corispondenza del Led Giallo , il relè ALARM 1 con il 3° Led rosso e il relè ALARM 2 con il Led ALARM. Poi dopo 5 
secondi la centralina torna automaticamente in funzionamento normale. 

NOTE

: la funzione si attiva su tutti i canali anche se disabilitati o con Fault e/o 1° e/o 2° Led Rosso accesi. Ma non 

è utilizzabile se uno o più ingressi sono oltre il 10%LEL (3° e/o 4° Led accesi). 

 

EN

 

 DESCRIPTION 

The 

47CPZ003

 is a control unit for heating plants or environments to be protected from possible gas leaks, 

which can 

be connected up to 3 remote catalytic detectors for flammable gases. It can be connected to the following detectors:

 

 The 47SE192KM should be used in plants using Methane. 

 The 47SE192KG should be used in plants using LPG.  

The 

47CPZ003

 is for wall mounting and the protection code is IP65. It is mains powered at 110÷240VAC / 50÷60Hz 

but can also be connected either to an external 24VDC power supply (e.g. p

ower supply unit with two 12V-7A/h buffer 

batteries

). 

On the front plate, there are three vertical Led bars that indicate the operating status and gas concentration detected 
by each remote detector and two 

function keys (

TEST e RESET

). 

The control unit has two alarm  levels with sealed relay outputs  (

ALARM1 e ALARM2

), with tension free changeover 

contacts. Furthermore, it is also present another output relay  (

FAULT

) in positive safety for fault situations, and an 

auxiliary input (

AUX

), configurable as an input to connect NO contact devices such as a 

manual Button

 or as a control 

input for 

Manual NC Resetting Valve with positioning sensor

In Fig.1

 a connection example with 3 remote gas detectors, siren, manual reset solenoid valve and manual button. 

OPERATIONAL DESCRIPTION 

Preheating

: when 

the control unit is powered, the 60 seconds preheating phase begins. This is only for the enabled 

inputs (remote detector installed), on the corresponding Led Bar, the yellow LED flashes and at the end of the pre-
heating, the green LED "

ON

" lights up. 

Normal operating

the control  unit reads the  gas concentration through the remote gas  detectors of the  enabled 

inputs and displays the status on the corresponding Led Bar.

 

The Green LED 

lights up 

to indicate the normal operation and the presence of power 

1

st

 Red LED: 

lights up

 if the gas concentration exceeds 4% LEL. 

2

nd

 Red LED: 

lights up

 if the gas concentration exceeds 8% LIE. 

3

nd

 Red LED (

ALARM 1

): 

lights up

 if the gas concentration exceeds 

the 1

st

 alarm threshold (configurable to 10 or 

15% LEL)

 and 

within 5 seconds the 

ALARM 1

 relay will activate. This relay is normally used as a prealarm using a 

siren.

 

4

st

 Red LED (

ALARM 2

): 

lights up

 if the gas concentration exceeds 

the 2

nd

 alarm threshold

 (20% LEL); if the gas 

persists, after 30 seconds,  the red LED 

ALARM 2

 

lights up

 and the 

ALARM 2

 relay will activate. It 

is configurable in 

positive (normally excited) or negative logic. 

It is normally used to stop the gas through the manual reset solenoid 

valve and/or the interruption of the electrical power at the plant only, 

the control unit must remain powered. 

If the manual button is connected to the AUX input, when pressed, the 

ALARM 2

 relay will be activated. 

If it has been installed a manual reset solenoid valve N.C. with magnetic sensor 

connected to “

AUX

” input, in the case that the gas is still 

open, the yellow LED and the 

FAULT

 Relay will activate (see 

FAULTS

 section). 

“RESET” Key:

 

this key has two functions: 

SILENCING

  : 

when  the  key  is  pressed,  the  3

rd

  Red  LED  on  the  alarm  channel  flashes  and  the 

ALARM 1

  relay 

connected to the Siren is silenced, but after 120 seconds, it will automatically reactivate.

 

RESET: 

if  the  2

nd

  alarm  threshold  is  exceeded,  the 

ALARM 2

  relay  and  the  channel  LED  bar  in  alarm 

remains 

activated (

latched

), even if the  gas concentration decreases (

because the mounted valve  is closed

, if installed). 

After having eliminated the cause of the alarm, to restore the normal working conditions press the 

RESET

 key. For 

safety

, the key cannot operate when the remote detector is detecting gas. 

Faults

The control unit indicates a fault condition of a remote gas detector

, with 

the yellow LED on the corresponding 

channel and the 

FAULT

 relay 

will activate. This relay 

is 

normally energized with voltage-free changeover contacts

, if 

necessary, it can be used both to signal remotely an occurred damage and to signal the absence of power to the 
instrument. 

Fault signals must not be connected to the alarm signals.

 

Manual reset solenoid valve NC with magnetic sensor failure: 

this situation appears 

ONLY

 when is installed an electro 

valve with magnetic sensor; if it not close the gas, (with the 

ALARM 2

 relay in alarm), the magnetic sensor signals to the control unit the 

malfunction. In this case all LED will be lighted and relays will be activated. The failure condition (yellow led lighted and 

FAULT

 relay activated) 

will be cancelled if pressing the 

RESET

 key, the solution of the problem will be visualized.

 

INSTALLATION 

The control unit and detectors should be installed 

according to the national disposition in force on the matter.  

Positioning:

 

The control unit must be installed in an accessible location, easily visible and away from heat sources. 

The control unit cannot be installed outdoors. 

Please  note  that  for  safety,  the  control  unit  is  to  be  installed  in  safe  areas  where  there  are  present  or  can  form 
flammable atmospheres and concentrations exceeding 24 % volume oxygen. 
The remote detectors:
 

it has to be installed as described in the specific instructions attached with it. After the instal-

lation and referred to the gas indicated on the testing label of the remote 

gas detector

, apply on the 

47CPZ003

, the 

self-sticking label with the name of the detected gas inserted 

in the package

Summary of Contents for 47CPZ003

Page 1: ...10 50 60Hz 6VA Alimentazione ausiliaria Auxiliary power supply Alimentation auxiliaire 24VDC 10 15 9W Rilevatore remoto Remote detector Sonde ext rieure Catalitico Catalityc Catalytiques Ingressi Inpu...

Page 2: ...il pulsante manuale collegato all ingresso AUX se premuto viene attivato il rel ALARM 2 Se stata installata un Elettrovalvola a Riarmo Manuale NC con Sensore di posizione collegata all ingresso AUX ne...

Page 3: ...SENSOR 2 e SENSOR 3 il n 4 non utilizzato e la sua posizione non ha effetti sul funzionamento ON Ingresso ABILITATO il Rilevatore installato la Barra Led e i rel di Fault e Allarme sono in funzione PE...

Page 4: ...hold 20 LEL if the gas persists after 30 seconds the red LED ALARM 2 lights up and the ALARM 2 relay will activate It is configurable in positive normally excited or negative logic It is normally used...

Page 5: ...you must configure the Dip Switches on the circuit in the housing cover Enable Disable SW1 Dip Switches No 1 No 2 No 3 enable or disable the corresponding input of the remote gas detector SENSOR 1 SEN...

Page 6: ...concentration de gaz rejoint 8 de la LIE La 3 me LED rouge ALARM 1 s allume lorsque la concentration de gaz rejoint le 1er seuil d alarme Configurable 10 ou 15 de la LIE et apr s 5 secondes le 1er rel...