Comelit ILS-2 Manual Download Page 17

 

17 

 

8 Maintenance 

 

With normal use, the filter element will eventually become contaminated with dust particles contained in the 
extracted air. It is recommended that the filter element (code 02-FL53) is replaced and detectors cleaned 
every 6 months (more frequently for dirty environments). 

 
Note: 

maintenance should be performed by authorised personnel. Before carrying out any maintenance, notify 

the proper authorities and isolate (disable) the unit to prevent incorrect alarm statuses from being 
triggered on the monitoring and signalling control panel.

 

 
Please follow the steps illustrated when performing a maintenance check on the system: 

 

1.  Remove the transparent cover using the special tool provided. 
2.  Disconnect the unit from the power supply. 
3.  Lift  out  the  filter  element  from  the  inlet  pipe  (long-nosed  pliers  are  recommended  for  this 

operation). 

 

4.  Fit the new filter element, ensuring that it is not compressed during fitting. Fit it inside the pipe so that the 

top surface of the filter is positioned flush with the pipe.  

5.  Remove the point detector(s) from the mounting base by twisting them anti-clockwise. 
6.  Remove the detector cover by prying away the 4 side tabs with a small-bladed flathead screwdriver. 

 

7.  Carefully  vacuum  the  inside  of  the  point  detector.  If  further  cleaning  is  required  continue  with  Step  8, 

otherwise skip to Step 12. 

8.  Remove the mesh insect screen and the optical chamber by pulling them out. 
9.  Clean the chamber again by vacuuming or blowing out dust and dirt particles. 
10.  Replace the optical chamber cover, aligning the arrows on the top with the arrow on the printed circuit board.  

  

11.  To replace the mesh insect screen, place it on the grooves over the optical chamber, turning it until it snaps 

into place. 

12.  Replace the plastic cover using the status LED holes to align the cover. 
13.  Reinstall the detector onto its mounting base, ensuring that it is in the SAME POSITION (address 1 fitted 

to detector 1 position). 

 

14.  Refit the transparent plastic cover, restore the power supply and carry out the Flow Calibration procedure.  
15.  Restore the relays’ enabled status. 

Summary of Contents for ILS-2

Page 1: ...1 ASPIRATING SMOKE DETECTOR 1 ZONE 2 DETECTORS ILS 2...

Page 2: ...ed The following typographic conventions are used in this manual Convention Description Bold Used to indicate emphasis used for menu names menu options toolbar icons Italic Used to indicate links to o...

Page 3: ...1 Piping specifications 7 4 2 Fixing 7 4 3 Bends 7 4 4 End caps 8 4 5 Sampling holes 8 4 6 Air outlet 8 4 7 Filters 8 4 8 Standard pipe configurations 9 5 Detectors 9 6 2 User functions 11 6 3 Setup n...

Page 4: ...installed by authorised personnel in accordance with local and national regulations Remove the transparent cover using the keys provided and loosen the fasteners Use the template to position the fixin...

Page 5: ...n the speed of the fan used for the application please refer to Table 11 2 Current Consumption vs Fan Speed 3 1 2 ACTION 2 ACTION 1 Relay output The voltage free contacts of the relay ACTION ACTION wi...

Page 6: ...6 3 1 5 External Reset The application of a voltage of 24 Vdc to these terminals triggers a reset of all fault and alarm events present...

Page 7: ...uted by clean air from other sampling holes and from the end cap hole 4 1 Piping specifications In accordance with EN54 20 standards the pipes must be red ABS and conform to EN 50086 1 Crushing 1 Impa...

Page 8: ...bris through to the end of the pipe in the latter case you will need to fit the end cap afterwards In standard applications the sampling hole faces downwards 4 6 Air outlet The extracted air after bei...

Page 9: ...y and the fan speed set to 9 maximum The use of bends as described in section 4 3 will have a minimal effect on performance e g response time Note the abovementioned values are based on EN54 20 certif...

Page 10: ...SMOKE DETECTOR FAULT detector fault 1 per detector ISOLATE Disabled relays not active AIRFLOW OK HIGH AIRFLOW LOW AIRFLOW POWER ON Power supply present FAN FAULT Fan fault GENERAL FAULT General fault...

Page 11: ...d one at a time e g press the CHANGE button six times to illuminate the number 5 LED on the display then press the SELECT button etc the CODE LED flashes during this procedure the Unlock LED will ligh...

Page 12: ...Set the delay in FLOW HIGH and LOW LEDs 2 See table paragraph 6 3 3 indication of flash together FLOW FAULT Set ALERT threshold The ALERT LED flashes 3 Set threshold for The ACTION LED 5 ACTION flash...

Page 13: ...13 sensors...

Page 14: ...gue values from the TWO detectors exceed the relevant thresholds Notes Mode 3 is not permitted in installations which require VdS approval ILS 2 is supplied in standard mode 1 If required jointly the...

Page 15: ...the calibrated reading for at least the duration of the flow fault indication delay see section 6 3 2 above For most installations especially if compliance with EN54 20 is required the default setting...

Page 16: ...r cover This test electronically simulates the effect of smoke in the optical chamber 7 2 System Before checking the system as a whole make sure the top cover of the unit is in place As a minimum requ...

Page 17: ...pipe so that the top surface of the filter is positioned flush with the pipe 5 Remove the point detector s from the mounting base by twisting them anti clockwise 6 Remove the detector cover by prying...

Page 18: ...Class C Class B Class A 1 18 6 3 100 2 9 3 1 100 3 4 1 N A 100 4 1 N A N A 100 5 or higher N A N A N A N A Note table 9 1 shows the limit that should not be exceeded for the 3 sensitivity classes Fig...

Page 19: ...cover is fitted properly and the enclosure is fully sealed Make sure the airflow calibration procedure has been carried out see section 6 2 Make sure the filter is in good condition see section 8 Flo...

Page 20: ...length of pipes 100 m Protection rating IP65 with air outlet piping installed IP23 without Operating temperature range From 10 to 50 C Operating humidity From 10 to 95 RH non condensing Certifications...

Page 21: ...21...

Reviews: