background image

 

 

 

  IE-HGS-N-H302x-02 

 

 

 

 

H302x regulators 

 with relay outputs                                                                                          

 

 

PRODUCT DESCRIPTION   

 

Programmable  regulators 

with  relay  outputs  are  designed  to  measure  temperature  and  relative  humidity  of  air  in  non-aggressive 

environment, to alarm indication and to control of external devices. Regulators are available in wall-mount and duct-mount versions or 
with probe on a cable. For measuring temperature and relative humidity of compressed air is used type HxxxxP.  

 

Two output relays

 functions can be set from regulator keyboard or from computer. Each relay can be assigned to one of measured or 

computed  value  (dewpoint  temperature,  absolute  humidity,  specific  humidity  mixing  ratio  and  specific  enthalpy).  Setting  of  delay, 

hysteresis, audible alarm is enabled for each relay.

 

Measured and calculated values are displayed on a two-line display. Using 

TSensor 

software (see 

www.cometsystem.cz/software.htm

) can be all regulator parameters set. To connect to PC is used USB adapter SP003 

(optional accessories). 

 
 

 

type * 

 

measured values    

 

construction 

 

 

 

mounting 

 

H3020 

 

T + RH + CV 

 

ambient air 

 

 

 

wall  

H3023 

 

T + RH + CV 

 

duct mount 

  

 

 

wall  

H3021

 

   

T + RH + CV 

 

probe with a cable   

 

 

wall  

H3021P   

T + RH + CV  

 

probe with a cable 

– pressure up to 25 bars  

wall  

 

f

  

*  models marked Hxxxx

Z

 are custom - specified devices 

 

 

 

                T…temperature, RH…relative humidity, CV…computed values  

 

 

 
 

INSTALATION AND OPERATION

 

 

The mounting holes and connection terminals are accessible after unscrewing the four screws in the corners of case and removing the 
lid.  Devices  have  to  be  mounted  on  a  flat  surface  to  prevent  its  deformation.  Pass  cables  (external  diameter  3  to  6.5  mm)  through  

released glands and connect wires according to diagram. Wire cross-section choose from 0,14 to 1.5mm

2

. Tighten glands and screw the 

lid. Insert attached plug into unused cable glands too. Pay attention to device mounting, because incorrect choice of working position or 
place of measuring could adversely affect accuracy and long-term stability of measured values. 

 

Actual parameters settings of each relay can be displayed by pressing of „ ▲“ key. To change any parameter, press the „

Set

“ key, enter 

password (default 0000) and set required value. Then click on „

Set

“ and pressing „

Esc

“ key exit setup mode. To change the password 

and to set all other parameters (alarm settings, used units, computed value selection etc.) is used 

Extended setting mode

 (see manual 

for devices at 

www.cometsystem.cz/manuals.htm

). 

 

 

Devices don´t require special maintenance. We recommend you periodic calibration for measurement accuracy validation.

 

  

 

 

ERROR STATES 

 

Device continuously checks its state during operation and if an error appears, it is displayed relevant code: 

Err 0

 – it is a serious error, please contact distributor of the device 

Err 1

 – measured or calculated value is over the upper limit 

Err 2 

– measured or calculated value is below the lower limit 

Err 3

 – it is a serious error, please contact distributor of the device 

Err 5 

– there is problem with assigned value to output relay  

Err 6 

– there is problem with assigned value to output relay  

Err 9

 – inserted password is not valid 

 

 

 

 
 

SAFETY INSTRUCTIONS  

 

 

-   Humidity and temperature sensors of the regulator can not be operate and store without a filter cap. 

-  Temperature and humidity sensors have not to be exposed to direct contact with water and other liquids. 
-   It is not recommended to use the humidity regulators for long time under condensation conditions. 
-   Take care when unscrewing the filter cap as the sensor element could be damaged. 

-   Don’t connect or disconnect devices while power supply voltage is on. 
-  If the sensing probe of H3021P regulator is installed, make sure that measured area is without pressure. 
-   Installation, electrical connection and commissioning should be performed by qualified personnel only. 

-   Devices contain electronic components, it needs to liquidate them according to currently valid conditions. 
-   For more information, please use detailed manuals and other documentation which are available at 

www.cometsystem.cz/manuals.htm 

or 

www.cometsystem.cz/software.htm

 

 