4
Start and Stop engine
4.1 MANUAL mode
Green LED above
AUTO
button is off (controller is in MANUAL mode). When there is no any active
shut down alarm you can start the engine by pressing
START
button. Green LED above button will
blink. LED is blinking during starting, cooling or stopping procedure. When the engine is properly
started, the green LED will stop blink and start lights continuously. The generator is ready to load.
When you press
START
button again the GCB will close
– only when the GCB is configured.
Press
STOP
button to stop the engine. First press will open the GCB and next press start cooling and
stopping procedure. When you press this button again the controller will stop the engine immediately.
For fast engine stop press and hold
STOP
button till engine stops.
4.2 AUTO mode
Green LED above
AUTO
button is on (controller is in AUTO mode). You can’t start the engine or
connect the load by pressing
START
button. The controller will start automatically when all conditions
for start and connecting
load will be reached. The engine in AUTO mode can’t be stopped by pressing
STOP
button.
Engine can be started or stopped via binary inputs
I02 Remote Start/Stop
or
I03 Remote Start And
Load
. For more details see InteliNano
NT
MRS 3 Reference Guide.