 1 2 10 1 2 8 1 4 8 1 4 24 36 1 2 34 1 2 18 1 4 32 1 4 2 1 2 16 5 8 4 3 8 36 3 8 7 7 29 3 8 6 22 1 2 19 1 2 Right Side View Left Side View Front View Outside Air Kit Location Electrical Outlet Firebox Top View ...

Page 6: ...igure 2 Product Specifications 36 Models 10 3 8 8 3 8 7 3 8 26 3 8 8 1 4 8 1 4 13 7 8 21 1 8 8 1 8 34 7 8 36 1 8 41 1 8 21 43 7 6 25 8 1 2 8 1 2 3 1 4 40 1 4 11 1 2 2 1 2 29 1 8 Right Side View Left Side View Front View Firebox Top View Outside Air Kit Location Electrical Outlet ...

Page 7: ...duct Specifications 42 Models 36 1 8 6 50 40 40 24 27 1 8 23 1 4 22 1 4 44 1 4 3 1 4 8 1 4 14 1 4 8 1 4 7 5 8 12 5 8 2 1 2 10 1 2 10 3 4 13 3 8 10 1 2 2 1 2 7 1 8 41 7 8 48 1 8 3 1 8 4 1 2 Right Side View Left Side View Front View Firebox Top View Outside Air Kit Location Electrical Outlet ...

Page 8: ...e can support 79 000 Btu Hr actual amount of Btu Hr used WARNING This heater shall not be installed in a room or space unless the required volume of indoor combustion air is provided by the method described in the National Fuel Gas Code ANSI Z223 1 NFPA 54 the International Fuel Gas Code or applicable local codes Readthefollowinginstructionstoinsureproper fresh air for this and other fuel burning ...

Page 9: ...confined space When ventilating to an adjoining unconfined space you must provide two permanent openings one within 12 of the ceiling and one within 12 of the floor on the wall connecting the two spaces see options 1 and 2 Figure 4 You can also remove door into adjoining room see option 3 Figure 4 Follow the National Fuel Gas Code ANSI Z223 1 NFPA 54 Air for Combustion and Ventilation for required...

Page 10: ...eate the easiest installation Use dimensions shown for rough openings to create the easiest installation see Built In Firebox Installation page 11 INSTALLATION CLEARANCES WARNING Maintaintheminimumclearances Ifyou can provide greater clearances from floor ceiling and adjoining wall Carefully follow these instructions This will ensure safe installation Minimum Wall and Ceiling Clearances see Figure...

Page 11: ...ns in Figures 8b 8c and 8d for rough opening 2 Install gas piping to firebox location See Installing Gas Line page 12 and Connecting to Gas Supply in log set owner s manual Figure 7 Minimum Mantel Clearances for Built In Installation Supplied Firebox Hood Must Be Used at All Times Wire mesh Screen Firebox Noncombustible Material May Project Off this Surface above the Firebox Hood Mantel Shelf Note...

Page 12: ... hole you have made to smooth edges This hole will line up with the hole in the outer casing CAUTION Donotuseexcessiveforcetoremovethe knockout Too much force may damage the firebrick concrete insert Figure 9 Attaching Firebox to Wall Studs Model May Vary From Illustration Nailing Flanges Nails or Wood Screws IMPORTANT If installing blower accessory see Wiring Instructions page 13 3 Carefully set ...

Page 13: ... 2 sheet metal screws as shown in Figure 12 2 Slide power source wiring through electrical bushing opening and electrical cover plate and make all necessary connections 3 Slide all wiring connections in electrical housing as shown in Figure 12 4 Secure electrical cover plate with screws previously removed Note Electrical housing and cover plate have sharp edges Wear protective gloves Figure 11 Loc...

Page 14: ...ccessory BK can now be installed If accessing thru the louver opening remove bottom louver panel by simultaneously pulling both top end spring latches towards center of appliance until they are disengaged from locating holes see Figure 13a Repeat for bottom spring latches and pull louver outward To install or replace items removed simply reverse procedures above WARNING If there is a duplex electr...

Page 15: ...nted crawl space AK4F or through a sidewall AK4 See Figure 19 CAUTION Combustion air inlet ducts shall not terminate in attic space Figure 19 Outside Air Kit Secure to Collars with Metal Tape Screws or Straps Min of 1 4 x 20 in size Air Inlet Location Must Allow For Bushes or Snow Vent Hood Required for Wall Installation Air Inlet Eyebrow Vented Crawl Space Check Local Codes Before Installing in a...

Page 16: ... hood to firebox using screws provided see Figure 20 2 Insert each rod through all rings located at top of screen 3 Insert first rod into rear hole in left side of firebox Fasten rod to rear hole near center of firebox using 10 x 3 8 Phillips screw provided see Figure 21 4 Insert other rod into front hole on right side of firebox and fasten using remaining Phillips screw LOCATING ACCESS COVER PLAT...

Page 17: ...o visit our web site at Comfortflame US com REPLACEMENT PARTS See Pages 20 to 23 for a complete replacement parts list Use only parts supplied from the manufacturer Normally all parts should be ordered through your IHP distributor or dealer Parts will be shipped at prevailing prices at time of order When ordering repair parts always give the following information 1 The model number of the fireplac...

Page 18: ... WITH FULL HEARTH BASE For all models Space saving mantel and hearth base corner design Complete assembly instructions included Note No 42 mantels offered at this time F1140 W32TU 32 Wall Cabinet Mantle Traditional Style Unfinished Oak F1141 W32TO 32 Wall Cabinet Mantle Traditional Style Light Oak Stain J3490 W32CO 32 Wall Cabinet Mantle Classic Style Oak Stain J3492 W32GO 32 Wall Cabinet Mantle G...

Page 19: ... Style Unfinished Oak F1147 C36TO 36 Corner Cabinet Mantle Traditional Style Light Oak Stain UNIVERSAL CABINET MANTEL Fits 36 Models Note No 42 mantels offered at this time NOT SHOWN F1152 LACMO Large Universal Cabinet Mantle Dark Oak Stain F1155 LACMW Large Universal Cabinet Mantle Dark Walnut Stain PERIMETER TRIM F1039 PT32 32 Perimeter Trim Kit Black F1040 PT32B 32 Perimeter Trim Kit Brushed Br...

Page 20: ...mfortflame US com 900563 00NC 20 1 2 3 4 5 6 7 8 PARTS CATALOG NO MODEL F2558 Cumberland32YWS F2559 Cumberland32XWS F2560 Cumberland36YWS F2561 Cumberland36XWS F2562 Cumberland42YWS F2563 Cumberland42XWS ...

Page 21: ...een 2 2 K2001 Screen Rod 2 J3975 Screen Rod 2 J4084 Screen Rod 2 3 J4956 Push On Nut 2 4 J4183 Hood Deflector 1 J4090 Hood Deflector 1 J4092 Hood Deflector 1 5 J6918 Spacer Top 4 6 J6934 Cover Gas Conduit 5 7 J4387 Electrical Duct assembly 1 8 J4052 Panel Access 2 AVAILABLE NOT SHOWN J8141 Louver Assembly 36 2 J7588 Louver Assembly 42 2 J8142 Louver Assembly 32 2 WARNING Contact an IHP dealer to o...

Page 22: ...omfortflame US com 900563 00NC 22 1 2 3 4 5 6 6 PARTS CATALOG NO MODEL F2558 Cumberland32YWS F2559 Cumberland32XWS F2560 Cumberland36YWS F2561 Cumberland36XWS F2562 Cumberland42YWS F2563 Cumberland42XWS ...

Page 23: ...ry White Stack 1 4 J4195 Bottom Rear Refractory White Stack 1 J6372 Bottom Rear Refractory White Stack 1 J6386 Bottom Rear Refractory White Stack 1 5 J4198 Bottom Front Refractory White Stack 1 J6374 Bottom Front Refractory White Stack 1 J6387 Bottom Front Refractory White Stack 1 6 J5185 Retainer Refractory 2 PARTS This list contains replaceable parts used in your firebox When ordering parts foll...

Page 24: ...________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _____________________________________...

Page 25: ...________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _____________________________________...

Page 26: ...________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _____________________________________...

Page 27: ... will cause damage to the Product will produce excessive temperatures and could result in a fire hazard c damages caused by failing to provide proper maintenance and service in accordance with the instructions provided with the Product d damages repairs or inefficiency resulting from faulty installation or application of the Product IHP is not responsible for inadequate fireplace system draft caus...

Page 28: ...ns pricesandalsotodiscontinuecolors stylesandproducts Consult your local distributor for fireplace code information Printed in U S A 2015 IHP LLC P N 900563 00 Rev N C 09 2015 1508 Elm Hill Pike Suite 108 Nashville TN 37210 Model Number Serial Number Date Installed Dealer s Name Dealer s Phone Number Keep receipt for warranty verification P900563 00 ...

Reviews: