COMFORT-AIRE Century RSG13 Installation And Start-Up Instructions Manual Download Page 6

Page 6 of 9

507708-01

Issue  1337

Cooling Cycle Charge Adjustment Procedure

Units with Indoor Pistons

  Units installed with indoor pistons require charging 

with the superheat method.

  The following procedure is valid when indoor airflow is 

within ± 20 % of its rated CFM.

  1.   Operate unit a minimum of 10 minutes before 

checking charge.

  2.   Measure suction pressure by attaching a gage to  

suction valve service port. Determine saturation 

temp from T/P chart.

  3.   Measure suction temperature by attaching an  

accurate thermistor type or electronic thermometer 

to suction line at service valve.

  4.   Calculate superheat (measured temp. - saturation 

temp.) .

  5.   Measure outdoor air dry-bulb temperature with 

thermometer.

  6.   Measure indoor air (entering indoor coil) wet-bulb 

temperature with a sling psychrometer.

  7.   Compare superheat reading at service valve with 

the chart located on control box cover.

  8.   If unit has a higher suction line temperature than 

charted temperature, add refrigerant until charted 

temperature is reached,

  9.   If unit has a lower suction line temperature than 

charted temperature, reclaim refrigerant until 

charted temperature is reached.

  10.  Remove charge if superheat is low and add charge 

if superheat is high.

Units with Indoor TXV

  Units installed with cooling mode TXV require charging 

with the subcooling method.

  1.   Operate unit a minimum of 10 minutes before 

checking charge.

  2.   Measure liquid service valve pressure by  

attaching an accurate gage to service port.  

Determine saturation temp. from T/P chart.

  3.   Measure liquid line temperature by attaching an 

accurate thermistor type or electronic thermometer 

to liquid line near outdoor coil.

  4.   Calculate subcooling (saturation temp. - measured 

temp.) and compare to table on back of control box 

cover. 

  5.   Add refrigerant if subcooling is lower than range 

shown in table. Recover refrigerant to decrease 

subcooling.

  6.   If ambient temp. is lower than 65° F, weigh  

refrigerant according to the name plate data.

NOTE:  If a TXV is installed on indoor unit, a hard start 

kit will be required on all models with  

reciprocating compressors. Refer to the  

specification sheet for details. Hard start kits 

are also recommended for areas with utility 

power lower than 208 Vac.

SYSTEM OPERATION

The outdoor unit and indoor blower cycle on demand 

from the room thermostat. When the thermostat blower 

switch is in the ON position, the indoor blower operates 

continuously.

Filter Drier

The filter drier is very important for proper system

operation and reliability. If the drier is shipped loose, it

must be installed by the installer in the field. Unit warranty

will be void, if the drier is not installed.

Summary of Contents for Century RSG13

Page 1: ...tion and Canadian Electrical Code Part 1 CSA WARNING Safety Precautions 2 Unit Location Installation 2 Rooftop Installation Recommendations 3 Indoor Coil Piston Selection 3 Refrigeration Line Sets 3 Installation of Line Sets 4 Leak Check 4 Evacuating Charging 4 P507708 01 TABLE OF CONTENTS Electrical Connections 5 Control Wiring 5 Start Up Procedure 5 Adjusting charge 5 Single Phase Wiring Diagram...

Page 2: ... In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit away from windows patios decks etc where unit operation sounds may disturb customer 2 Ensure that vapor and liquid tube diameters are appropriate to capacity of unit 3 Run refigerant tubes as directly as possible by avoiding unecessary turns and bends 4 Leave some slack b...

Page 3: ...ance less than 2 ft from a second uni With clearance less than 4 ft on top of unit Indoor Coil Piston Selection The outdoor section must be matched to a factory approved indoor section It is mandatory that the installer ensure that the correct piston or TXV is installed in the indoor section If necessary remove the existing piston and replace it with the correct piston or TXV See indoor unit instr...

Page 4: ... for leaks after brazing and before evacuation The recommended procedure is to apply a trace amount of vapor refrigerant approximately two ounces or 3 psig into the line set and indoor coil then pressurize with 150 psig of dry nitrogen Use a refrigerant leak detector to check all joints The system may also be checked for leaks using a halide torch or pressure and soapy solution After completion of...

Page 5: ... wire to ground connection in control box for safety Connect power wiring to contactor High voltage power connections to 3 phase models is made to Pig Tail leads with field supplied splice connectors Contol Wiring The control voltage is 24 VAC NEC Class I insulated 18 AWG is required for control wiring For lengths longer than 150 feet contact your local distributor for technical service Ensure the...

Page 6: ...its with Indoor TXV Units installed with cooling mode TXV require charging with the subcooling method 1 Operate unit a minimum of 10 minutes before checking charge 2 Measure liquid service valve pressure by attaching an accurate gage to service port Determine saturation temp from T P chart 3 Measure liquid line temperature by attaching an accurate thermistor type or electronic thermometer to liqui...

Page 7: ...507708 01 Page 7 of 9 Issue 1337 534773W A C SINGLE PHASE WIRING DIAGRAM Single speed condenser fan ...

Page 8: ...Page 8 of 9 507708 01 Issue 1337 A C SINGLE PHASE WIRING DIAGRAM Multi speed condenser fan 537511 01 ...

Page 9: ...rees can be drawn into coils by movement of the air Clogged condenser coils will lower the efficiency of your unit and cause damage to the condenser Periodically debris should be brushed from the condenser coils SHARP OBJECT HAZARD WARNING Condenser coils have sharp edges Wear adequate body protection on body extremities e g gloves FAILURE TO FOLLOW THIS WARNING COULD RESULT IN BODILY INJURY Use a...

Reviews: