7
Profile
Setting
Active channels
Channels with active ventilation
CH1, CH2 and CH3
CH 4
CH1, CH2 and CH3
CH4
S 0
YES
NO
NO
-
S 1
YES
YES
YES
YES
S 2
YES
YES
NO
NO
S 3
YES
NO
YES
-
S 4
Each channel can be activated as well as the relative ventilation
Display request
sequence
Profile
Description
A nnn
0,1,2,3
Setting of the alarm threshold common to the
channels activated by profile selection (see previous
table)
t nnn
0,1,2,3
Setting of the trip threshold common to the channels
activated by profile selection (see previous table)
L nnn
1,3
Setting of the ventilation stop threshold common to
the channels activated by profile selection (see
previous table)
H nnn
1,3
Setting of the ventilation start threshold common to
the channels activated by profile selection (see
previous table)
NOTE
For profiles 0, 1, 2 and 3, the settings include one single alarm
threshold and one single release threshold common to all activated
channels.
The ventilation setting (profiles 1 and 3) will also have common
thresholds.
Profile 4 is useful when maximum flexibility is required since any
combination of active channels can be selected, while activation of
the alarm and release thresholds and ventilation can be set for these
channels independently.
Once the required operating profile has been selected, it must be
confirmed by pressing the key.
Programming proceeds with a request for entry of the alarm and
release thresholds and, for the profiles concerned, entry of the
ventilation activation and deactivation thresholds as shown in the
table.
PROG
CHANGE