3.2.2 Inactive warning
When a warning becomes inactive,
O04 Alarm
and
O15 Common Warning
output will open, the red
LED above
STOP
button will stop blinking, and the warning symbol on main screen will go out.
Figure 3.5
inactive warning
– Low Battery
3.3
Shutdowns
3.3.1 Shutdown procedure
The
InteliNano
NT
controller opens outputs
O05 GCB Close/Open
,
O01 Starter
,
O08 Prestart
and
O02 Fuel Solenoid
and closes
O03 Stop Solenoid
to stop the engine immediately.
O04 Alarm
and
O16 Common Shutdown
outputs are closed. Active or not confirmed shutdowns are blocking next
start of gen-set.
3.3.2 Active unconfirmed shutdown
When a shutdown occurs, the
Shutdown procedure
will start, the red LED above
STOP
button
blinks, the shutdown symbol will blink in the upper right corner of LCD, and the proper shutdown
symbol is displayed in history with running hours stamp. The record in history is inversed, see
For shutdown alarm confirmation press
STOP
button.
Figure 3.6
active unconfirmed shutdown
– Emergency Stop
3.3.3 Active confirmed shutdown
When an active shutdown is confirmed the red LED above the
STOP
button stops blinking. The record
in history stays inversed with confirmation symbol at the end.
O04 Alarm
and
O16 Common
Shutdown
outputs are open.
Figure 3.7
active confirmed shutdown
– Emergency Stop
3.3.4 Inactive unconfirmed shutdown
O04 Alarm
and
O16 Common Shutdown
o utputs are closed, red LED above
STOP
button blinks.
Shutdown symbol is displayed in upper-right corner of the LCD, and proper warning symbol is
displayed in history with running hours stamp. See
For shutdown alarm confirmation press
STOP
button.
Figure 3.8
inactive unconfirmed shutdown
– Emergency Stop