  IE-SNC-T4211-01 

LCD Info mode 

Several settings of installed transmitter is possible to verify without a use of the computer. It is 

necessary to connect power. 

Unscrew  the  transmitter  lid  and  shortly  press  button  between  display  and  interconnection 

terminals by means of a tool (e.g. screwdriver). 

 

Range and type of value for output 1 (Uout 1 = symbol „1“on display). Type 
of  value,  assigned  to  output  1,  is  indicated  by  displayed  unit  (here  °C). 
Upper  line  displays  voltage  value  corresponding  to  measured  value  (lower 
line). Here 0V corresponds to ambient temperature -30 °C. 
 
 
After  next  press  of  the  button  value  for  upper  point  appears,  here  10  V 
corresponds to ambient tempe80 °C. 
 
Press button again to end info mode and display actual measured values. 

 

Notice:

  during  info  mode  no  measurement  and  no  output  voltage  generation  proceed.  The 

transmitter stays at info mode 15 s, and then automatically goes back to measuring cycle. 

 

 
 

Readings on LCD display 

°C, °F    

  Reading next to this symbol is measured temperature or error state of value. 

 
 
 

Procedure of modification of transducer adjustment: 

 

Device adjustment is performed by means of the optional SP003 communication cable, 
connected to USB port of the PC. 

 

It  is  necessary to  have installed configuration program  Tsensor on the PC. It is free to 
download  at  www.cometsystem.cz.  During  installation  please  take  care  about 
installation of driver for  USB communication cable. 

 

Connect SP003 communication cable to the PC. Installed USB driver detect connected 
cable and create virtual COM port inside the PC. 

 

Unscrew four screws of the device lid a remove the lid. If device is already installed to 
measuring system, disconnect leads from terminals. 

 

Connect  SP003  communication  cable  to  the  device.  Display  must  light  up,  or  at  least 
must  light  up  all  symbols  for  one  second  (if  LCD  was  switched  OFF  by  program 
before).  

 

Run installed Tsensor program and select corresponding communication COM port (as 
described above). 

 

When new setting is saved and finished, disconnect the cable from the device, connect 
leads into its terminals and place the lid back to the device. 

 
 