508146-01
Issue 2051
Page 15 of 7
0
•
Initiate furnace ignition sequence and move to and
hold mid-fire rate by applying a jumper to R and W2.
•
Apply then remove the jumper from R to W1 and W2
to change the firing rate from low fire to mid fire and
high fire.
•
A vent calibration sequence can be initiated even if a
thermostat signal is not present. Press and hold the
push button until a solid “C” is displayed. Release
the button and calibration will begin. The furnace will
perform the high-fire and low-fire pressure switch
calibrations and display “CAL”. After calibration, the
LED will return to the flashing “-” display.
During Field Test mode operation, all safety switches
are still in the circuit (they are not by-passed) and indoor
blower performance and timings will match DIP switch
selections. Current furnace firing rate, indoor blower CFM
and flame signal will be displayed. To exit the Field Test
mode, press and hold the button. The menu will resume
from the beginning. Also, cycle the main power to exit the
Field Test mode. The integrated control will automatically
exit the Field Test mode after 45 minutes of operation.
Soft Disable
Soft disabling is when thermostat finds a device on the
BUS that it does not recognize and the thermostat sends
a the device a message to be in soft disabling mode until
properly configured. Two horizontal bars will display.
Steps to follow if the damper control module is displaying
the soft disable code.
1.
Confirm proper wiring between all devices (thermostat,
damper control module, indoor and outdoor).
2.
Cycle power to the control that is displaying the soft
disable code.
3.
Put the room thermostat through set up.
4.
Go to setup / system devices / thermostat / edit / then
push reset.
5.
Go to setup / system devices / thermostat / edit / then
push resetAll.
These options are displayed on the menu when the button is pressed during normal operation
Display
Action (when button is released)
No change (idle)
Remain in idle mode
Solid “E”
Enter diagnostic mode
Solid “-”
Enter field test mode
NOTE - No change implies the display will continue to show whatever is currently being displayed for normal operation
Table 10. Idle Menu Options
These options are displayed when the button is used in Field Test Mode
Display
Action (when button is released)
No change (blinking “-”)
Remain in field test mode
Solid “-”
Exit field test mode
Solid “c”
Start pressure switch calibration
Table 11. Field Test Menu Options
These options are displayed when the button is used in diagnostic recall mode
Display
Action (when button is released)
No change (displaying error history)
Remain in diagnostic recall mode
Solid (3 horizontal bars)
Exit diagnostic recall mode
Solid “c”
Clear error history
Once the button is released to clear the error history a blinking “c” will be shown on the display for up to 10 seconds. During this
time the user must press and release the button one additional time to confirm the action of deleting the error history. Once the error
history is deleted it cannot be recovered.
Table 12. Diagnostic Recall Menu Options