Specifications
16
Input (programmable)
Outputs:
- OUT1
- OUT2
- OUT3
Electromechanical relay
SSR
MOS gate
Output for external SSR
- OUT1
- OUT2
- OUT3
Serial Interface
USB Interface
Control Algorithm
Alarms
Power Supply
Consumption
Measurement Error
Temperature Drift
Ambient Temperature / Humidity
Protection / Insulation
Pt100, 10 T/C types, mA, mV, V, k
Ω
up to 3
alarm AL1,
control OUT1
none,
alarm AL2,
control OUT2
none,
alarm AL3
5A/250VAC with NO contact
1A/250VAC
0.1A/60V, optically isolated
5...24 VDC, 30 mA
relay,
SSR,
MOS gate,
for ext. SSR,
0
÷
20 mA,
4
÷
20 mA,
0
÷
5 V,
0
÷
10 V
relay,
SSR,
MOS gate,
for ext. SSR
relay,
SSR,
MOS gate,
for ext. SSR
RS485 with MODBUS RTU/ASCII protocol
mini-A connector for parameter Read/Write
PID-fuzzy or ON/OFF
11 alarm types plus 2 system alarms
85…265 VAC
less than 4 VA
≤
±
0.3% from span
≤
±
0.01% from span for 1 °C
0…50 °C / 20…85% RH,
IP10 / >10 M
Ω
at 500 VDC
Warranty and Support
………………………….
serial number
………………………….
manufacturing date
QC check mark …….……(passed)
(stamp)
88 Slavyanska Str.
P.O.Box 378
Plovdiv 4000, BULGARIA
tel: +359 32 646523, 646524
fax: +359 32 634089, 646517
e-mail: [email protected]
QD-8.2.4-WC
Warranty
COMECO warrants this product to be free
from defects in materials and workmanship
for 2 years. If your unit is found to be
defective within that time, we will promptly
repair or replace it. This warranty does not
cover accidental damage, wear or tear, or
consequential or incidental loss. This
warranty does not cover any defects caused
by wrong transportation, storage, installation,
or operating (see '
Specifications
').
Technical support
In the unlikely event that you encounter
a problem with your COMECO device,
please call your local dealer or contact
directly our support team.
COMECO Inc., P.O.Box 378, Plovdiv 4000, BULGARIA, tel: +359 32 646523, 646524, fax: 634089
e-mail: [email protected], WWW.COMECOGROUP.COM
RT1900-R
O PER A T ION MAN U AL
Please read this Operation Manual before mounting and operating!
Save the Manual for future references!
Communication
14
Serial network interface
If serial interface is installed,
follow the additional
requirements given in
RT1800 Communication
Manual available from
www.comeco.org/downloads
(Software->Communication
Prots->Rt1800).
Read/Write parameters
Regardless of installed serial
interface, RT1900-R is
equipped with an independent
parameter copy system via
USB interface and IA400
converter.
All parameters can be copied,
saved and transferred to
other units using 'Parameter
Copy' free software.
Error Messaging
Message Error type
in1E
sensor error
AdCF
ADC failure *
CJCE
Input measurement or CJC failure *
UUU1
measured value above high SV limit
(parameter
USPL
)
nnn1
measured value below low SV limit
(parameter
LSPL
)
rAMF
RAM (memory) failure *
intF
interface problem
AUtF
unsuccessful auto-tuning
WARNING!
When a message marked
with (*) appears and stays,
return the unit for repair!
Overview
3
RT1900-R is a DIN-rail mounting controller with universal input accepting Pt100, 10
T/C types and various linear signals. It can have up to 3 relays (control or alarm) and
analog output that may be controlled through ON/OFF and self-tuning PID-fuzzy
algorithms as well as optional RAMP/SOAK pattern control. A bumpless auto-manual
change-over is also built in the PID algorithm. RT1900-R is equipped with 4-digit LED
display and 4-button keyboard for programming. A triple input/output/supply isolation
protects the controller from electro-magnetic disturbances. Communication features
include RS485 MODEBUS interface and USB port for program parameter storage.
RT1900-R is well equipped for trouble-free operation in harsh industrial conditions.
Mounting
♦
RT1900-R can be mounted on
every 33-mm rail confirming EN
50022.
♦
Install RT1900-R following the
steps 1-2 as shown on the left.
♦
Always observe device
dimensions (W40xH107xD43)
before installation!
♦
Uninstall Rt1900-R using a
suitable screwdriver and
following the steps 1-2 as
shown on the left picture.
♦
If install 2 or more units on the
same rail, use the enclosed
plastic spacer to provide
adequate air cooling distance
following the marks on the left.
Never place units without a
gap (min. 5mm) between them or
other rail-mounted devices!
It may result in overheating and
device failure!
UNIVERSAL PID CONTROLLER
v
1
-0
9
.1
2