It will reset PA and then re-detect the PA output power and reflected power, if they are normal, the PA
Service Status will turn to
Normal
, if PA output power or reflected power is still over the threshold, PA
Service Status will turn to
Recovery
again.
If PA output power or reflected power is still over the threshold after six times of PA Recovery, PA
Service status will be
Shutdown
which will need to be reset manually. Reset at Management > PA
Reset.
Figure 31: RF Unit Detail Information
5.2.2
[COMMISSIONING]
A work flow of the commissioning process is shown on [Commissioning] Screen. Click the [Start] button,
the software will guide you through the commissioning step by step. For details, please refer to chapter
5.3.
Figure 32: [Commissioning] Screen
Click 800MHz to
check
Alarm information and
configuration table of
800MHz RFU
RF parameter setting
table of 800MHz RFU