507715-01
Page 52 of 61
Issue 1716
GUH92A 070*B3 Performance (Less Filter)
External
Static
Pressure
in. w.c.
Air Volume / Watts at Various Blower Speeds
High
Medium-High
Medium-Low
Low
cfm
Watts
cfm
Watts
cfm
Watts
cfm
Watts
0.00
1615
680
1355
570
1140
480
1030
400
0.10
1565
660
1365
545
1150
465
1020
385
0.20
1535
630
1340
525
1150
440
1025
375
0.30
1440
600
1300
500
1110
420
1000
350
0.40
1405
570
1255
470
1075
400
975
345
0.50
1340
535
1200
445
1045
380
945
330
0.60
1255
500
1125
420
995
355
875
310
0.70
1165
475
1080
395
935
335
820
290
0.80
1060
455
990
365
870
315
750
265
0.90
955
425
895
345
750
285
660
245
GUH92A 090*C3 Performance (Less Filter)
External
Static
Pressure
in. w.c.
Air Volume / Watts at Various Blower Speeds
High
Medium-High
Medium-Low
Low
cfm
Watts
cfm
Watts
cfm
Watts
cfm
Watts
0.00
1620
745
1340
620
1130
500
965
405
0.10
1610
720
1335
595
1135
490
975
395
0.20
1565
695
1335
565
1145
465
970
385
0.30
1525
665
1300
555
1135
455
970
370
0.40
1485
635
1295
520
1110
435
960
355
0.50
1430
600
1260
495
1090
405
940
345
0.60
1365
570
1210
475
1035
390
900
330
0.70
1295
535
1155
445
995
365
860
305
0.80
1200
505
1065
415
930
340
745
270
0.90
1060
460
955
375
820
305
695
260
GUH92A 090*C4 Performance (Less Filter)
External
Static
Pressure
in. w.c.
Air Volume / Watts at Various Blower Speeds
High
Medium-High
Medium-Low
Low
cfm
Watts
cfm
Watts
cfm
Watts
cfm
Watts
0.00
2025
900
1690
780
1395
645
1200
540
0.10
1995
880
1705
760
1390
635
1205
525
0.20
1925
835
1675
715
1405
605
1205
505
0.30
1850
795
1640
680
1400
580
1170
490
0.40
1790
760
1575
645
1395
560
1170
475
0.50
1700
725
1540
625
1350
535
1140
450
0.60
1610
690
1455
580
1295
505
1100
430
0.70
1540
645
1365
550
1225
480
1030
405
0.80
1415
615
1265
510
1125
445
980
385
0.90
1270
565
1165
470
1060
420
900
350
NOTE
: All air is measured external to unit without filter (filter not furnished - field provided)